Safety Features - CXM and DXM Controls

Safety Features – CXM/DXM Control

The safety features below are provided to protect 
the compressor, heat exchangers, wiring, and other 
components from damage caused by operation outside 
of design conditions.

Anti-short cycle protection: The control features a 5 
minute anti-short cycle protection for the compressor.

Note: The 5 minute anti-short cycle also occurs at 
power up.

Random start: The control features a random start upon 
power up of 5-80 seconds.
Fault Retry: In Fault Retry mode, the Status LED begins 
slowly fl ashing to signal that the control is trying to 
recover from a fault input. The control will stage off the 
outputs and then “try again” to satisfy the thermostat 
input call. Once the thermostat input call is satisfi ed, 
the control will continue on as if no fault occurred. If 3 
consecutive faults occur without satisfying the thermostat 
input call, the control will go into “lockout” mode. The 
last fault causing the lockout will be stored in memory 
and can be viewed at the “fault” LED (DXM board) or 
by going into test mode (CXM board).  

Note:  LT1/LT2 

faults are factory set at only one try.

Lockout: In lockout mode, the status LED will begin fast 
fl ashing. The compressor relay is turned off immediately. 
Lockout mode can be “soft” reset by turning off the 
thermostat (or satisfying the call). A “soft” reset keeps 
the fault in memory but resets the control.  A “hard” 
reset (disconnecting power to the control) resets the 
control and erases fault memory.
Lockout with emergency heat: While in lockout mode, 
if W becomes active (CXM), emergency heat mode will 
occur.  If DXM is confi gured for heat pump thermostat 
type (DIP 1.3), emergency heat will become active if O/
W2 is energized.
High pressure switch: When the high pressure switch 
opens due to high refrigerant pressures, the compressor 
relay is de-energized immediately since the high pressure 
switch is in series with the compressor contactor coil. The 
high pressure fault recognition is immediate (does not 
delay for 30 continuous seconds before de-energizing 
the compressor).

High pressure lockout code = 2

Example: 2 quick fl ashes, 10 sec pause, 2 quick fl ashes, 10 
sec. pause, etc.
Low pressure switch: The low pressure switch must be open 
and remain open for 30 continuous seconds during “on” 
cycle to be recognized as a low pressure fault. If the low 
pressure switch is open for 30 seconds prior to compressor 
power up it will be considered a low pressure (loss of charge) 
fault. The low pressure switch input is bypassed for the initial 
120 seconds of a compressor run cycle.

Low pressure lockout code = 3

Water coil low temperature (LT1): The LT1 thermistor 
temperature must be below the selected low 
temperature limit setting for 30 continuous seconds 
during a compressor run cycle to be recognized as a LT1 
fault. The LT1 input is bypassed for the initial 120 seconds 
of a compressor run cycle. LT1 is set at the factory for one 
try. Therefore, the control will go into lockout mode once 
the LT1 fault has occurred.

LT1 lockout code = 4

Air coil low temperature (LT2): The LT2 thermistor 
temperature must be below the selected low 
temperature limit setting for 30 continuous seconds 
during a compressor run cycle to be recognized as a LT2 
fault. The LT2 input is bypassed for the initial 60 seconds 
of a compressor run cycle. LT2 is set at the factory for one 
try. Therefore, the control will go into lockout mode once 
the LT2 fault has occurred.

LT2 lockout code = 5

Condensate overfl ow: The condensate overfl ow sensor 
must sense overfl ow level for 30 continuous seconds to 
be recognized as a CO fault. Condensate overfl ow will be 
monitored at all times.

CO lockout code = 6

Over/under voltage shutdown: An over/under voltage 
condition exists when the control voltage is outside the 
range of 19VAC to 30VAC. Over/under voltage shut 
down is a self-resetting safety. If the voltage comes back 
within range for at least 0.5 seconds, normal operation 
is restored. This is not considered a fault or lockout. If 
the CXM/DXM is in over/under voltage shutdown for 15 
minutes, the alarm relay will close.

Over/under voltage shut down code = 7

Unit Performance Sentinel-UPS (patent pending): The 
UPS feature indicates when the heat pump is operating 
ineffi ciently. A UPS condition exists when:

a.  In heating mode with compressor energized, LT2 is greater 

than 125°F [52°C] for 30 continuous seconds, or:

b.  In cooling mode with compressor energized, LT1 is greater 

than 125°F [52°C] for 30 continuous seconds, or:

c.  In cooling mode with compressor energized, LT2 is less 

than 40°F [4.5°C] for 30 continuous seconds. 

Summary of Contents for Tranquility 16

Page 1: ...l Power Wiring 22 Electrical Power Low Voltage Wiring 23 Electrical Low Voltage Wiring 24 Electrical Thermostat Wiring 25 TC Blower Performance Data 26 Typical Wiring Diagram Units with DXM Board and...

Page 2: ...2 ClimateMaster Water Source Heat Pumps CL IM ATEM ASTER WATER SOURCE HEAT PUMPS Tranquility Compact TC Series R ev 02 04 13 This Page Intentionally Left Blank...

Page 3: ...D RANGE w ULTRAQUIET 0 NONE FUTURE USE A Copper Water Coil w CoatedAir Coil HEAT EXCHANGER OPTIONS C Copper Water Coil w Non CoatedAir Coil L LEFT RETURN RETURNAIR OPTIONS R RIGHT RETURN B BACK DISCHA...

Page 4: ...tenance information which is important but which is not hazard related WARNING The EarthPure Application and Service Manual should be read and understood before attempting to service refrigerant circu...

Page 5: ...nstalling any of the system components Remove any dirt or debris found in or on these components Pre Installation Installation Operation and Maintenance instructions are provided with each unit Horizo...

Page 6: ...24x21 75 20x17 25 24x21 76 24x28 25 24x28 25 Filter Standard 1 Throwaway 10x18 10x18 10x18 20x20 20x20 20x20 20x20 24x24 20x20 24x24 1 14x24 1 18x24 1 14x24 1 18x24 Weight Operating lbs 103 105 114 1...

Page 7: ...anels Provide sufficient room to make water electrical and duct connection s If the unit is located in a confined space such as a closet provisions must be made for return air to freely enter the spac...

Page 8: ...QLW 3RZHU LVFRQQHFW 3RZHU LULQJ QVXODWHG VXSSO GXFW ZLWK DW OHDVW RQH GHJ HOERZ WR UHGXFH DLU QRLVH 5HWXUQ LU 6XSSO LU 8QLW DQJHU PP WKUHDGHG URGV 8QLW 3RZHU OH LEOH XFW RQQHFWRU 2SWLRQDO RZ 3UHVVXUH...

Page 9: ...Lift out the access panel and set aside Lift and rotate the discharge panel to the other position as shown being careful with the blower wiring 3 Check blower wire routing and connections for tension...

Page 10: ...s and model of the specific unit If the unit is connected to existing ductwork a previous check should have been made to ensure that the ductwork has the capacity to handle the airflow required for th...

Page 11: ...8 for typical installation illustrations Refer to unit submittal data or engineering design guide for dimensional data 1 Install the unit on a piece of rubber neoprene orother mounting pad material fo...

Page 12: ...stalled and pitched away from the unit to allow for proper drainage This connection must meet all local plumbing building codes Vertical units utilize a condensate hose inside the cabinet as a trappin...

Page 13: ...water temperature is below the minimum expected dew point of the pipe ambient conditions Insulation is required if loop water temperature drops below the dew point insulation is required for ground l...

Page 14: ...ve and or J type swivel connection Balancing valves and an external low pressure drop solenoid valve for use in variable speed pumping systems may also be included in the hose kit The piping system sh...

Page 15: ...er your local sales office should be consulted to determine the antifreeze best suited to your area Freeze protection should be maintained to 15 F 9 C below the lowest expected entering loop temperatu...

Page 16: ...umps CL IM ATEM ASTER WATER SOURCE HEAT PUMPS Tranquility Compact TC Series R ev 02 04 13 Ground Loop Heat Pump Applications Figure 13 Typical Ground Loop Application High and Low Voltage Knockouts Vi...

Page 17: ...PVC or CPVS piping may cause failure of the PVC CPVC PVC CPVC piping should never be used as supply or return water piping with water source heat pump products containing HFC 410A as system failures a...

Page 18: ...esired flow of 1 5 to 2 gpm per ton 2 0 to 2 6 l m per kW is achieved A second method of flow control requires a flow control device mounted on the outlet of the water control valve The device is typi...

