TECHNICAL MANUAL
CVM 3000
C 5030 CV/04-99 GB
51
100
CO
TYPE OF COMPRESSOR STARTUP:
0=DIRECT
1=PART-WINDING
1 flag
101
M
TOTAL NUMBER OF COMPRESSOR UNITS
1
↔
8
1-8 num
102
CO
NUMBER OF CAPACITY STEPS PER
COMPRESSOR
0
↔
3
0-3 num
103
C
NUMBER OF SOLENOID VALVES PER CIRCUIT
0
↔
2
1-2 num
104
C
NUMBER OF VENTILATION CONTROL STEPS
PER CIRCUIT
0
↔
4
0-4 num
105
C
NUMBER OF 4-WAY VALVES PER CIRCUIT
(WRAN)
0
↔
1
0-1 num
106
C
NUMBER OF AUXILIARY VALVES PER CIRCUIT
(WRAQ)
0
↔
10
0-7 num
107
M
NUMBER OF ANTIFREEZE REALYS
1
↔
2
1-2 num
108
M
NUMBER OF RELAYS FOR FREE COOLING
0
↔
1
0-1 num
109
M
PRESENCE OF PROBES IN HOT WATER CIRCUIT
0
↔
1
0-1 flag
110
M
NUMBER OF PROBES AT COLD WATER OUTLET
1
↔
9
1-3 num
111
M
NUMBER OF PROBES AT HOT WATER OUTLET
0
↔
9
0-3 num
112
M
TOTAL NUMBER OF DEFROST PROBES
0
↔
8
0-4 num
113
M
NUMBER OF TEMPERATURE PROBES FOR
TOTAL COMPRESSOR DELIVERY OUTLETS
0
↔
8
1-8 num
114
M
NUMBER OF TEMPERATURE PROBES FOR FREE
COOLING
0
↔
2
0-2 num
115
C
NUMBER OF RECOVERY RELAYS PER CIRCUIT
0
↔
1
0-1 num
116
C
ENABLING OF PUMP DOWN DURING UNIT’S
START (WORKS ONLY IF PUMP DOWN UNIT’S
STOP IS ENABLED)
IT MUST BE 0 FOR UNITS WITH SCREW
COMPRESSORS
0=NOT ENABLED
1=ENABLED
0 flag
117
M
VOLTAGE ALARM ENABLING/DISABLING
0=DISABLED
1=ENABLED
1
118
M
FREQUENCY ALARM ENABLING/DISABLING
0= DISABLED
1= ENABLED
1
119
M
EXPANSION MODULE CONFIGURATION
0= DISABLED
1= ENABLED
0
120
M
ST1 temperature probe offset
-10
↔
10
0.0 °C
121
M
ST2 temperature probe offset
-10
↔
10
0.0 °C
122
M
ST3 temperature probe offset
-10
↔
10
0.0 °C
123
M
ST4 temperature probe offset
-10
↔
10
0.0 °C
124
M
ST5 temperature probe offset
-10
↔
10
0.0 °C
125
M
ST6 temperature probe offset
-10
↔
10
0.0 °C
126
M
ST7 temperature probe offset
-10
↔
10
0.0 °C
127
M
ST8 temperature probe offset
-10
↔
10
0.0 °C
128
M
ST9 temperature probe offset
-10
↔
10
0.0 °C
129
M
ST10 temperature probe offset
-10
↔
10
0.0 °C
130
M
ST11 temperature probe offset
-10
↔
10
0.0 °C
131
M
ST12 temperature probe offset
-10
↔
10
0.0 °C
132
M
ST13 temperature probe offset
-10
↔
10
0.0 °C
133
M
ST14 temperature probe offset
-10
↔
10
0.0 °C
134
M
ST15 temperature probe offset
-10
↔
10
0.0 °C
135
M
ST16 temperature probe offset
-10
↔
10
0.0 °C