ClimateMaster Tranquility 16 Installation, Operation & Maintenance Manual Download Page 10

10

C l i m a t e M a s t e r   W a t e r- S o u r c e   H e a t   P u m p s

C L I M A T E M A S T E R   W A T E R - S O U R C E   H E A T   P U M P S

Tranquility

®

 Compact (TC) Series

R e v. :   0 2 / 0 4 / 1 3

Horizontal Installation

* Some units include a painted drain connection. 

Using a threaded pipe or similar device to clear 

any excess paint accumulated inside this fitting 

may ease final drain line installation.

ರ3HU

)RRW

Figure 6: Horizontal Condensate Connection

CAUTION!  

Ensure condensate line is pitched toward drain 

1/8 inch per ft [11mm per m] of run.

 

CAUTION!

 

Duct System Installation

 - Proper duct sizing and design 

is critical to the performance of the unit. The duct system 
should be designed to allow adequate and even airfl ow 
through the unit during operation. Air fl ow through 
the unit MUST be at or above the minimum stated 
airfl ow for the unit to avoid equipment damage. Duct 
systems should be designed for quiet operation. Refer 
to Figure 3 for horizontal duct system details or Figure 
8 for vertical duct system details. A fl exible connector 
is recommended for both discharge and return air duct 
connections on metal duct systems to eliminate the 
transfer of vibration to the duct system. To maximize 
sound attenuation of the unit blower, the supply and 
return plenums should include internal fi berglass duct 
liner or be constructed from ductboard for the fi rst few 
feet. Application of the unit to uninsulated ductwork in 
an unconditioned space is not recommended, as the 
unit’s performance may be adversely affected.

At least one 90° elbow should be included in the supply 
duct to reduce air noise. If air noise or excessive air fl ow 
is a problem, the blower speed can be changed. For 
airfl ow charts, consult submittal data for the series and 
model of the specifi c unit.

If the unit is connected to existing ductwork, a previous 
check should have been made to ensure that the 
ductwork has the capacity to handle the airfl ow required 
for the unit. If ducting is too small, as in the replacement 
of a heating only system, larger ductwork should be 
installed. All existing ductwork should be checked for 
leaks and repaired as necessary.

Condensate Piping

e

0 / 0 / 3

Duct System Installation

Condensate Piping

 - Horizontal Units -

 

A condensate 

drain line must be installed and pitched away for the unit 
to allow for proper drainage. This connection must meet 
all local plumbing/building codes.

Pitch the unit toward the drain as shown in Figure 2 to 
improve the condensate drainage. On small units (less 
than 2.5 tons/8.8 kW), ensure that unit pitch does not 
cause condensate leaks inside the cabinet.

Install condensate trap at each unit with the top of 
the trap positioned below the unit condensate drain 
connection as shown in Figure 6.  Design the depth of 
the trap (water-seal) based upon the amount of ESP 
capability of the blower (where 2 inches [51mm] of ESP 
capability requires 2 inches [51mm] of trap depth). 
As a general rule, 1-1/2 inch [38mm] trap depth is the 
minimum.

Each unit must be installed with its own individual trap 
and connection to the condensate line (main) or riser. 
Provide a means to fl ush or blow out the condensate line. 
DO NOT install units with a common trap and/or vent.

Always vent the condensate line when dirt or air 
can collect in the line or a long horizontal drain line 
is required. Also vent when large units are working 
against higher external static pressure than other units 
connected to the same condensate main since this may 
cause poor drainage for all units on the line. 

WHEN A 

VENT IS INSTALLED IN THE DRAIN LINE, IT MUST BE 
LOCATED AFTER THE TRAP IN THE DIRECTION OF 
THE CONDENSATE FLOW.

Summary of Contents for Tranquility 16

Page 1: ...l Power Wiring 22 Electrical Power Low Voltage Wiring 23 Electrical Low Voltage Wiring 24 Electrical Thermostat Wiring 25 TC Blower Performance Data 26 Typical Wiring Diagram Units with DXM Board and...

Page 2: ...2 ClimateMaster Water Source Heat Pumps CL IM ATEM ASTER WATER SOURCE HEAT PUMPS Tranquility Compact TC Series R ev 02 04 13 This Page Intentionally Left Blank...

Page 3: ...D RANGE w ULTRAQUIET 0 NONE FUTURE USE A Copper Water Coil w CoatedAir Coil HEAT EXCHANGER OPTIONS C Copper Water Coil w Non CoatedAir Coil L LEFT RETURN RETURNAIR OPTIONS R RIGHT RETURN B BACK DISCHA...

Page 4: ...tenance information which is important but which is not hazard related WARNING The EarthPure Application and Service Manual should be read and understood before attempting to service refrigerant circu...

Page 5: ...nstalling any of the system components Remove any dirt or debris found in or on these components Pre Installation Installation Operation and Maintenance instructions are provided with each unit Horizo...

Page 6: ...24x21 75 20x17 25 24x21 76 24x28 25 24x28 25 Filter Standard 1 Throwaway 10x18 10x18 10x18 20x20 20x20 20x20 20x20 24x24 20x20 24x24 1 14x24 1 18x24 1 14x24 1 18x24 Weight Operating lbs 103 105 114 1...

Page 7: ...anels Provide sufficient room to make water electrical and duct connection s If the unit is located in a confined space such as a closet provisions must be made for return air to freely enter the spac...

Page 8: ...QLW 3RZHU LVFRQQHFW 3RZHU LULQJ QVXODWHG VXSSO GXFW ZLWK DW OHDVW RQH GHJ HOERZ WR UHGXFH DLU QRLVH 5HWXUQ LU 6XSSO LU 8QLW DQJHU PP WKUHDGHG URGV 8QLW 3RZHU OH LEOH XFW RQQHFWRU 2SWLRQDO RZ 3UHVVXUH...

Page 9: ...Lift out the access panel and set aside Lift and rotate the discharge panel to the other position as shown being careful with the blower wiring 3 Check blower wire routing and connections for tension...

Page 10: ...s and model of the specific unit If the unit is connected to existing ductwork a previous check should have been made to ensure that the ductwork has the capacity to handle the airflow required for th...

Page 11: ...8 for typical installation illustrations Refer to unit submittal data or engineering design guide for dimensional data 1 Install the unit on a piece of rubber neoprene orother mounting pad material fo...

Page 12: ...stalled and pitched away from the unit to allow for proper drainage This connection must meet all local plumbing building codes Vertical units utilize a condensate hose inside the cabinet as a trappin...

Page 13: ...water temperature is below the minimum expected dew point of the pipe ambient conditions Insulation is required if loop water temperature drops below the dew point insulation is required for ground l...

Page 14: ...ve and or J type swivel connection Balancing valves and an external low pressure drop solenoid valve for use in variable speed pumping systems may also be included in the hose kit The piping system sh...

Page 15: ...er your local sales office should be consulted to determine the antifreeze best suited to your area Freeze protection should be maintained to 15 F 9 C below the lowest expected entering loop temperatu...

Page 16: ...umps CL IM ATEM ASTER WATER SOURCE HEAT PUMPS Tranquility Compact TC Series R ev 02 04 13 Ground Loop Heat Pump Applications Figure 13 Typical Ground Loop Application High and Low Voltage Knockouts Vi...

Page 17: ...PVC or CPVS piping may cause failure of the PVC CPVC PVC CPVC piping should never be used as supply or return water piping with water source heat pump products containing HFC 410A as system failures a...

Page 18: ...esired flow of 1 5 to 2 gpm per ton 2 0 to 2 6 l m per kW is achieved A second method of flow control requires a flow control device mounted on the outlet of the water control valve The device is typi...

Page 19: ...ll 0 5 ppm Maximum Maximum Allowable at maximum water temperature Chloride Levels 10 C 24 C 38 C Copper Cupronickel 20ppm NR NR 150 ppm NR NR 304 SS 400 ppm 250 ppm 150 ppm 316 SS 1000 ppm 550 ppm 375...

Page 20: ...on and sound transmission to the building General Line Voltage Wiring Be sure the available power is the same voltage and phase shown on the unit serial plate Line and low voltage wiring must be done...

Page 21: ...8 230 60 3 197 254 1 8 9 58 0 3 00 11 9 14 1 20 F 460 60 3 414 506 1 4 2 28 0 1 70 5 9 7 0 15 036 G 208 230 60 1 197 254 1 16 7 79 0 1 80 18 5 22 7 35 E 265 60 1 239 292 1 13 5 72 0 2 00 15 5 18 9 30...

Page 22: ...gher static is required Low speed will deliver approximately 85 of rated airflow at 0 10 in w g 25 Pa An optional high static blower is available on some models WARNING Disconnect electrical power sou...

Page 23: ...l connections Review the appropriate AOM Application Operation and Maintenance manual for units with DDC controls Low Water Temperature Cutout Selection The CXM DXM control allows the field selection...

Page 24: ...e 19 Accessory Wiring Water Solenoid Valves An external solenoid valve s should be used on ground water installations to shut off flow to the unit when the compressor is not operating A slow closing v...

Page 25: ...aled to prevent erroneous temperature measurement Position the thermostat back plate against the wall so that it appears level and so the thermostat wires protrude through the middle of the back plate...

Page 26: ...D 988 960 922 846 713 589 HS LOW 979 960 931 912 884 855 827 751 675 030 HI 1000 750 1102 1074 1045 1017 979 903 798 MED 1188 1169 1140 1121 1093 1064 1036 1017 988 960 922 846 LOW 1064 1045 1017 998...

Page 27: ...27 climatemaster com THE SMART SOLUTION FOR ENERGY EFFIC I E NC Y Tranquility Compact TC Series R ev 0 2 0 4 1 3 Typical Wiring Diagram Units with DXM Board and PSC Fan Motor Three Phase...

Page 28: ...28 ClimateMaster Water Source Heat Pumps CL IM ATEM ASTER WATER SOURCE HEAT PUMPS Tranquility Compact TC Series R ev 02 04 13 Typical Wiring Diagram Units with CXM Board and PSC Fan Motor Single Phase...

Page 29: ...4 CXM LED And Alarm Relay Operations CAUTION CAUTION Do not restart units without inspection and remedy of faulting condition Equipment damage may occur CXM Control For detailed control information se...

Page 30: ...clipped under extenuating circumstances as recommended by ClimateMaster technical services Not Clipped 30 F 1 C Clipped 10 F 12 C Alarm relay setting Jumper 4 JW4 AL2 Dry provides field selection of t...

Page 31: ...Accessory DIP Switch Settings 1 3 Thermostat type heat pump or heat cool DIP 1 3 provides selection of thermostat type Heat pump or heat cool thermostats can be selected When in heat cool mode Y1 is t...

Page 32: ...10 sec pause 2 quick flashes 10 sec pause etc Low pressure switch The low pressure switch must be open and remain open for 30 continuous seconds during on cycle to be recognized as a low pressure faul...

Page 33: ...the unit The green status light will flash code 3 when the unit is in ESD mode ESD mode code 3 green status LED Diagnostic Features The LED on the CXM board advises the technician of the current statu...

Page 34: ...e 8 are not normal or continuous operating conditions Minimum maximum limits are start up conditions to bring the building space up to occupancy temperatures Units are not designed to operate under th...

Page 35: ...per 1000 l of water or other equivalent approved cleaning agent Reset the boiler to raise the loop temperature to 100 F 38 C Circulate the solution for a minimum of 8 to 24 hours At the end of this pe...

Page 36: ...former has the properly selected voltage tap Entering water and air Ensure that entering water and air temperatures are within operating limits of Table 8a b Low water temperature cutout Verify that l...

Page 37: ...e 9 In S I units the formula is as follows HR kW TD x l s x 4 18 f Check air temperature drop across the air coil when compressor is operating Air temperature drop should be between 15 F and 25 F 8 C...

Page 38: ...the electrical panel Exercise caution when working with energized equipment CAUTION Verify that ALL water control valves are open and allow water flow prior to engaging the compressor Freezing of the...

Page 39: ...23 4 2 6 17 6 2 1 14 7 1 8 12 4 4 5 0 28 5 9 40 6 4 6 31 5 3 9 26 9 3 4 23 4 024 3 0 0 19 2 2 15 2 1 7 11 6 1 4 9 6 1 2 8 3 4 5 0 28 4 0 27 6 3 2 22 2 2 8 19 3 2 5 17 2 6 0 0 38 7 2 49 6 5 9 40 6 5 2...

Page 40: ...3 5 4 7 4 3 5 5 5 17 23 18 24 19 25 50 1 5 2 25 3 124 134 122 132 120 130 211 231 199 219 187 207 9 14 12 17 15 20 10 15 9 14 8 13 18 20 13 2 15 2 8 4 10 4 17 23 17 23 17 23 101 111 105 115 110 120 3...

Page 41: ...5 18 24 19 25 19 25 50 1 5 2 25 3 136 146 134 144 133 143 198 218 183 203 171 191 10 15 10 15 11 16 14 19 13 18 13 18 22 24 16 5 18 5 11 13 19 25 19 25 19 25 101 111 105 115 109 119 302 322 306 326 3...

Page 42: ...20 15 20 7 7 9 7 5 7 7 7 3 7 5 7 19 27 19 27 20 28 50 1 5 2 25 3 121 131 120 130 120 130 249 269 231 251 214 234 12 17 12 17 12 17 9 14 8 13 8 13 19 4 21 4 14 4 16 4 9 4 11 4 17 25 18 26 18 26 91 101...

Page 43: ...96 106 100 110 309 329 313 333 317 337 8 13 9 14 9 14 3 8 3 8 3 8 9 5 11 5 7 9 4 6 6 6 23 31 24 32 24 32 70 1 5 2 25 3 129 139 129 139 129 139 337 357 328 348 300 320 8 13 8 13 8 13 12 17 11 16 11 16...

Page 44: ...ts should never be operated without a filter Washable high efficiency electrostatic filters when dirty can exhibit a very high pressure drop for the fan motor and reduce air flow resulting in poor per...

Page 45: ...ck for piping slope away from unit Check slope of unit toward outlet Poor venting Check vent location X Moisture on sensor Check for moisture shorting to air coil X X Plugged air filter Replace air fi...

Page 46: ...e Check fan motor operation and air flow restrictions Too high of external static Check static vs blower table X Reduced or no water flow in cooling Check pump operation or valve operation setting Che...

Page 47: ...eed Tap PSC Temperatures F or C Antifreeze Pressures PSIG or kPa Type Cooling Mode Heating Mode Entering Fluid Temperature Leaving Fluid Temperature Temperature Differential Return Air Temperature DB...

Page 48: ...035 6625 6 5 68 7 21 7 1 1 6 6 36 6 7 36 6 7 5 2 3 7 1 48 1 3 16 21 9 9 5 2 36 6 7 36 6 7 7 5 1 7 5 287 36 36 7 5 1 7 5 287 36 36 8VH IRU ZDWHU IRU DQWLIUHH H 7 5 5 5 6 6 1 3 6 1625 3 16 21 9 9 7 5 5...

Page 49: ...suf cient or incorrect system design or the improper application of CM s products CM is not responsible for 1 The costs of any uids refrigerant or other system components or associated labor to repair...

Page 50: ...DWHG LQ D PDQQHU FRQWUDU WR 0 V SULQWHG LQVWUXFWLRQV 3URGXFWV ZKLFK KDYH GHIHFWV GDPDJH RU LQVXI FLHQW SHUIRUPDQFH DV D UHVXOW RI LQVXI FLHQW RU LQFRUUHFW V VWHP GHVLJQ RU WKH LPSURSHU DSSOLFDWLRQ LQV...

Page 51: ...51 climatemaster com THE SMART SOLUTION FOR ENERGY EFFIC I E NC Y Tranquility Compact TC Series R ev 0 2 0 4 1 3 Notes...

Page 52: ...ANDARD 13256 1 HEAT PUMPS W A T E R T O AIR BRI N E T O A I R ClimateMaster Inc 2009 ClimateMaster works continually to improve its products As a result the design and specifications of each product a...

Reviews: