7.13 Demand limit
Menu accessible only after having entered the password.
Access reserved only to specifically t
r
ained personnel.
The parameter modific
a
tion can cause irreversible damages.
It is possible to limit the absorbed electric power with an external signal 0-10 Vcc.
The higher the signal is, the lower the number of compressors available to meet the thermal need.
If only P0002: EnDemandLimit ≠ 0
Path: Main Menu / Unit parameters / Demand limit
Step Display
Action
Menu/Variable
Keys
Notes
1
Press 3 sec.
2
Password
Set
Password
3
Press
4
Main menu
Select
Unit parameters
5
Unit parameters
Select
Set Point
6
Set Point
Select
Demand limit
7
Set
Demand limit
8
Confirm
9
Press 3 sec.
10
Select
Local connections
Path: Main Menu / Unit parameters / Demand limit
Parameters
Short description
description
P0200
setpointdemandlimit Parameter setting of the value % of demand limit
28