6.
9
Modbus - RS485
Option
LED BSP
communication with AP1 module
LED BUS
communication with Modbus
green
communication ok
green
communication ok
yellow
software ok but communication with AP1
down
yellow
startup / channel not communicating
red
flashing: software error
red
communication down
fixed: hardware error
A. Unit
B. Metal conduit
C. Metal septums
D. Metal-lined sheath (sleeve)
Modbus / LonWorks / BACnet Cable requirements
Couple of conductors twisted and shielded
Section of conductor 0,22mm2…0,35mm2
Rated power between conductors < 50 pF/m
Nominal impedance 120 Ω
Recommended cable BELDEN 3106A
•
Every RS485 serial line must be set up using the ‘In/Out’ bus system.
•
Other types of networks are not allowed, such as Star or Ring networks.
•
The
diff
erence in potential between the earth of the two RS485 devices that the cable shielding needs to be connected to must be
lower than 7 V
•
There must be suitable arresters to protect the serial lines fr
om the eff
ects of atmospheric discharges
•
A 120 ohm resistance must be located on the end of the serial line. Alternatively, when the last serial board is equipped with an
internal terminator, it must be enabled using the specific jumpe
r
, dip switch or link.
•
The cable must have insulation features and non-flame p
r
opagation in accordance with applicable regulations.
•
The RS485 serial line must be kept as far away as possible from sources of electromagnetic interference.
23
Summary of Contents for MSE-XSC3 100.4
Page 1: ...MSE XSC3 90 4 160 4 Installation and operating manual...
Page 3: ...Index of contents 1 4 2 6 3 8 4 10 5 14 6 18 7 26 8 35 9 47 10 52 11 53 12 54 57 3...
Page 19: ...Connections performed by the Customer 19...
Page 50: ...9 15 Compressor replacement 50...
Page 51: ...9 16 Exchanger replacement 51...