![ClimateMaster Genesis Compact (GC) Series Installation, Operation & Maintenance Instructions Manual Download Page 36](http://html1.mh-extra.com/html/climatemaster/genesis-compact-gc-series/genesis-compact-gc-series_installation-operation-and-maintenance-instructions-manual_2624719036.webp)
36
C l i m a t e M a s t e r W a t e r- S o u r c e H e a t i n g a n d C o o l i n g S y s t e m s
C L I M AT E M A S T E R W AT E R - S O U R C E H E AT P U M P S
P a c k a g e d U n i t s
R e v. : 1 / 0 6 / 0 9 B
Electrical - Line Voltage
Table 4k: Tranquility 16™ (TC) Series Electrical Data - (Standard 50Hz Units)
TC
Model
Voltage
Code
Rated
Voltage
Voltage
Min/
Max
Compressor
Fan
Motor
FLA
Total
Unit
FLA
Min
Circuit
Amp
Max
Fuse/
HACR
QTY
RLA
LRA
015
V
220/240-50-1
209/252
1
4.7
23.0
0.9
5.6
6.7
15
018
V
220/240-50-1
209/252
1
5.9
24.0
0.9
6.8
8.2
15
024
V
220/240-50-1
209/252
1
9
52.0
1.3
10.3
12.6
20
030
V
220/240-50-1
209/252
1
11.2
60.0
2.7
13.9
16.7
25
U
380/415-50-3
361/436
1
3.9
28.0
1.7
5.6
6.6
15
036
V
220/240-50-1
209/252
1
13.5
67.0
2.0
15.5
18.9
30
U
380/415-50-3
361/436
1
5.4
38.0
1.2
6.6
8.0
15
042
U
380/415-50-3
361/436
1
6
46.0
1.7
7.7
9.2
15
048
U
380/415-50-3
361/436
1
6.1
43.0
1.8
7.9
9.4
15
060
U
380/415-50-3
361/436
1
7.8
51.5
2.5
10.3
12.3
20
HACR circuit breaker in USA only
All fuses Class RK-5