Page 19: ...ll 0 5 ppm Maximum Maximum Allowable at maximum water temperature Chloride Levels 10 C 24 C 38 C Copper Cupronickel 20ppm NR NR 150 ppm NR NR 304 SS 400 ppm 250 ppm 150 ppm 316 SS 1000 ppm 550 ppm 375...

Page 20: ...on and sound transmission to the building General Line Voltage Wiring Be sure the available power is the same voltage and phase shown on the unit serial plate Line and low voltage wiring must be done...

Page 21: ...8 230 60 3 197 254 1 8 9 58 0 3 00 11 9 14 1 20 F 460 60 3 414 506 1 4 2 28 0 1 70 5 9 7 0 15 036 G 208 230 60 1 197 254 1 16 7 79 0 1 80 18 5 22 7 35 E 265 60 1 239 292 1 13 5 72 0 2 00 15 5 18 9 30...

Page 22: ...gher static is required Low speed will deliver approximately 85 of rated airflow at 0 10 in w g 25 Pa An optional high static blower is available on some models WARNING Disconnect electrical power sou...

Page 23: ...l connections Review the appropriate AOM Application Operation and Maintenance manual for units with DDC controls Low Water Temperature Cutout Selection The CXM DXM control allows the field selection...

Page 24: ...e 19 Accessory Wiring Water Solenoid Valves An external solenoid valve s should be used on ground water installations to shut off flow to the unit when the compressor is not operating A slow closing v...

Page 25: ...aled to prevent erroneous temperature measurement Position the thermostat back plate against the wall so that it appears level and so the thermostat wires protrude through the middle of the back plate...

Page 26: ...D 988 960 922 846 713 589 HS LOW 979 960 931 912 884 855 827 751 675 030 HI 1000 750 1102 1074 1045 1017 979 903 798 MED 1188 1169 1140 1121 1093 1064 1036 1017 988 960 922 846 LOW 1064 1045 1017 998...

Page 27: ...27 climatemaster com THE SMART SOLUTION FOR ENERGY EFFIC I E NC Y Tranquility Compact TC Series R ev 0 2 0 4 1 3 Typical Wiring Diagram Units with DXM Board and PSC Fan Motor Three Phase...

Page 28: ...28 ClimateMaster Water Source Heat Pumps CL IM ATEM ASTER WATER SOURCE HEAT PUMPS Tranquility Compact TC Series R ev 02 04 13 Typical Wiring Diagram Units with CXM Board and PSC Fan Motor Single Phase...

Page 29: ...4 CXM LED And Alarm Relay Operations CAUTION CAUTION Do not restart units without inspection and remedy of faulting condition Equipment damage may occur CXM Control For detailed control information se...

Page 30: ...clipped under extenuating circumstances as recommended by ClimateMaster technical services Not Clipped 30 F 1 C Clipped 10 F 12 C Alarm relay setting Jumper 4 JW4 AL2 Dry provides field selection of t...

Page 31: ...Accessory DIP Switch Settings 1 3 Thermostat type heat pump or heat cool DIP 1 3 provides selection of thermostat type Heat pump or heat cool thermostats can be selected When in heat cool mode Y1 is t...

Page 32: ...10 sec pause 2 quick flashes 10 sec pause etc Low pressure switch The low pressure switch must be open and remain open for 30 continuous seconds during on cycle to be recognized as a low pressure faul...

Page 33: ...the unit The green status light will flash code 3 when the unit is in ESD mode ESD mode code 3 green status LED Diagnostic Features The LED on the CXM board advises the technician of the current statu...

Page 34: ...e 8 are not normal or continuous operating conditions Minimum maximum limits are start up conditions to bring the building space up to occupancy temperatures Units are not designed to operate under th...

Page 35: ...per 1000 l of water or other equivalent approved cleaning agent Reset the boiler to raise the loop temperature to 100 F 38 C Circulate the solution for a minimum of 8 to 24 hours At the end of this pe...

Page 36: ...former has the properly selected voltage tap Entering water and air Ensure that entering water and air temperatures are within operating limits of Table 8a b Low water temperature cutout Verify that l...

Page 37: ...e 9 In S I units the formula is as follows HR kW TD x l s x 4 18 f Check air temperature drop across the air coil when compressor is operating Air temperature drop should be between 15 F and 25 F 8 C...

