Sound levels
Size
Sound power level (dB)
Sound
power
level
Sound
pressure
level
Octave band (Hz)
63
125
250
500
1000
2000
4000
8000
dB(A)
dB(A)
7.1
69
73
76
77
77
75
70
74
82
65
10.1
77
75
77
79
79
77
71
75
84
66
14.2
73
78
79
82
81
79
74
78
86
68
The sound levels are referred to unit operating at full load in nominal conditions. The sound pressure level is referred at a distance of 1 m. from the ducted unit surface operating in free field conditions. External static pressure 50 Pa.
(standard UNI EN ISO 9614-2)
Measures are according to UNI EN ISO 9614-2 regulations, with respect to the EUROVENT 8/1 certication, which provides for a tolerance of 3 dB(A) on the sound power level, which is the only acoustic data to be considered binding. If unit is
set without Axitop, the sound power level presents an increase up to 3 dB(A).
Please note that when the unit is installed in conditions different from nominal test conditions (e.g. near walls or obstacles in general), the sound levels may undergo substantial variations.
M06K10A18-00
CKN-XHE2i 7.1-14.2
5