C l i m a t e M a s t e r W a t e r- S o u r c e H e a t i n g a n d C o o l i n g S y s t e m s
C L I M AT E M A S T E R W AT E R - S O U R C E H E AT P U M P S
P a c k a g e d U n i t s
R e v. : 1 / 0 6 / 0 9 B
Unit Operating Conditions
018
Full Load Cooling - without HWG active
Full Load Heating - without HWG active
Entering
Water
Temp °F
Water
Flow
GPM/ton
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Superheat
Subcool-
ing
Water
Temp Rise
°F
Air Temp
Drop °F
DB
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Superheat
Subcool-
ing
Water
Temp Drop
°F
Air Temp
Rise °F DB
30
1.5
2.25
3
120-130
120-130
120-130
155-175
142-162
128-148
27-32
27-32
27-32
11-16
9-14
9-14
16.9-19.9
12.5-14.5
8.1-10.1
16-22
17-23
17-23
73-83
75-85
78-88
268-288
270-290
272-292
8-13
8-13
8-13
4-9
4-9
4-9
6.1-8.1
4.4-6.4
2.9-4.9
15-21
16-22
16-22
50
1.5
2.25
3
137-147
137-147
137-147
220-240
206-226
192-212
16-21
16-21
16-21
10-15
8-13
8-13
17-19
12.6-14.6
8.4-10.4
16-22
17-23
17-23
102-112
106-116
110-120
295-315
297-317
299-319
8-13
8-13
8-13
8-13
8-13
8-13
9.1-11.1
6.9-8.9
4.7-6.7
20-26
21-27
21-27
70
1.5
2.25
3
142-152
142-152
142-152
287-307
273-239
259-279
7-12
7-12
7-12
10-15
8-13
8-13
15.9-17.9
11.8-13.8
7.8-9.8
16-22
17-23
17-23
131-141
137-147
144-154
324-344
326-346
328-348
9-14
9-14
9-14
10-15
10-15
10-15
12.1-14.1
9.3-11.3
6.6-8.6
25-33
26-34
26-34
90
1.5
2.25
3
146-156
146-156
146-156
375-395
361-381
347-367
6-11
6-11
6-11
10-15
8-13
8-13
14.9-16.9
11-13
7.2-9.2
16-22
17-23
17-23
174-184
180-190
187-197
360-380
367-387
374-394
10-15
11-16
12-17
12-17
12-17
12-17
15.8-17.8
11.9-13.9
8-10
32-40
33-41
33-41
110
1.5
2.25
3
154-164
154-164
154-164
478-498
461-481
445-465
6-11
6-11
6-11
10-15
8-13
8-13
14-16
10.2-12.2
6.5-8.5
16-22
16-22
16-22
012
Full Load Cooling
Full Load Heating
Entering
Water
Temp °F
Water
Flow
GPM/ton
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Superheat
Subcooling
Water
Temp Drop
°F
Air Temp
Rise °F
DB
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Superheat
Sub cooling
Water
Temp Drop
°F
Air Temp
Rise °F DB
30
1.5
2.25
3
98-108
98-108
99-109
140-160
135-155
127-148
36-41
36-41
36-41
14-19
12-17
10-15
17.1-19.1
12.5-14.5
7.9-9.9
19-25
19-25
19-25
72-82
85-95
78-88
301-321
304-324
308-328
9-14
9-14
9-14
12-17
12-17
12-17
6.5-8.5
4.7-6.7
2.9-4.9
21-27
21-27
22-28
50
1.5
2.25
3
118-128
118-128
118-128
215-235
200-220
185-205
22-27
22-27
22-27
14-19
12-17
10-15
18.1-20.1
13.1-15.1
8.1-10.1
20-26
20-26
19-25
100-110
98-108
95-105
337-357
334-354
332-352
10-15
10-15
11-16
15-20
15-20
15-20
9.5-11.5
6.6-8.6
3.8-5.8
26-32
26-32
26-32
70
1.5
2.25
3
132-142
132-142
132-142
300-320
263-282
245-265
11-16
11-16
12-17
12-17
10-15
7-12
17-19
12.6-14.6
8.2-10.2
19-25
19-25
19-25
115-125
112-122
110-120
361-381
360-380
356-376
19-24
20-25
21-26
18-23
18-23
18-23
11.1-13.1
8-10
4.8-6.8
29-35
29-35
29-35
90
1.5
2.25
3
138-148
138-148
138-148
366-386
353-373
340-360
9-14
9-14
9-14
11-16
9-14
6-11
15.8-17.8
14.9-16.9
14-16
18-24
18-24
18-24
122-132
123-133
124-134
376-396
378-398
380-400
34-39
36-41
38-43
22-27
22-27
23-28
12.1-14.1
9-11
5.8-7.8
32-38
32-38
32-38
110
1.5
2.25
3
145-155
145-155
145-155
453-473
442-462
431-451
9-14
9-14
9-14
9-14
7-12
5-10
14.7-16.7
10.8-12.8
6.8-8.8
16-22
16-22
17-23
024
Full Load Cooling - without HWG active
Full Load Heating - without HWG active
Entering
Water
Temp °F
Water
Flow
GPM/ton
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Superheat
Subcool-
ing
Water
Temp Rise
°F
Air Temp
Drop °F
DB
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Superheat
Subcool-
ing
Water
Temp Drop
°F
Air Temp
Rise °F DB
30
1.5
2.25
3
115-125
115-125
115-125
154-174
141-161
127-147
40-45
40-45
40-45
8-13
6-11
6-11
16.5-18.5
12.1-14.1
77.7-9.7
19-25
20-26
20-26
73-83
75-85
78-88
283-303
285-305
287-307
8-12
8-12
8-12
6-11
6-11
6-11
5.9-7.9
4.2-6.2
2.7-4.7
16-22
17-23
18-24
50
1.5
2.25
3
115-120
115-120
115-120
209-229
195-215
181-201
24-29
24-29
24-29
10-15
8-13
8-13
15.7-17.7
11.6-13.6
7.6-9.6
18-24
18-24
18-24
102-112
106-116
110-120
313-333
314-334
316-336
8-12
8-12
8-12
8-13
8-13
8-13
8.9-10.9
6.7-8.7
4.5-6.5
22-28
23-29
23-29
70
1.5
2.25
3
136-146
136-146
136-146
275-295
261-281
247-267
6-11
6-11
6-11
6-11
5-10
4-9
15.7-17.7
11.6-13.6
7.6-9.6
18-24
18-24
18-24
128-138
134-144
141-151
340-360
342-362
344-364
9-14
9-14
9-14
9-14
9-14
9-14
11.3-13.3
8.5-10.5
5.8-7.8
27-34
28-35
28-35
90
1.5
2.25
3
140-150
140-150
140-150
361-381
347-367
333-353
6-11
6-11
6-11
6-11
5-10
4-9
14.9-16.9
11-13
7.2-9.2
18-24
18-24
18-24
162-172
166-176
171-181
370-390
376-396
383-403
14-19
15-20
16-21
9-14
9-14
9-14
14.4-16.4
10.8-12.8
7.1-9.1
32-40
34-42
34-42
110
1.5
2.25
3
144-154
144-154
144-154
460-480
445-465
428-448
6-11
6-11
6-11
6-11
4-9
4-9
13.9-15.9
10.2-12.2
6.5-8.5
17-23
17-23
17-23
Table 12: TS Series Typical Unit Operating Pressures and Temperatures: Continued