background image

37

c l i m a t e m a s t e r. c o m

T H E   S M A R T   S O L U T I O N   F O R   E N E R G Y   E F F I C I E N C Y

Tranquility

®

 Compact (TC) Series

R e v. :   0 2 / 0 4 / 1 3

Unit Start-up Procedure

1.  Turn the thermostat fan position to “ON”. Blower 

should start.

2.  Balance air fl ow at registers.
3.  Adjust all valves to their full open positions. Turn on 

the line power to all heat pumps.

4.  Room temperature should be within the minimum-

maximum ranges of table 7. During start-up checks, 
loop water temperature entering the heat pump 
should be between 60°F [16°C] and 95°F [35°C].

5.  Two factors determine the operating limits 

of ClimateMaster heat pumps, (a) return air 
temperature, and (b) water temperature. When any 
one of these factors is at a minimum or maximum 
level, the other factor must be at normal level to 
ensure proper unit operation.

a.  Adjust the unit thermostat to the warmest setting. 

Place the thermostat mode switch in the “COOL” 
position. Slowly reduce thermostat setting until 
the compressor activates.

b.  Check for cool air delivery at the unit grille within a 

few minutes after the unit has begun to operate.

 

Note: Units have a fi ve minute time delay in 
the control circuit that can be eliminated on the 
CXM/DXM control board as shown in Figure 23. 
See controls description for details.

c.   Verify that the compressor is on and that the water 

fl ow rate is correct by measuring pressure drop 
through the heat exchanger using the P/T plugs 
and comparing to table 9.

d.   Check the elevation and cleanliness of the 

condensate lines. Dripping may be a sign of a 
blocked line. Check that the condensate trap is 
fi lled to provide a water seal.

e.   Refer to table 11. Check the temperature of both 

entering and leaving water. If temperature is within 
range, proceed with the test. Verify correct water 
fl ow by comparing unit pressure drop across the 
heat exchanger versus the data in table 9. Heat of 
rejection (HR) can be calculated and compared to 
submittal data capacity pages.  The formula for HR 
for systems with water is as follows:
HR (Btuh) = TD x GPM x 500,where TD is the 
temperature difference between the entering and 
leaving water, and GPM is the fl ow rate in U.S. 
GPM, determined by comparing the pressure drop 
across the heat exchanger to table 9. In S-I units, 
the formula is as follows: HR (kW) = TD x l/s x 4.18.

f. 

Check air temperature drop across the air coil when 
compressor is operating. Air temperature drop 
should be between 15

°

F and 25

°

F [8°C and 14°C].

g.  Turn thermostat to “OFF” position. A hissing noise 

indicates proper functioning of the reversing valve.

6. Allow fi ve (5) minutes between tests for pressure to 

equalize before beginning heating test.

a.  Adjust the thermostat to the lowest setting. Place 

the thermostat mode switch in the “HEAT” position.

b.  Slowly raise the thermostat to a higher 

temperature until the compressor activates.

c.  Check for warm air delivery within a few minutes 

after the unit has begun to operate.

d.  Refer to table 11. Check the temperature of both 

entering and leaving water. If temperature is within 
range, proceed with the test. If temperature is 
outside of the operating range, check refrigerant 
pressures and compare to table 10. Verify correct 
water fl ow by comparing unit pressure drop across 
the heat exchanger versus the data in table 9. 
Heat of extraction (HE) can be calculated and 
compared to submittal data capacity pages.  The 
formula for HE for systems with water is as follows: 

 

HE (kW) = TD xGPM x 500, where TD is the 
temperature difference between the entering 
and leaving water, and l/s is the fl ow rate in U.S. 
GPM, determined by comparing the pressure drop 
across the heat exchanger to tables 10a through 
10e. In S-I units, the formula is as follows: HE (kW) 
= TD x l/s x 4.18.

e.  Check air temperature rise across the air coil when 

compressor is operating. Air temperature rise 
should be between 20°F and 30°F [11°C and 17°C]. 

f.  Check for vibration, noise, and water leaks.

7.  If unit fails to operate, perform troubleshooting analysis 

(see troubleshooting section). If the check described fails 
to reveal the problem and the unit still does not operate, 
contact a trained service technician to ensure proper 
diagnosis and repair of the equipment.

8.  When testing is complete, set system to maintain 

desired comfort level.

