M06K40A18-00
CKN-XHE2i 7.1-14.2
23
7.12 ECO mode
The air flow supply remains constant at varied heat loads and is shutdown when setpoint is fulfilled.
To further increase the energy savings in this condition, it is also possible to set less demanding operation setpoints for the unit in respect to
the standard mode.
This function is indicated for the thermal maintenance of the served area in case it is temporarily not used, which can for example occur
at night.
In ECO mode, the renewal air is not managed.
The ECO mode can be activated:
•
Manually: P04 Enable EcoMode = 1
•
Automatically by means supervision system
Example in cooling mode:
7.13 Operating mode
The set point can be fixed (1) or variable depending on the outdoor temperature (2).
Menu: Auto Temp. Setting
The HEAT/COOL mode can be modified:
•
manually through the SA5 contact, from the keypad or through the BMS
•
automatically depending on the return temperature
To choose, set 1.06 EnMode.
Entonces será posible elegir entre 4 tipos de funcionamiento:
1. Fixed set point - Manual mode
2. Fixed set point - Automatic mode
3. Variable set point - Manual mode
4. Automatic set point - Automatic mode