TECHNICAL MANUAL
CVM 3000
C 5030 CV/04-99 GB
52
136
M
HYSTERESIS TO ENABLE PROPORTIONAL
REGULATION AT PRIMARY CIRCUIT OUTLET
-10
↔
10
°C
137
M
HYSTERESIS TO ENABLE PROPORTIONAL
REGULATION AT SECONDARY CIRCUIT
OUTLET
-10
↔
10
°C
138
M
FAN ACTIVATION HYSTERESIS IN FREE-
COOLING MODE
-10
↔
10
1 °C
139
M
OFFSET FOR FAN ACTIVATION IN FREE-
COOLING MODE
-10
↔
10
2 °C
140
M
FAN SHUTDOWN DELAY IN FREE-COOLING
MODE
0
↔
500
20 sec
141
M
FAN STARTUP DELAY IN FREE-COOLING MODE
0
↔
500
20 sec
142
M
ENABLING CONDENSING PRESSURE RELAY
0
↔
2
0 num
143
CI
RELAY 1 SET POINT
0
↔
30
10.0 Bar
144
CI
RELAY 1 DIFFERENTIAL
0
↔
10
5.0 Bar
145
CI
RELAY 2 SET POINT
0
↔
30
9.5 Bar
146
CI
RELAY 2 DIFFERENTIAL
0
↔
10
0.5 Bar
152
M
SP1 HP pressure probe offset CIRCUIT N°1
-10
↔
10
0.0 Bar
153
M
SP2 HP pressure probe offset CIRCUIT N°2
-10
↔
10
0.0 Bar
154
M
SP3 HP pressure probe offset CIRCUIT N°3
-10
↔
10
0.0 Bar
155
M
SP4 HP pressure probe offset CIRCUIT N°4
-10
↔
10
0.0 Bar
156
M
SP5 LP pressure probe offset CIRCUIT N°1
-10
↔
10
0.0 Bar
157
M
SP6 LP pressure probe offset CIRCUIT N°2
-10
↔
10
0.0 Bar
158
M
SP7 LP pressure probe offset CIRCUIT N°3
-10
↔
10
0.0 Bar
159
M
SP8 LP pressure probe offset CIRCUIT N°4
-10
↔
10
0.0 Bar
160
M
SP9 0P pressure probe offset COMP. N°1
-10
↔
10
0.0 Bar
161
M
SP10 0P pressure probe offset COMP. N°2
-10
↔
10
0.0 Bar
162
M
SP11 0P pressure probe offset COMP. N°3
-10
↔
10
0.0 Bar
163
M
SP12 0P pressure probe offset COMP. N°4
-10
↔
10
0.0 Bar
164
M
SP13 0P pressure probe offset COMP. N°5
-10
↔
10
0.0 Bar
165
M
SP14 0P pressure probe offset COMP. N°6
-10
↔
10
0.0 Bar
166
M
SP15 0P pressure probe offset COMP. N°7
-10
↔
10
0.0 Bar
167
M
SP16 0P pressure probe offset COMP. N°8
-10
↔
10
0.0 Bar
170
M
ENABLING SUMMER/WINTER SWITCH-OVER IN
HEAT PUMPS
0
↔
1
0 flag
171
M
AT27 INPUT POLARITY
0
↔
1
1 flag
172
M
COMPRESSOR FORCING TIME IN OFF AFTER
SWITCH-OVER
10
↔
3600
10 sec
173
M
INLET TEMPERATURE SET BEYOND WHICH NO
ALARM IS TRIGGERED IN THE CHILLER/HEAT
PUMP SWITCH-OVER
0
↔
50
30 °C
174
M
INLET TEMPERATURE SET BELOW WHICH NO
ALARM IS TRIGGERED IN THE CHILLER/HEAT
PUMP SWITCH-OVER
0
↔
50
20 °C
184
M
YEAR
1992
↔
2091
1998 num
185
M
MONTH
1
↔
12
0 num
186
M
DAY
1
↔
31
0 num
187
M
HOUR
0
↔
23
0 num
188
M
MINUTES
0
↔
59
0 num
189
M
DAY OF THE WEEK
1
↔
7
0 num