Page 38: ...the electrical panel Exercise caution when working with energized equipment CAUTION Verify that ALL water control valves are open and allow water flow prior to engaging the compressor Freezing of the...

Page 39: ...23 4 2 6 17 6 2 1 14 7 1 8 12 4 4 5 0 28 5 9 40 6 4 6 31 5 3 9 26 9 3 4 23 4 024 3 0 0 19 2 2 15 2 1 7 11 6 1 4 9 6 1 2 8 3 4 5 0 28 4 0 27 6 3 2 22 2 2 8 19 3 2 5 17 2 6 0 0 38 7 2 49 6 5 9 40 6 5 2...

Page 40: ...3 5 4 7 4 3 5 5 5 17 23 18 24 19 25 50 1 5 2 25 3 124 134 122 132 120 130 211 231 199 219 187 207 9 14 12 17 15 20 10 15 9 14 8 13 18 20 13 2 15 2 8 4 10 4 17 23 17 23 17 23 101 111 105 115 110 120 3...

Page 41: ...5 18 24 19 25 19 25 50 1 5 2 25 3 136 146 134 144 133 143 198 218 183 203 171 191 10 15 10 15 11 16 14 19 13 18 13 18 22 24 16 5 18 5 11 13 19 25 19 25 19 25 101 111 105 115 109 119 302 322 306 326 3...

Page 42: ...20 15 20 7 7 9 7 5 7 7 7 3 7 5 7 19 27 19 27 20 28 50 1 5 2 25 3 121 131 120 130 120 130 249 269 231 251 214 234 12 17 12 17 12 17 9 14 8 13 8 13 19 4 21 4 14 4 16 4 9 4 11 4 17 25 18 26 18 26 91 101...

Page 43: ...96 106 100 110 309 329 313 333 317 337 8 13 9 14 9 14 3 8 3 8 3 8 9 5 11 5 7 9 4 6 6 6 23 31 24 32 24 32 70 1 5 2 25 3 129 139 129 139 129 139 337 357 328 348 300 320 8 13 8 13 8 13 12 17 11 16 11 16...

Page 44: ...ts should never be operated without a filter Washable high efficiency electrostatic filters when dirty can exhibit a very high pressure drop for the fan motor and reduce air flow resulting in poor per...

Page 45: ...ck for piping slope away from unit Check slope of unit toward outlet Poor venting Check vent location X Moisture on sensor Check for moisture shorting to air coil X X Plugged air filter Replace air fi...

Page 46: ...e Check fan motor operation and air flow restrictions Too high of external static Check static vs blower table X Reduced or no water flow in cooling Check pump operation or valve operation setting Che...

Page 47: ...eed Tap PSC Temperatures F or C Antifreeze Pressures PSIG or kPa Type Cooling Mode Heating Mode Entering Fluid Temperature Leaving Fluid Temperature Temperature Differential Return Air Temperature DB...

Page 48: ...035 6625 6 5 68 7 21 7 1 1 6 6 36 6 7 36 6 7 5 2 3 7 1 48 1 3 16 21 9 9 5 2 36 6 7 36 6 7 7 5 1 7 5 287 36 36 7 5 1 7 5 287 36 36 8VH IRU ZDWHU IRU DQWLIUHH H 7 5 5 5 6 6 1 3 6 1625 3 16 21 9 9 7 5 5...

Page 49: ...suf cient or incorrect system design or the improper application of CM s products CM is not responsible for 1 The costs of any uids refrigerant or other system components or associated labor to repair...

Page 50: ...DWHG LQ D PDQQHU FRQWUDU WR 0 V SULQWHG LQVWUXFWLRQV 3URGXFWV ZKLFK KDYH GHIHFWV GDPDJH RU LQVXI FLHQW SHUIRUPDQFH DV D UHVXOW RI LQVXI FLHQW RU LQFRUUHFW V VWHP GHVLJQ RU WKH LPSURSHU DSSOLFDWLRQ LQV...

Page 51: ...51 climatemaster com THE SMART SOLUTION FOR ENERGY EFFIC I E NC Y Tranquility Compact TC Series R ev 0 2 0 4 1 3 Notes...

Page 52: ...ANDARD 13256 1 HEAT PUMPS W A T E R T O AIR BRI N E T O A I R ClimateMaster Inc 2009 ClimateMaster works continually to improve its products As a result the design and specifications of each product a...

Reviews: