TECHNICAL MANUAL
CVM 3000
C 5030 CV/04-99 GB
13
RELAY
N.A.
COM.
RL44
152
155
RL45
153
162
RL46
154
RL47
156
RL48
157
RL49
158
RL50
159
RL51
160
RL52
161
RL53
163
167
RL54
164
RL55
165
RL56
166
RL57
168
RL58
169
RL59
170
RL60
171
RL61
172
RL62
173
RL63
174
177
RL64
175
RL65
176
2 Voltage/frequency input
The main board has an input for monitoring the voltage and frequency value.
103 - 104
Input for voltage to be monitored (range 0 -260 Vac).
Verification of the voltage value read by the board:
•
read the voltage to terminals 103 and 104 using a tester:
•
visualise the value of parameter 93.
If the two values do not correspond, make the necessary calibration using the trimmer
shown in Figure 1-1 MAIN BOARD.
N.B.: the value of parameter 93, indicated on display B5, is not updated dynamically.
Update the displayed value using the B6 keys.