9.  BE CERTAIN TO FILL OUT AND FORWARD ALL WARRANTY 

REGISTRATION PAPERS TO CLIMATEMASTER.

Note: If performance during any mode appears 
abnormal, refer to the CXM/DXM section or 
troubleshooting section of this manual. To obtain 
maximum performance, the air coil should be cleaned 
before start-up. A 10% solution of dishwasher 
detergent and water is recommended.

Unit Start-Up Procedure

Summary of Contents for Tranquility 16

Page 1: ...l Power Wiring 22 Electrical Power Low Voltage Wiring 23 Electrical Low Voltage Wiring 24 Electrical Thermostat Wiring 25 TC Blower Performance Data 26 Typical Wiring Diagram Units with DXM Board and...

Page 2: ...2 ClimateMaster Water Source Heat Pumps CL IM ATEM ASTER WATER SOURCE HEAT PUMPS Tranquility Compact TC Series R ev 02 04 13 This Page Intentionally Left Blank...

Page 3: ...D RANGE w ULTRAQUIET 0 NONE FUTURE USE A Copper Water Coil w CoatedAir Coil HEAT EXCHANGER OPTIONS C Copper Water Coil w Non CoatedAir Coil L LEFT RETURN RETURNAIR OPTIONS R RIGHT RETURN B BACK DISCHA...

Page 4: ...tenance information which is important but which is not hazard related WARNING The EarthPure Application and Service Manual should be read and understood before attempting to service refrigerant circu...

Page 5: ...nstalling any of the system components Remove any dirt or debris found in or on these components Pre Installation Installation Operation and Maintenance instructions are provided with each unit Horizo...

Page 6: ...24x21 75 20x17 25 24x21 76 24x28 25 24x28 25 Filter Standard 1 Throwaway 10x18 10x18 10x18 20x20 20x20 20x20 20x20 24x24 20x20 24x24 1 14x24 1 18x24 1 14x24 1 18x24 Weight Operating lbs 103 105 114 1...

Page 7: ...anels Provide sufficient room to make water electrical and duct connection s If the unit is located in a confined space such as a closet provisions must be made for return air to freely enter the spac...

Page 8: ...QLW 3RZHU LVFRQQHFW 3RZHU LULQJ QVXODWHG VXSSO GXFW ZLWK DW OHDVW RQH GHJ HOERZ WR UHGXFH DLU QRLVH 5HWXUQ LU 6XSSO LU 8QLW DQJHU PP WKUHDGHG URGV 8QLW 3RZHU OH LEOH XFW RQQHFWRU 2SWLRQDO RZ 3UHVVXUH...

Page 9: ...Lift out the access panel and set aside Lift and rotate the discharge panel to the other position as shown being careful with the blower wiring 3 Check blower wire routing and connections for tension...

Page 10: ...s and model of the specific unit If the unit is connected to existing ductwork a previous check should have been made to ensure that the ductwork has the capacity to handle the airflow required for th...

Page 11: ...8 for typical installation illustrations Refer to unit submittal data or engineering design guide for dimensional data 1 Install the unit on a piece of rubber neoprene orother mounting pad material fo...

Page 12: ...stalled and pitched away from the unit to allow for proper drainage This connection must meet all local plumbing building codes Vertical units utilize a condensate hose inside the cabinet as a trappin...

Page 13: ...water temperature is below the minimum expected dew point of the pipe ambient conditions Insulation is required if loop water temperature drops below the dew point insulation is required for ground l...

Page 14: ...ve and or J type swivel connection Balancing valves and an external low pressure drop solenoid valve for use in variable speed pumping systems may also be included in the hose kit The piping system sh...

Page 15: ...er your local sales office should be consulted to determine the antifreeze best suited to your area Freeze protection should be maintained to 15 F 9 C below the lowest expected entering loop temperatu...

Page 16: ...umps CL IM ATEM ASTER WATER SOURCE HEAT PUMPS Tranquility Compact TC Series R ev 02 04 13 Ground Loop Heat Pump Applications Figure 13 Typical Ground Loop Application High and Low Voltage Knockouts Vi...

Page 17: ...PVC or CPVS piping may cause failure of the PVC CPVC PVC CPVC piping should never be used as supply or return water piping with water source heat pump products containing HFC 410A as system failures a...

Page 18: ...esired flow of 1 5 to 2 gpm per ton 2 0 to 2 6 l m per kW is achieved A second method of flow control requires a flow control device mounted on the outlet of the water control valve The device is typi...

Page 19: ...ll 0 5 ppm Maximum Maximum Allowable at maximum water temperature Chloride Levels 10 C 24 C 38 C Copper Cupronickel 20ppm NR NR 150 ppm NR NR 304 SS 400 ppm 250 ppm 150 ppm 316 SS 1000 ppm 550 ppm 375...

Page 20: ...on and sound transmission to the building General Line Voltage Wiring Be sure the available power is the same voltage and phase shown on the unit serial plate Line and low voltage wiring must be done...

Page 21: ...8 230 60 3 197 254 1 8 9 58 0 3 00 11 9 14 1 20 F 460 60 3 414 506 1 4 2 28 0 1 70 5 9 7 0 15 036 G 208 230 60 1 197 254 1 16 7 79 0 1 80 18 5 22 7 35 E 265 60 1 239 292 1 13 5 72 0 2 00 15 5 18 9 30...

Page 22: ...gher static is required Low speed will deliver approximately 85 of rated airflow at 0 10 in w g 25 Pa An optional high static blower is available on some models WARNING Disconnect electrical power sou...

Page 23: ...l connections Review the appropriate AOM Application Operation and Maintenance manual for units with DDC controls Low Water Temperature Cutout Selection The CXM DXM control allows the field selection...

Page 24: ...e 19 Accessory Wiring Water Solenoid Valves An external solenoid valve s should be used on ground water installations to shut off flow to the unit when the compressor is not operating A slow closing v...

Page 25: ...aled to prevent erroneous temperature measurement Position the thermostat back plate against the wall so that it appears level and so the thermostat wires protrude through the middle of the back plate...

Page 26: ...D 988 960 922 846 713 589 HS LOW 979 960 931 912 884 855 827 751 675 030 HI 1000 750 1102 1074 1045 1017 979 903 798 MED 1188 1169 1140 1121 1093 1064 1036 1017 988 960 922 846 LOW 1064 1045 1017 998...

Page 27: ...27 climatemaster com THE SMART SOLUTION FOR ENERGY EFFIC I E NC Y Tranquility Compact TC Series R ev 0 2 0 4 1 3 Typical Wiring Diagram Units with DXM Board and PSC Fan Motor Three Phase...

Page 28: ...28 ClimateMaster Water Source Heat Pumps CL IM ATEM ASTER WATER SOURCE HEAT PUMPS Tranquility Compact TC Series R ev 02 04 13 Typical Wiring Diagram Units with CXM Board and PSC Fan Motor Single Phase...

Page 29: ...4 CXM LED And Alarm Relay Operations CAUTION CAUTION Do not restart units without inspection and remedy of faulting condition Equipment damage may occur CXM Control For detailed control information se...

Page 30: ...clipped under extenuating circumstances as recommended by ClimateMaster technical services Not Clipped 30 F 1 C Clipped 10 F 12 C Alarm relay setting Jumper 4 JW4 AL2 Dry provides field selection of t...

Page 31: ...Accessory DIP Switch Settings 1 3 Thermostat type heat pump or heat cool DIP 1 3 provides selection of thermostat type Heat pump or heat cool thermostats can be selected When in heat cool mode Y1 is t...

Page 32: ...10 sec pause 2 quick flashes 10 sec pause etc Low pressure switch The low pressure switch must be open and remain open for 30 continuous seconds during on cycle to be recognized as a low pressure faul...

Page 33: ...the unit The green status light will flash code 3 when the unit is in ESD mode ESD mode code 3 green status LED Diagnostic Features The LED on the CXM board advises the technician of the current statu...

Page 34: ...e 8 are not normal or continuous operating conditions Minimum maximum limits are start up conditions to bring the building space up to occupancy temperatures Units are not designed to operate under th...

Page 35: ...per 1000 l of water or other equivalent approved cleaning agent Reset the boiler to raise the loop temperature to 100 F 38 C Circulate the solution for a minimum of 8 to 24 hours At the end of this pe...

Page 36: ...former has the properly selected voltage tap Entering water and air Ensure that entering water and air temperatures are within operating limits of Table 8a b Low water temperature cutout Verify that l...

Page 37: ...e 9 In S I units the formula is as follows HR kW TD x l s x 4 18 f Check air temperature drop across the air coil when compressor is operating Air temperature drop should be between 15 F and 25 F 8 C...

Page 38: ...the electrical panel Exercise caution when working with energized equipment CAUTION Verify that ALL water control valves are open and allow water flow prior to engaging the compressor Freezing of the...

Page 39: ...23 4 2 6 17 6 2 1 14 7 1 8 12 4 4 5 0 28 5 9 40 6 4 6 31 5 3 9 26 9 3 4 23 4 024 3 0 0 19 2 2 15 2 1 7 11 6 1 4 9 6 1 2 8 3 4 5 0 28 4 0 27 6 3 2 22 2 2 8 19 3 2 5 17 2 6 0 0 38 7 2 49 6 5 9 40 6 5 2...

Page 40: ...3 5 4 7 4 3 5 5 5 17 23 18 24 19 25 50 1 5 2 25 3 124 134 122 132 120 130 211 231 199 219 187 207 9 14 12 17 15 20 10 15 9 14 8 13 18 20 13 2 15 2 8 4 10 4 17 23 17 23 17 23 101 111 105 115 110 120 3...

Page 41: ...5 18 24 19 25 19 25 50 1 5 2 25 3 136 146 134 144 133 143 198 218 183 203 171 191 10 15 10 15 11 16 14 19 13 18 13 18 22 24 16 5 18 5 11 13 19 25 19 25 19 25 101 111 105 115 109 119 302 322 306 326 3...

Page 42: ...20 15 20 7 7 9 7 5 7 7 7 3 7 5 7 19 27 19 27 20 28 50 1 5 2 25 3 121 131 120 130 120 130 249 269 231 251 214 234 12 17 12 17 12 17 9 14 8 13 8 13 19 4 21 4 14 4 16 4 9 4 11 4 17 25 18 26 18 26 91 101...

Page 43: ...96 106 100 110 309 329 313 333 317 337 8 13 9 14 9 14 3 8 3 8 3 8 9 5 11 5 7 9 4 6 6 6 23 31 24 32 24 32 70 1 5 2 25 3 129 139 129 139 129 139 337 357 328 348 300 320 8 13 8 13 8 13 12 17 11 16 11 16...

Page 44: ...ts should never be operated without a filter Washable high efficiency electrostatic filters when dirty can exhibit a very high pressure drop for the fan motor and reduce air flow resulting in poor per...

Page 45: ...ck for piping slope away from unit Check slope of unit toward outlet Poor venting Check vent location X Moisture on sensor Check for moisture shorting to air coil X X Plugged air filter Replace air fi...

Page 46: ...e Check fan motor operation and air flow restrictions Too high of external static Check static vs blower table X Reduced or no water flow in cooling Check pump operation or valve operation setting Che...

Page 47: ...eed Tap PSC Temperatures F or C Antifreeze Pressures PSIG or kPa Type Cooling Mode Heating Mode Entering Fluid Temperature Leaving Fluid Temperature Temperature Differential Return Air Temperature DB...

Page 48: ...035 6625 6 5 68 7 21 7 1 1 6 6 36 6 7 36 6 7 5 2 3 7 1 48 1 3 16 21 9 9 5 2 36 6 7 36 6 7 7 5 1 7 5 287 36 36 7 5 1 7 5 287 36 36 8VH IRU ZDWHU IRU DQWLIUHH H 7 5 5 5 6 6 1 3 6 1625 3 16 21 9 9 7 5 5...

Page 49: ...suf cient or incorrect system design or the improper application of CM s products CM is not responsible for 1 The costs of any uids refrigerant or other system components or associated labor to repair...

Page 50: ...DWHG LQ D PDQQHU FRQWUDU WR 0 V SULQWHG LQVWUXFWLRQV 3URGXFWV ZKLFK KDYH GHIHFWV GDPDJH RU LQVXI FLHQW SHUIRUPDQFH DV D UHVXOW RI LQVXI FLHQW RU LQFRUUHFW V VWHP GHVLJQ RU WKH LPSURSHU DSSOLFDWLRQ LQV...

Page 51: ...51 climatemaster com THE SMART SOLUTION FOR ENERGY EFFIC I E NC Y Tranquility Compact TC Series R ev 0 2 0 4 1 3 Notes...

Page 52: ...ANDARD 13256 1 HEAT PUMPS W A T E R T O AIR BRI N E T O A I R ClimateMaster Inc 2009 ClimateMaster works continually to improve its products As a result the design and specifications of each product a...

Reviews: