WARNING!
When the disconnect switch is closed, high
voltage is present in some areas of the electrical panel.
Exercise caution when working with energized equipment.
CAUTION!
Verify that ALL water control valves are open and
allow water
fl
ow prior to engaging the compressor. Freezing
of the coax or water lines can permanently damage the heat
pump.
Figure 28: Test Mode Pins
WARNING!
CAUTION!
Table 10a: TT Coax Water Pressure Drop
UNIT OPERATING CONDITIONS
Model
U.S.
GPM
l/s
l/m
Pressure Drop, psi [kPa]*
30°F [-1°C]
50°F [10°C]
70°F [21°C]
90°F [32°C]
026
4.0
0.252
15
1.5 [10.3]
1.3 [9.0]
1.1 [7.6]
1.0 [6.9]
6.0
0.378
23
3.1 [21.4]
2.6 [17.9]
2.3 [15.9]
2.1 [14.5]
7.0
0.441
26
4.1 [28.3]
3.4 [23.4]
3.0 [20.7]
2.7 [18.6]
8.0
0.504
30
5.1 [35.2]
4.3 [29.7]
3.8 [26.2]
3.4 [23.4]
038
4.0
0.252
15
1.2 [8.3]
1.0 [6.9]
0.8 [5.5]
0.6 [4.1]
6.0
0.378
23
2.6 [17.9]
2.5 [17.2]
2.3 [15.9]
2.1 [14.5]
8.0
0.504
30
4.5 [31.0]
4.2 [29.0]
4.0 [27.6]
3.7 [25.5]
9.0
0.567
34
5.7 [39.3]
5.2 [35.9]
4.8 [33.1]
4.4 [30.3]
049
5.5
0.347
21
1.1 [7.6]
0.9 [6.2]
0.8 [5.5]
0.7 [4.8]
8.3
0.523
31
2.2 [15.2]
2.1 [14.5]
2.0 [13.8]
1.8 [12.4]
11.0
0.693
42
3.9 [26.9]
3.6 [24.8]
3.2 [22.1]
3.1 [21.4]
12.0
0.756
45
4.5 [31.0]
4.2 [29.0]
3.8 [26.2]
3.5 [24.1]
064
7.0
0.441
26
0.5 [3.4]
0.3 [2.1]
0.2 [1.4]
0.1 [0.7]
10.5
0.662
40
1.9 [13.1]
1.8 [12.4]
1.7 [11.7]
1.6 [11.0]
14.0
0.882
53
3.9 [26.9]
3.5 [24.1]
3.2 [22.1]
2.9 [20.0]
15.0
0.945
57
4.8 [33.1]
4.3 [29.7]
3.9 [26.9]
3.5 [24.1]
072
7.5
0.473
29
1.7 [11.7]
1.5 [10.3]
1.3 [9.0]
1.3 [9.0]
11.3
0.712
43
3.9 [26.9]
3.4 [23.4]
3.0 [20.7]
2.8 [19.3]
15.0
0.945
57
6.9 [47.6]
6.0 [41.4]
5.4 [37.2]
5.0 [34.5]
17.0
1.071
64
8.9 [61.4]
7.7 [53.1]
6.9 [47.6]
6.5 [44.8]
*Note: To convert
kPa to millibars,
multiply by 10.
Short test pins
together to enter Test
Mode and speed-up
timing and delays for
20 minutes.
Unit Start-Up Procedure