background image

 

 pag 

17 

START-UP 

ALL THE EQUIPMENT MUST BE COMMISSIONED BY AUTHORISED SERVICE CENTRES. 

THIS SERVICE IS LIMITED TO START-UP OF THE UNIT ONLY AND NOT THE CONNECTIONS OR INSTALLATION OF 

THE SYSTEM. 

ONLY QUALIFIED TECHNICIANS MUST PERFORM THE FOLLOWING OPERATIONS. 

 

PRELIMINARY CHECKS  

Before checking, please verify the following  
1.  the unit should be installed properly and in conformity 

with this manual. 

2.  the electrical power supply line should be sectioned at 

the beginning. 

3.  the sectioning device is locked and the proper warning 

“not to operate” sign is placed on the handle.  

4.  make sure no tension is present  
5.  the coils must be clean and free of obstacles  
6.  the ventilators must be free of leaves, cardboard, fixed 

obstacles (beams, barriers, etc.), snow, etc  

7.  the external ventilators must not be blocked  

 

The external ventilators can be subject to a temporary 
block, especially if the inactivity period before the first 
start-up was quite long or if external temperature is 
very low. It is also possible to unblock them manually 
(ONLY WHEN THE UNIT IS UNPLUGGED  – RISK 
OF INJURES) so that jams or electric overloads  are 
avoided when the unit is restarted.  

AERAULIC SYSTEM 

Check that:  

1.  the air filters are not removed from unit and are 

cleaned (possible ventilation checks and the operating 
starting period determinate a ducting “cleaning” with 
conseguent filter precocius clogging, filters that must 
be cleaned and replaced) 

2.  ducting are completed, connected and without 

obstructions 

3.  possible dampers are opened (for ex. fire stop 

dampers) and calibrated (for ex. external air damper, 
control damper, ejection damper) 

4.  Grilles, outlets, and diffusers must be free of 

obstructions (furniture, shelves, etc.), open and pre-
calibrated, so as to ensure proper air distribution, 
which is essential to comfort in the room.  

REFRIGERANT SYSTEM 

Carefully check the refrigerating circuit: the presence of oil 
stains can mean leakage caused by transportation, 
movements or other). 
Open the cocks of the refrigerator circuit, if there are any. 
Using the unit manometers, if present, or service 
manometers, verify that the refrigerating circuit is in 
pressure. 
Make sure that all the service outlets are closed with 
proper caps; if caps are not present a leak of refrigerant 
can be possible.

 

WATER SYSTEM 

Ensure that the plumbing system has been washed. Drain 
the wash water before connecting the unit to the system. 

Check that the water circuit has been filled and 
pressurised. 
Perform a seal check at max. working pressure checking 
that no leaks are present. 
Check that the shut-off valves in the circuit are in the 
"OPEN" position.  
Check that there is no air in the circuit. If required, bleed it 
using the vent valves in the system. 
Check that there are no ARIES EFFECTS in the transient 
(pump and / or valve  activation/deactivation) 
When using antifreeze solutions, make sure the glycol 
percentage is suitable for the type of use envisaged.  
% weight of ethylene 
glycol 

10 % 

20 % 

30 % 

40 % 

Freezing point 

- 4 °C 

- 9 °C  - 15 °C - 23 °C

Safety temperature 

- 2 °C 

- 7 °C  - 13 °C - 21 °C

 
Check that the circulator pumps are not blocked. In fact, 
their motor shaft may seize up, especially after long 
shutdowns. Unblocking can be accomplished with a 
screwdriver using the purge hole.  

ELECTRICAL SYSTEM 

Check the proper tightening of the screws that fix the 
conductors to the electrical components in the board 
(during handling and transportation, the vibrations could 
have loosened them). 
Verify that the unit is connected to the ground plant.  
Control that all panels and protection devices of the unit 
are repositioned and blocked. 
Charge the unit by closing the sectioning device, but leave 
it on OFF. 
Make sure that the tension and net frequency values are 
within the limit of: 
230 +/- 6% single phase unit; 400/3/50 +/- 6% three-phase 
unit 
Control the unbalancing of the phases: it must be lower 
than 2% . 
Example:  
L1 - L2 = 388 V,    L2 - L3 = 379 V,   L3 - L1 = 377 V   
average of the measured values = (388 + 379 + 377) / 3 = 
381 
maximum deviation from the average = 388-381= 7V 
Unbalancing = (7/381) x 100 = 1.83%  = ACCEPTABLE 
Operating out of the indicated limits causes the loss of the 
guarantee as well as very serious damages.  

 
 

 

Summary of Contents for CPAN-U-17

Page 1: ...CPAN U 17 21 25 31 41 51 ELFOFRESH LARGE Make up unit full fresh air Installation and Use Manual M25E40P5 11 22 04 14...

Page 2: ......

Page 3: ...MAINS 15 FUNCTIONAL CONNECTIONS 15 SYSTEM COMPOSITION 16 S T A R T U P 1 7 PRELIMINARY CHECKS 17 AERAULIC SYSTEM 17 REFRIGERANT SYSTEM 17 WATER SYSTEM 17 ELECTRICAL SYSTEM 17 VERIFy tensions absorpti...

Page 4: ...This provides unique identification of the machine It makes it possible to trace the specific features of the unit and to identify the components installed in it Without this number it is not possible...

Page 5: ...pressed SUMMER WINTER MODE CHANGE Key hold pressed The key is not operative if the unit is set for the automatic operating mode under such conditions the AUTO indication is displayed SOLO FAN Holding...

Page 6: ...e instructions given in this manual will cause the warranty to lapse INTENDED USE The unit must only be used for the specific purpose it was designed The unit is designed for civil air conditioning wi...

Page 7: ...L RISKS A smell of burning smoke or other indications of serious irregularity could signal the onset of situations liable to cause damage to persons or property or to the unit itself Isolate the unit...

Page 8: ...0 in weight CEE No Non applicable for mixtures Commercial name 03 Hazard identification Hazard identification Liquefied gas Vapours are heavier than air and can cause choking by reducing the oxygen av...

Page 9: ...alve if supplied is correctly assembled Verify that the cap if supplied is well assembled and that there is adequate ventilation Verify that the norms in force are respected 15 Information on the norm...

Page 10: ...es which activate the safety valves HANDLING The operation of handling the unit must be carried out respecting the instructions of the safety norms in force Legislative Decree 626 94 and following mod...

Page 11: ...s must be doubled POSITIONING 1 The units are designed for INDOOR installations performed in fixed positions and in areas accessible only to qualified and authorized personnel 2 SAFETY VALVE only if p...

Page 12: ...IONS SUPPORTS The weight of the hydraulic connections must be supported in the exterior of the unit so as not to stress the connections of user devices exchangers coils humidifiers etc ANTI VIBRATION...

Page 13: ...cs pressure inclusive between 0 1 and 0 8 Mpa 1 8bar temperature inclusive between 1 and 40 C Do not use softened water it may cause corrosion of the electrodes and foaming resulting in malfunctions f...

Page 14: ...ak off the short circuit power whose value should be determined according to the plant features The section of supply cables and protection cable must be seized according to the characteristics of the...

Page 15: ...cess is reserved to authorized assistance centres in order to avoid unauthorized modifications ON OFF FROM REMOTE CONTROL Generally the unit is delivered with bridged terminals if the control is not u...

Page 16: ...ions available on the machine keyboard SERIAL CONVERTER TTL RS485 OPTIONAL code PE6B0020 The supervision services are available with standard modbus protocol Plugged in in the main module on the elect...

Page 17: ...er Open the cocks of the refrigerator circuit if there are any Using the unit manometers if present or service manometers verify that the refrigerating circuit is in pressure Make sure that all the se...

Page 18: ...condensation pressure increases The phase optional monitor which controls the phase sequence can be installed later REMOTE INPUT CONFIGURATIONS Check used remote inputs are activated ON OFF etc as giv...

Page 19: ...tilation EXTERNAL temperature 10 C 35 C OFF OFF ON AMBIENT temperature 16 C 30 C OFF OFF ON OUTLET temperature OPERATING MODES SUMMER WINTER MODE MODE CHANGE MANUAL The choice between the HEATING or t...

Page 20: ...acing them of 1 C respect the manual set COOLING 24 C HEATING 22 C AUTOMATIC AMBIENT SET POINT The set point can also be adjusted AUTOMATICALLY to the external temperature variations the variation cur...

Page 21: ...t alarms are reset holding the buttons ECO and Clean pressed KEY LOCK All button functions can be locked by holding the buttons Clean and On Off pressed The lock is signalled by the characters wheneve...

Page 22: ...by the ALARM CODE blinking and by the machine time it they occurred The cumulative lock relay activates simultaneously with the alarm code displaying Some alarms typically PRE ALARMS do not activate...

Page 23: ...ess Dehumidification signalling with reduced flow rate E33 Recovery compressor lockout for low enthalpy ambient air temperature heat mode Automatic Recovery compressor lockout and ventilation lockout...

Page 24: ...e key ON OFF pressed With unit off the indication OFF is displayed even if the unit has been switched off by a digital input or supervisor COOLING HEATING SELECTION To select the unit operating mode h...

Page 25: ...11 Setpoint compensation outside temperature 4 Text4 30 C 12 Setpoint compensation value 0 set 00 19 C 13 Setpoint compensation value 1 set 01 21 C 14 Setpoint compensation value 2 set 02 23 C 15 Setp...

Page 26: ...ompressor operating mode 1 heat pump 0 1 010 Active dehumidification status 0 1 011 Free Cooling status 0 1 012 Free Heating status 0 1 013 Vfan control variable 014 Supply Fan control signal 015 Supp...

Page 27: ...homologation day 044 Modulation time of resi stance water control valve opening count sec 045 Correction time of resi stance water control valve opening count sec 046 On off status of electrostatic f...

Page 28: ...Verify that the aluminum fins are not bent or damaged In the event of damages contact the authorized assistance center and get the battery ironed out in order to restore the initial condition for an...

Page 29: ...ion 3 Fill the spray pump with the prepared solution 4 Position the filter to be washed on a support so you can work comfortably Spray the detergent on the blades of the electrostatic filter 5 Also sp...

Page 30: ...y fine grain steel wool Because of the high voltage that powers them the ionization wires are subject to wear Yearly replacement will prevent unexpected breakage If breakage occurs 1 Remove all pieces...

Page 31: ...general condition lack of leaks quarterly after not more than 1000 hours of service check of operation general condition lack of leaks any replacement required yearly after not more than 2500 hours of...

Page 32: ...th a corrosive atmosphere 97 23 CE PED DIRECTIVE PUT AT REST If a long period of inactivity is foreseen for example the winter for the cooling unit the following is recommended to turn the power off i...

Page 33: ...20 8 35 71 25 8 44 22 30 8 51 59 35 8 58 09 40 8 63 92 1 0 37 03 6 0 4 10 11 0 13 40 16 0 26 01 21 0 36 08 26 0 44 53 31 0 51 86 36 0 58 34 41 0 64 14 1 2 34 84 6 2 3 24 11 2 13 97 16 2 26 46 21 2 36...

Page 34: ...eds calibrating insufficient refrigerant charge FAN PROTECTION 1 Identify the part on the wiring diagram 2 fan mechanically jammed bearings drive belt if present 3 Loose electric contacts terminals le...

Page 35: ...ored in special containers When recovering the substances present in the unit all measures must be taken to avoid damaging persons and things and polluting the surrounding area Awaiting dismantling an...

Page 36: ...00 180 270 340 AIR HANDLING SECTION FANS EXHAUST Type of fans 4 CFG Number of fans 1 Standard air flow l s 300 360 440 550 640 860 Installed unit power kW 0 3 0 3 0 4 0 4 0 6 0 6 Max outside static pr...

Page 37: ...ET BULB TO OUTDOOR AIR TEMPERATURE HANDLING COIL INLET C DB DRY BULB 1 THE DASHED AREA REFERS TO THE FIELD OF UNITS OPERATION STANDARD 2 OPERATION FIELD EXTENSION WITH PREHEATING HEATERS SOUND LEVELS...

Page 38: ...ER OUTLET ADDITIONAL COIL 3 4 15 WATER INLET ADDITIONAL COIL 3 4 16 HUMIDIFIER INLET WATER 1 2 GAS 17 CONDENSATE DISCHARGE 18 AUXILIARY ELECTRIC HEATERS OPTIONAL 19 EXHAUST AIR FILTER G4 OPTIONAL 20 B...

Page 39: ...T ADDITIONAL COIL 3 4 15 WATER INLET ADDITIONAL COIL 3 4 16 HUMIDIFIER INLET WATER 1 2 GAS 17 CONDENSATE DISCHARGE 18 AUXILIARY ELECTRIC HEATERS OPTIONAL 19 EXHAUST AIR FILTER G4 OPTIONAL 20 BRACKETS...

Page 40: ...R OUTLET ADDITIONAL COIL 3 4 15 WATER INLET ADDITIONAL COIL 3 4 16 HUMIDIFIER INLET WATER 1 2 GAS 17 CONDENSATE DISCHARGE 18 AUXILIARY ELECTRIC HEATERS OPTIONAL 19 EXHAUST AIR FILTER G4 OPTIONAL 20 BR...

Page 41: ...T ADDITIONAL COIL 3 4 15 WATER INLET ADDITIONAL COIL 3 4 16 HUMIDIFIER INLET WATER 1 2 GAS 17 CONDENSATE DISCHARGE 18 AUXILIARY ELECTRIC HEATERS OPTIONAL 19 EXHAUST AIR FILTER G4 OPTIONAL 20 BRACKETS...

Page 42: ...pag 42...

Page 43: ...pag 43...

Page 44: ...93 8606248 Fax 34 93 8855392 info clivetcomercial com CLIVET ESPA A S A U Service and Maintenance Division Calle Real de Burgos N 12 28860 Paracuellos del Jarama Madrid Espa a Tel 34 91 6658280 Fax 34...

Reviews: