7.17 Start-up report
Identifying the operating objective conditions is useful to control the unit over time.
With unit at steady state, i.e. in stable and close-to-work conditions, identify the following data:
•
total voltages and absorptions with unit at full load
•
absor
ptions of the diff
erent electric loads (compressors, fans, pumps etc)
•
temperatures and fl w
s of the diff
erent fluids ( ater, air) both in input and in output from the unit
•
temperature and pressures on the characteristic points of the refrigerating circuit (compressor discharge, liquid, intake)
The measurements must be kept and made available during maintenance interventions.
7.18 2014/68/UE PED directive
DIRECTIVE 2014/68/UE PED gives instructions for installers, users and maintenance technicians as well.
Refer to local regulations; briefly and as an xample, see the following:
Compulsory verific tion of the first install tion:
•
only for units assembled on the installer’s building site (for ex. Condensing c direct expansion unit)
Certific tion of setting in service:
•
for all the units
Periodical verific tions:
•
to be executed with the frequency indicated by the Manufacturer (see the “maintenance inspections” paragraph)