TECHNICAL MANUAL
CVM 3000
C 5030 CV/04-99 GB
53
190
M
relay status S0 (FOR WRQ/WRAQ UNITS ONLY)
000
↔
3FF
000 hex
191
M
relay time S0 (FOR WRQ/WRAQ UNITS ONLY)
000
↔
100
0 sec
192
M
relay status S1 (FOR WRQ/WRAQ UNITS ONLY)
000
↔
3FF
022 hex
193
M
relay time S1 (FOR WRQ/WRAQ UNITS ONLY)
0
↔
100
0 sec
194
M
relay status S2 (FOR WRQ/WRAQ UNITS ONLY)
000
↔
3FF
061 hex
195
M
relay time S2 (FOR WRQ/WRAQ UNITS ONLY)
000
↔
100
0 sec
196
M
relay status S3 (FOR WRQ/WRAQ UNITS ONLY)
000
↔
3FF
002 hex
197
M
relay time S3 (FOR WRQ/WRAQ UNITS ONLY)
0
↔
100
0 sec
198
M
relay status S4 (FOR WRQ/WRAQ UNITS ONLY)
000
↔
3FF
001 hex
199
M
relay time S4 (FOR WRQ/WRAQ UNITS ONLY)
000
↔
100
0 sec
200
M
relay status S5 (FOR WRQ/WRAQ UNITS ONLY)
000
↔
3FF
00D hex
201
M
relay time S5 (FOR WRQ/WRAQ UNITS ONLY)
0
↔
100
0 sec
202
M
relay status S6 (FOR WRQ/WRAQ UNITS ONLY)
000
↔
3FF
018 hex
203
M
relay time S6 (FOR WRQ/WRAQ UNITS ONLY)
000
↔
100
0 sec
204
M
relay status S7 (FOR WRQ/WRAQ UNITS ONLY)
000
↔
3FF
009 hex
205
M
relay time S7 (FOR WRQ/WRAQ UNITS ONLY)
0
↔
100
0 sec
206
M
relay status S8 (FOR WRQ/WRAQ UNITS ONLY)
000
↔
3FF
009 hex
207
M
relay time S8 (FOR WRQ/WRAQ UNITS ONLY)
0
↔
100
0 sec
210
M
first step HP set
0
↔
30
14 Bar
211
M
first step differential
0
↔
10.5
2.0 Bar
212
M
second step HP set
0
↔
30
15.5 Bar
213
M
second step HP differential
0
↔
10.5
2.0 Bar
214
M
third step HP set
0
↔
30
17.0 Bar
215
M
third step HP differential
0
↔
10.5
2.0 Bar
216
M
fourth step HP set
0
↔
30
18.0 Bar
217
M
fourth step HP differential
0
↔
10.5
2.0 Bar
218
M
first step LP set
0
↔
30
5.0 Bar
219
M
first step LP differential
0
↔
10.5
1.4 Bar
220
M
second step LP set
0
↔
30
5.0 Bar
221
M
second step LP differential
0
↔
10.5
1.4 Bar
222
M
third step LP set
0
↔
30
8.0 Bar
223
M
third step LP differential
0
↔
10.5
1.0 Bar
224
M
fourth step LP set
0
↔
30
8.0 Bar
225
M
fourth step LP differential
0
↔
10.5
1.0 Bar
226
M
Activation of HP and LP steps
0=continuous
activation (step
regulation)
1= activation with
switch-over to fan feed
from auto-transformer
(continuous step
regulation)
0
227
M
FORCED VENTILATION TIME DURING STAND-
BY TIME AFTER DEFROSTING (FOR WRQ UNITS
ONLY)
0
↔
60
0 sec
229
M
CUMULATIVE COMPRESSOR ALARM
0
↔
1
0 flag