M06K40A18-00
CKN-XHE2i 7.1-14.2
4
10.3 Immersed electrode humidifier
SUPPLY WATER
The humidifier must be supplied with mains water having the following features:
•
pressure between 0.1 and 0.8 Mpa (1 – 8 bar)
•
temperature between 1 and 40°C
Do not use:
•
water treated with softeners: it can corrode the electrodes and form foam with possible faults/malfunctionings
•
pit, industrial or potentially polluted (chemically or bacteriologically) water
•
disinfectants or anti-corrosive substances mixed with water, as potentially irritating
Supplying the humidifier with water treated with reverse osmosis filtering system gives the following advantages:
•
reduces limescale deposits
•
reduces energy consumptions
•
reduces maintenance costs
•
increases the humidifier’s duration
Check that the filter guarantees a water flow rate higher than the flow rate of the installed humidifier.
DRAINAGE WATER
It can reach a temperature of 100°C
It contains the same substances of the supply water but in higher concentration.
As it is not toxic, it can be disposed of with white waters.
Periodical checks
Do not use solvents or detergents to clean the plastic components.
For descaling use a vinegar or acetic acid solution at 20%, subsequently rinsing with water.
15 days
Cylinder:
not over 300 hours of work
checking operation, general state, no leaks
90 days
Cylinder:
not over 1000 hours of work
checking operation, general state, no leaks, any replacement
1 year
Cylinder:
not over 2500 hours of work (disposable cylinders)
Load solenoid valve replacement:
disconnect electric power supply, dismantle valve, clean the filter
Drain solenoid valve:
disconnect electric power supply, remove reel and dismantle valve body and any impurity and rinse
The power supply bowl, piping:
check they are free and without impurities
5 years
Cylinder:
not over 10000 hours of work (inspectional cylinders)
replacement
Summary of Contents for CKN-XHE2i 10.1
Page 7: ...M06K40A18 00 CKN XHE2i 7 1 14 2 7...
Page 16: ...16 CKN XHE2i 7 1 14 2 M06K40A18 00 6 5 Connections performer by customer...
Page 44: ...M06K40A18 00 CKN XHE2i 7 1 14 2 44 Fans...
Page 45: ...4 CKN XHE2i 7 1 14 2 M06K40A18 00 VALVES Only value 14 2...
Page 51: ...5 CKN XHE2i 7 1 14 2 M06K40A18 00 Flue stack assembly...
Page 53: ...5 CKN XHE2i 7 1 14 2 M06K40A18 00 10 6 Hot water coil...
Page 65: ......