TECHNICAL MANUAL
CVM 3000
C 5030 CV/04-99 GB
33
7.2.1 Default set point settings
The following table shows, based on the number of steps, the commonly used set point
and
∆
t values.
The theoretical minimum and maximum values indicated in the table for the outlet
temperature refer to nominal flow rate operation, and therefore with a 5° C evaporator
thermal head.
No. of steps Set point [°C]
∆
∆
t [°C]
Theoret. min out temp. Theoret. max out temp.
1
41
1
40
46
2
42.5
2.5
41.2
46.3
3
44
4
42.6
46.4
>=4
45
5
<=43.7
<=46.3
Warning:
the regulation is made based on the temperature reading at the condenser’s
inlet.