Error code
:
Exception Code)
01
Illegal function code
Unsupported function code.
02
illegal data address
The address that is sent when query or set, undefined in the online
controller.
03
illegal data value
The parameters set are illegal, beyond the reasonable range or not
the valid parameter for current state of the wired controller.
Customer's BMS registers
Register
number
Register content
Note
0
Mode setting
8=OFF; 0=Stanby; 1=Cooling mode;
2=Heating mode
1
Temperature setpoint
16°C -- 28°C
2
Ur% setpoint
0% -- 100%
3
Constant airflow setpoint
set [m3/h]
4
Enable Auto Temperature
0=OFF; 1=ON
5
Enable ECO Mode
0=OFF; 1=ON
6
Air quality setpoint
set [ppm]
7
void
8
void
9
void
10
void
Status
Register
number
Register content
Note
200
Host address
-
201
PCB swithches setting
-
202
Encoder setting
7 = size 7.1; 11 = size 10.1; 18 = size 14.2
203
Operation mode
8=OFF; 0=Stanby; 1=Cooling mode;
2=Heating mode
204
HMI visualization
1 = ON
0 = OFF
BIT0 = Unit running
BIT1 = Compressor 1 running
BIT2 = Compressor 2 running
BIT3 = Electric air heater
BIT4 = Gas Burner or Water coil
BIT5 = Defrost Logo
BIT6 = Indoor fan state
BIT7 = Humidifier state
BIT8 = ECO running
BIT9 = Fault state
205
Current compressor
Current [A] Compressor A
37
Summary of Contents for CKN-XHE2i 10.1
Page 7: ...M06K40A18 00 CKN XHE2i 7 1 14 2 7...
Page 16: ...16 CKN XHE2i 7 1 14 2 M06K40A18 00 6 5 Connections performer by customer...
Page 44: ...M06K40A18 00 CKN XHE2i 7 1 14 2 44 Fans...
Page 45: ...4 CKN XHE2i 7 1 14 2 M06K40A18 00 VALVES Only value 14 2...
Page 51: ...5 CKN XHE2i 7 1 14 2 M06K40A18 00 Flue stack assembly...
Page 53: ...5 CKN XHE2i 7 1 14 2 M06K40A18 00 10 6 Hot water coil...
Page 65: ......