47
c l i m a t e m a s t e r. c o m
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
Tranquility
®
Compact (TC) Series
R e v. : 0 2 / 0 4 / 1 3
Start-Up Log Sheet
Installer:
Complete unit and system checkout and follow unit start-up procedures in the IOM. Use this form to record
unit information, temperatures and pressures during start-up. Keep this form for future reference.
Job
Name:
Street
Address:
Model
Number:
Serial
Number:
Unit
Location
in
Building:
Date:
Sales
Order
No:
In order to minimize troubleshooting and costly system failures, complete the following checks and data entries before
the system is put into full operation.
Fan
Motor:
Speed
Tap
(PSC)
Temperatures:
F
or
C
Antifreeze:
%
Pressures: PSIG or kPa
Type:
Cooling Mode
Heating Mode
Entering Fluid Temperature
Leaving Fluid Temperature
Temperature Differential
Return-Air Temperature
DB
WB
DB
Supply-Air Temperature
DB
WB
DB
Temperature Differential
Water Coil Heat Exchanger
(Water Pressure IN)
Water Coil Heat Exchanger
(Water Pressure OUT)
Pressure Differential
Water Flow GPM
Compressor
Amps
Volts
Discharge Line Temperature
Motor
Amps
Volts
Allow unit to run 15 minutes in each mode before taking data.
Note: Never connect refrigerant gauges during startup procedures. Conduct water-side analysis using P/T ports to determine water
fl
ow and temperature difference. If
water-side analysis shows poor performance, refrigerant troubleshooting may be required. Connect refrigerant gauges as a last resort.