![ClimateMaster Genesis Compact (GC) Series Installation, Operation & Maintenance Instructions Manual Download Page 92](http://html1.mh-extra.com/html/climatemaster/genesis-compact-gc-series/genesis-compact-gc-series_installation-operation-and-maintenance-instructions-manual_2624719092.webp)
92
C l i m a t e M a s t e r W a t e r- S o u r c e H e a t i n g a n d C o o l i n g S y s t e m s
C L I M AT E M A S T E R W AT E R - S O U R C E H E AT P U M P S
P a c k a g e d U n i t s
R e v. : 1 / 0 6 / 0 9 B
Unit Operating Conditions
NOTE: Tables 11 through 16 include the following notes:
• Air
fl
ow is at nominal (rated) conditions;
• Entering air is based upon 70°F [21°C] DB in heating
and 80/67°F [27/19°C] in cooling;
• Subcooling is based upon head pressure at
compressor service port;
• GC series units have cap tube expansion devices; all
others in this manual include TXV expansion devices;
• Cooling air and water values can vary greatly with
changes in humidity level.
Table 17: Water Temperature Change Through Heat
Exchanger
Water Flow, gpm [l/m]
Rise, Cooling
°F, [°C]
Drop, Heating
°F, [°C]
For Closed Loop: Ground Source or
Closed Loop Systems at 3 gpm per
ton [3.2 l/m per kW]
9 - 12
[5 - 6.7]
4 - 8
[2.2 - 4.4]
For Open Loop: Ground Water
Systems at 1.5 gpm per ton
[1.6 l/m per kW]
20 - 26
[11.1 - 14.4]
10 - 17
[5.6 - 9.4]
Table 15: GC Series Typical Unit Operating Pressures and Temperatures (60Hz - I.P. Units)
Entering
Water
Temp °F
Water
Flow
GPM/ton
Full Load Cooling - without HWG active
Full Load Heating - without HWG active
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Superheat
Subcooling
Water
Temp Rise
°F
Air Temp
Drop °F
DB
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Superheat
Subcooling
Water
Temp Drop
°F
Air Temp
Rise °F DB
60
1.5
2.25
3
66-75
65-75
64-74
160-190
145-175
130-160
10-20
15-25
20-30
6-16
8-18
10-20
20-23
12-15
8-12
20-25
20-25
20-25
60-70
63-73
65-75
205-230
210-238
215-242
10-18
10-18
10-18
1-5
1-5
1-5
12.1-14
7.2-9.0
5.8-6.9
23-29
24-30
25-31
70
1.5
2.25
3
71-82
70-80
69-79
200-230
185-215
175-205
10-20
15-25
20-30
6-16
8-18
10-20
19-22
12-17
7-12
19-24
19-24
19-24
66-72
68-74
70-76
205-230
210-238
215-242
15-25
15-25
15-25
2-8
2-8
2-8
14.0-15.2
9.0-10.2
6.7-7.9
28-34
30-37
31-38
80
1.5
2.25
3
75-85
74-84
72-82
230-260
215-245
200-230
10-16
13-20
15-25
5-12
7-14
8-15
19-22
12-17
7-12
18-23
18-23
18-23
68-74
70-76
72-76
205-230
210-238
215-242
20-35
20-35
20-35
2-10
2-10
2-10
14.2-15.9
9.9-11.1
6.9-8.1
32-39
33-41
35-42
90
1.5
2.25
3
79-90
77-88
75-87
260-290
245-275
230-260
2-8
5-12
8-16
1-8
2-9
3-10
18-21
10-14
6-11
17-23
17-23
17-23
Table 16: GC Series Typical Unit Operating Pressures and Temperatures (50Hz - S.I. Units)
Entering
Water
Temp °C
Water
fl
ow
l/m per kW
Cooling - without HWG active
Heating - without HWG active
Suction
Pressure
bar
Discharge
Pressure
bar
Superheat
°C
Subcooling
°C
Water
Temp Rise
°C
Air
Temp Drop
°C
Suction
Pressure
bar
Discharge
Pressure
bar
Superheat
°C
Subcooling
°C
Water
Temp Drop
°C
Air
Temp Rise
°C
15
1.6
2.4
3.2
4.6-5.2
4.5-5.2
4.4-5.1
11.0-13.1
10.0-12.1
9.0-11.0
6-11
8-14
11-17
3-9
4-10
6-11
11-13
7-8
4-7
11-14
11-14
11-14
4.1-4.8
4.3-5.0
4.5-5.2
14.1-15.9
14.5-16.4
14.8-16.7
6-10
6-10
6-10
1-3
1-3
1-3
7-8
4-5
3-4
13-16
13-17
14-17
20
1.6
2.4
3.2
4.9-5.7
4.8-5.5
4.8-5.4
13.8-15.9
12.8-14.8
12.1-14.1
6-11
8-14
11-17
3-9
4-10
6-11
11-12
7-9
4-7
11-13
11-13
11-13
4.6-5.0
4.7-5.1
4.8-5.2
14.1-15.9
14.5-16.4
14.8-16.7
8-14
8-14
8-14
1-4
1-4
1-4
8-8
5-6
4-4
16-19
17-21
17-21
27
1.6
2.4
3.2
5.2-5.9
5.1-5.8
5.0-5.7
15.9-17.9
14.8-16.9
13.8-15.9
6-9
7-11
8-14
3-7
4-8
4-8
11-12
7-9
4-7
10-13
10-13
10-13
4.7-5.1
4.8-5.2
5.0-5.2
14.1-15.9
14.5-16.4
14.8-16.7
11-19
11-19
11-19
1-6
1-6
1-6
8-9
6-6
4-5
18-22
18-23
19-23
32
1.6
2.4
3.2
5.4-6.2
5.3-6.1
5.2-6.0
17.9-20.0
16.9-19.0
15.9-17.9
1-4
3-7
4-9
1-4
1-5
2-6
10-12
6-8
3-6
9-13
9-13
9-13