background image

 

 pag 

14 

ELECTRICAL CONNECTION

 

 

GENERAL 

The characteristics of the electrical lines and relevant 
components must be determined by SPECIALIZED 
PERSONNEL ABLE TO DESIGN ELECTRICAL 
INSTALLATIONS; moreover, the lines must be in 
conformity with professional procedures and the regulations 
in force.  
All electrical operations should be performed by trained 
PERSONNEL HAVING THE NECESSARY REQUISITES 
UNDER LAW and being informed about the risks relevant 
to these activities. 
Before performing any operation on the electrical system, 
make sure that the unit supply line is SELECTED AT 
START. 
The earth connection must be made prior to other electrical 
connections.  
For all electrical type operations, REFER TO THE 
ELECTRICAL DIAGRAM ATTACHED TO THE UNIT; the 
number of the diagram is shown on the registration plate 
positioned on the electrical board or next to it. 
The electrical diagram should be carefully kept together 
with this manual and should be AVAILABLE FOR FUTURE 
INTERVENTION ON THE UNIT.

 

LINE OF UNIT POWER SUPPLY 
The ELECTRICAL DATA OF THE UNIT are shown in the 
technical chart of this manual and on the unit registration 
plate. The presence of accessories can vary according to 
the unit; the electrical data shown in the technical chart 

refer to standard units. In the event of differences between 
the data of the registration plate and the data shown in this 
manual, as well as in the technical chart, please refer to the 
DATA SHOWN IN THE REGISTRATION PLATE. 
The protection device of the unit power supply line should 
break off the short circuit power whose value should be 
determined according to the plant features. 
The section of supply cables and protection cable must be 
seized according to the characteristics of the protections 
used. 

SIGNALS / DATA LINES 
Do not overpass the maximum power allowed, which 
varies, according to the type of signal. 
Lay the cables far from power cables or cables having a 
different tension and that are able to emit electromagnetic 
disturbances.

  

Do not lay the cable near devices which can generate 
electromagnetic interferences. 
Do not lay the cables parallel to other cables; cable 
crossings are possible, only if laid at 90°. 
Connect the screen to the ground, only if there are no 
disturbances  
Assure the continuity of the screen during the entire 
extension of the cable.  
Observe, if any, the requirements about impendency, 
capacity, attenuation 

 

STANDARD UNIT ELECTRICAL DATA 

 

Voltage 

230/1/50 

400/3/50 + NEUTRAL 

Size 17

21

25

31

41 

51

F.L.A. Full load current at max admissible conditions

 

F.L.A. - Compressor 1 

8,6 10,7  11  5,4  8  10,3 

F.L.A. - Single Outlet fan 

2,4 2,4  5  5  4,6 6,7 

F.L.A. - Single exhaust air fan 

2,4 2,4  5  5  4,6 6,7 

F.L.A. – Total 

13,4 

15,5 21 15,4 17,2 23,7 

L.R.A. Locked rotor amperes

 

L.R.A. - Compressor 1 

43 

62 

62 

43 

48 

64 

L.R.A. - Single Outlet fan 

12 12 25 25 29,5 34 

F.L.I. Full load power input at max admissible condition

 

F.L.I. - Compressore 1 

kW 

1,9 

2,4 

2,5 

3,1 

4,3 

6,1 

F.L.I. - Single Outlet fan 

kW 

0,3 0,3 0,37 

0,37 0,55 0,55 

F.L.I. - Single exhaust air fan 

kW 0,3 

0,3 

0,37 

0,37 0,55 0,55 

F.L.I. 

Total 

kW 

2,5 3 3,3 3,8 5,4 7,2 

M.I.C. Maximum inrush current 

M.I.C. - Value 

67 

86 112 93 107 132 

 
Power supply: 230/1/50 Hz +/-6% 
Power supply: 400/3/50 Hz +/-6% 
voltage unbalance: max 2 % 
Values not including accessories 
 
 
 

Summary of Contents for CPAN-U-17

Page 1: ...CPAN U 17 21 25 31 41 51 ELFOFRESH LARGE Make up unit full fresh air Installation and Use Manual M25E40P5 11 22 04 14...

Page 2: ......

Page 3: ...MAINS 15 FUNCTIONAL CONNECTIONS 15 SYSTEM COMPOSITION 16 S T A R T U P 1 7 PRELIMINARY CHECKS 17 AERAULIC SYSTEM 17 REFRIGERANT SYSTEM 17 WATER SYSTEM 17 ELECTRICAL SYSTEM 17 VERIFy tensions absorpti...

Page 4: ...This provides unique identification of the machine It makes it possible to trace the specific features of the unit and to identify the components installed in it Without this number it is not possible...

Page 5: ...pressed SUMMER WINTER MODE CHANGE Key hold pressed The key is not operative if the unit is set for the automatic operating mode under such conditions the AUTO indication is displayed SOLO FAN Holding...

Page 6: ...e instructions given in this manual will cause the warranty to lapse INTENDED USE The unit must only be used for the specific purpose it was designed The unit is designed for civil air conditioning wi...

Page 7: ...L RISKS A smell of burning smoke or other indications of serious irregularity could signal the onset of situations liable to cause damage to persons or property or to the unit itself Isolate the unit...

Page 8: ...0 in weight CEE No Non applicable for mixtures Commercial name 03 Hazard identification Hazard identification Liquefied gas Vapours are heavier than air and can cause choking by reducing the oxygen av...

Page 9: ...alve if supplied is correctly assembled Verify that the cap if supplied is well assembled and that there is adequate ventilation Verify that the norms in force are respected 15 Information on the norm...

Page 10: ...es which activate the safety valves HANDLING The operation of handling the unit must be carried out respecting the instructions of the safety norms in force Legislative Decree 626 94 and following mod...

Page 11: ...s must be doubled POSITIONING 1 The units are designed for INDOOR installations performed in fixed positions and in areas accessible only to qualified and authorized personnel 2 SAFETY VALVE only if p...

Page 12: ...IONS SUPPORTS The weight of the hydraulic connections must be supported in the exterior of the unit so as not to stress the connections of user devices exchangers coils humidifiers etc ANTI VIBRATION...

Page 13: ...cs pressure inclusive between 0 1 and 0 8 Mpa 1 8bar temperature inclusive between 1 and 40 C Do not use softened water it may cause corrosion of the electrodes and foaming resulting in malfunctions f...

Page 14: ...ak off the short circuit power whose value should be determined according to the plant features The section of supply cables and protection cable must be seized according to the characteristics of the...

Page 15: ...cess is reserved to authorized assistance centres in order to avoid unauthorized modifications ON OFF FROM REMOTE CONTROL Generally the unit is delivered with bridged terminals if the control is not u...

Page 16: ...ions available on the machine keyboard SERIAL CONVERTER TTL RS485 OPTIONAL code PE6B0020 The supervision services are available with standard modbus protocol Plugged in in the main module on the elect...

Page 17: ...er Open the cocks of the refrigerator circuit if there are any Using the unit manometers if present or service manometers verify that the refrigerating circuit is in pressure Make sure that all the se...

Page 18: ...condensation pressure increases The phase optional monitor which controls the phase sequence can be installed later REMOTE INPUT CONFIGURATIONS Check used remote inputs are activated ON OFF etc as giv...

Page 19: ...tilation EXTERNAL temperature 10 C 35 C OFF OFF ON AMBIENT temperature 16 C 30 C OFF OFF ON OUTLET temperature OPERATING MODES SUMMER WINTER MODE MODE CHANGE MANUAL The choice between the HEATING or t...

Page 20: ...acing them of 1 C respect the manual set COOLING 24 C HEATING 22 C AUTOMATIC AMBIENT SET POINT The set point can also be adjusted AUTOMATICALLY to the external temperature variations the variation cur...

Page 21: ...t alarms are reset holding the buttons ECO and Clean pressed KEY LOCK All button functions can be locked by holding the buttons Clean and On Off pressed The lock is signalled by the characters wheneve...

Page 22: ...by the ALARM CODE blinking and by the machine time it they occurred The cumulative lock relay activates simultaneously with the alarm code displaying Some alarms typically PRE ALARMS do not activate...

Page 23: ...ess Dehumidification signalling with reduced flow rate E33 Recovery compressor lockout for low enthalpy ambient air temperature heat mode Automatic Recovery compressor lockout and ventilation lockout...

Page 24: ...e key ON OFF pressed With unit off the indication OFF is displayed even if the unit has been switched off by a digital input or supervisor COOLING HEATING SELECTION To select the unit operating mode h...

Page 25: ...11 Setpoint compensation outside temperature 4 Text4 30 C 12 Setpoint compensation value 0 set 00 19 C 13 Setpoint compensation value 1 set 01 21 C 14 Setpoint compensation value 2 set 02 23 C 15 Setp...

Page 26: ...ompressor operating mode 1 heat pump 0 1 010 Active dehumidification status 0 1 011 Free Cooling status 0 1 012 Free Heating status 0 1 013 Vfan control variable 014 Supply Fan control signal 015 Supp...

Page 27: ...homologation day 044 Modulation time of resi stance water control valve opening count sec 045 Correction time of resi stance water control valve opening count sec 046 On off status of electrostatic f...

Page 28: ...Verify that the aluminum fins are not bent or damaged In the event of damages contact the authorized assistance center and get the battery ironed out in order to restore the initial condition for an...

Page 29: ...ion 3 Fill the spray pump with the prepared solution 4 Position the filter to be washed on a support so you can work comfortably Spray the detergent on the blades of the electrostatic filter 5 Also sp...

Page 30: ...y fine grain steel wool Because of the high voltage that powers them the ionization wires are subject to wear Yearly replacement will prevent unexpected breakage If breakage occurs 1 Remove all pieces...

Page 31: ...general condition lack of leaks quarterly after not more than 1000 hours of service check of operation general condition lack of leaks any replacement required yearly after not more than 2500 hours of...

Page 32: ...th a corrosive atmosphere 97 23 CE PED DIRECTIVE PUT AT REST If a long period of inactivity is foreseen for example the winter for the cooling unit the following is recommended to turn the power off i...

Page 33: ...20 8 35 71 25 8 44 22 30 8 51 59 35 8 58 09 40 8 63 92 1 0 37 03 6 0 4 10 11 0 13 40 16 0 26 01 21 0 36 08 26 0 44 53 31 0 51 86 36 0 58 34 41 0 64 14 1 2 34 84 6 2 3 24 11 2 13 97 16 2 26 46 21 2 36...

Page 34: ...eds calibrating insufficient refrigerant charge FAN PROTECTION 1 Identify the part on the wiring diagram 2 fan mechanically jammed bearings drive belt if present 3 Loose electric contacts terminals le...

Page 35: ...ored in special containers When recovering the substances present in the unit all measures must be taken to avoid damaging persons and things and polluting the surrounding area Awaiting dismantling an...

Page 36: ...00 180 270 340 AIR HANDLING SECTION FANS EXHAUST Type of fans 4 CFG Number of fans 1 Standard air flow l s 300 360 440 550 640 860 Installed unit power kW 0 3 0 3 0 4 0 4 0 6 0 6 Max outside static pr...

Page 37: ...ET BULB TO OUTDOOR AIR TEMPERATURE HANDLING COIL INLET C DB DRY BULB 1 THE DASHED AREA REFERS TO THE FIELD OF UNITS OPERATION STANDARD 2 OPERATION FIELD EXTENSION WITH PREHEATING HEATERS SOUND LEVELS...

Page 38: ...ER OUTLET ADDITIONAL COIL 3 4 15 WATER INLET ADDITIONAL COIL 3 4 16 HUMIDIFIER INLET WATER 1 2 GAS 17 CONDENSATE DISCHARGE 18 AUXILIARY ELECTRIC HEATERS OPTIONAL 19 EXHAUST AIR FILTER G4 OPTIONAL 20 B...

Page 39: ...T ADDITIONAL COIL 3 4 15 WATER INLET ADDITIONAL COIL 3 4 16 HUMIDIFIER INLET WATER 1 2 GAS 17 CONDENSATE DISCHARGE 18 AUXILIARY ELECTRIC HEATERS OPTIONAL 19 EXHAUST AIR FILTER G4 OPTIONAL 20 BRACKETS...

Page 40: ...R OUTLET ADDITIONAL COIL 3 4 15 WATER INLET ADDITIONAL COIL 3 4 16 HUMIDIFIER INLET WATER 1 2 GAS 17 CONDENSATE DISCHARGE 18 AUXILIARY ELECTRIC HEATERS OPTIONAL 19 EXHAUST AIR FILTER G4 OPTIONAL 20 BR...

Page 41: ...T ADDITIONAL COIL 3 4 15 WATER INLET ADDITIONAL COIL 3 4 16 HUMIDIFIER INLET WATER 1 2 GAS 17 CONDENSATE DISCHARGE 18 AUXILIARY ELECTRIC HEATERS OPTIONAL 19 EXHAUST AIR FILTER G4 OPTIONAL 20 BRACKETS...

Page 42: ...pag 42...

Page 43: ...pag 43...

Page 44: ...93 8606248 Fax 34 93 8855392 info clivetcomercial com CLIVET ESPA A S A U Service and Maintenance Division Calle Real de Burgos N 12 28860 Paracuellos del Jarama Madrid Espa a Tel 34 91 6658280 Fax 34...

Reviews: