pag
25
SOLO FAN
In the main menu, holding both keys
HEAT
and
COOL
pressed the SOLO FAN mode is activated. To restore the machine
standard operation repeat this step.
The SOLO FAN indication is displayed with the unit in solo fan mode, instead of the outlet temperature.
PARAMETER MODIFY
1
Push SET button
2
Select the
parameter
3
Modify the value
4
Select another
parameter
5
SET to esc
ACCESSIBLE PARAMETERS FROM KEYPAD
Accessibile parameters
Num. Control
parameters
Mnemonic
Value UM
1
Enables manual selection of the operating mode
OnModeMan
1
Flag
4
Enables manual ambient setpoint
OnSetMan
1
Flag
5
Manual ambient Setpoint
ManSet
23
°C
7
Setpoint compensation: outside temperature 0
Text0
15
°C
8
Setpoint compensation: outside temperature 1
Text1
18
°C
9
Setpoint compensation: outside temperature 2
Text2
21
°C
10
Setpoint compensation: outside temperature 3
Text3
24
°C
11
Setpoint compensation: outside temperature 4
Text4
30
°C
12
Setpoint compensation: value 0
set-00
19
°C
13
Setpoint compensation: value 1
set-01
21
°C
14
Setpoint compensation: value 2
set-02
23
°C
15
Setpoint compensation: value 3
set-03
25
°C
16
Setpoint compensation: value 4
set-04
27
°C
26
Supply SetPoint in the winter operating
SetOutHeat
21
°C
30
RH SetPoint in the winter operating
SetURHeat
55
%
40
Supply SetPoint in the summer operating
SetOutCool
25
°C
66
Air quality Set point
SetCO2
900
%
97
RH Set point in the summer operating
SetURCool
60
%
ALARM DISPLAYING
1
blinking
alarm code
alarm machine hours
2
alarm log access short
pressing
ALARM
3
the most recent alarm is
displayed
to display further alarms
arrow keys
4
to quit
short pressing
ALARM
5
to RESET
ALARM HOLD PRESSED
AL
AR
M
STA
TU
S
SE
T
AL
AR
M
ST
AT
US
SE
T
AL
AR
M
ST
AT
US
SE
T
AL
AR
M
STA
TU
S
SE
T
AL
AR
M
ST
AT
US
SE
T
AL
AR
M
STATU
S
SET
E 11
2
AL
AR
M
ST
ATUS
SE
T
AL
AR
M
STA
TUS
SE
T
AL
AR
M
ST
ATUS
SE
T
AL
AR
M
ST
ATU
S
SE
T