Electrical - Line Voltage
Table 4n: Genesis Standard (GR) Series Electrical Data
GRH/V
036
G
R22
208-
230/60/1
197/254
1
14.4
82.0
3.00
17.4
21.0
35
0.8
18.2
21.8
35
E
R22
265/60/1
239/292
1
12.2
64.0
2.70
14.9
18.0
30
0.7
15.6
18.7
30
H
R22
208-
230/60/3
197/254
1
9.4
65.5
3.00
12.4
14.8
20
0.8
13.2
15.6
20
F
R22
460/60/3
414/506
1
4.4
33.0
1.70
6.1
7.2
15
0.7
6.8
7.9
15
V
R22
220-
240/50/1
197/254
1
12.2
83.0
2.7
14.9
18.0
30
N/A
N/A
N/A
N/A
V
R407C
220-
240/50/1
197/254
1
11.5
83.0
2.7
17.2
20.8
35
N/A
N/A
N/A
N/A
GRH/V
042
G
R22
208-
230/60/1
197/254
1
16.2
96.0
3.00
19.2
23.3
35
0.8
20.0
24.1
40
H
R22
208-
230/60/3
197/254
1
10.3
75.0
3.00
13.3
15.9
25
0.8
14.1
16.7
25
F
R22
460/60/3
414/506
1
4.3
40.0
1.70
6.0
7.1
15
0.7
6.7
7.8
15
N
R22
575/60/3
518/633
1
3.7
31.0
1.50
5.2
6.0
15
N/A
N/A
N/A
N/A
U
R22
380-
420/50/3
342/462
1
4.3
40.0
1.7
6.0
7.1
15
N/A
N/A
N/A
N/A
U
R407C
380-
420/50/3
342/462
1
5.5
34.5
1.7
6.0
7.1
15
N/A
N/A
N/A
N/A
GRH/V
048
G
R22
208-
230/60/1
197/254
1
18.3
102.0
3.40
21.7
26.3
40
1.07
22.8
27.3
45
H
R22
208-
230/60/3
197/254
1
12.6
91.0
3.40
16.0
19.2
30
1.07
17.1
20.2
20
F
R22
460/60/3
414/506
1
5.7
42.0
1.80
7.5
8.9
15
1.07
8.6
10.0
15
N
R22
575/60/3
518/633
1
4.7
39.0
1.40
6.1
7.3
15
N/A
N/A
N/A
N/A
U
R22
380-
420/50/3
342/462
1
5.7
42.0
1.8
7.5
8.9
15
N/A
N/A
N/A
N/A
U
R407C
380-
420/50/3
342/462
1
5.9
42.0
1.8
7.5
8.9
15
N/A
N/A
N/A
N/A
All GR Units
Standard GR Units
GR Units with Secondary Pump
Model
Voltage
Code
Refrigerant
Voltage
Min/Max
Voltage
Compressor
Fan
Motor
FLA
Total
Unit
FLA
Min
Circuit
Amps
Max
Fuse/
HACR
Pump
FLA
Total
Unit
FLA
Min
Circuit
Amps
Max
Fuse/
HACR
QTY
RLA
LRA
GRH/V
048
High
Static
G
R22
208-
230/60/1
197/254
1
18.3
102.0
4.9
23.2
27.8
45
1.07
24.3
28.8
45
H
R22
208-
230/60/3
197/254
1
12.6
91.0
4.9
17.5
20.7
30
1.07
18.6
21.7
30
F
R22
460/60/3
414/506
1
5.7
42.0
2.5
8.2
9.6
15
1.07
9.3
10.7
15
N
R22
575/60/3
518/633
1
4.7
39.0
1.9
6.6
7.6
15
N/A
N/A
N/A
N/A
GRH/V
060
G
R22
208-
230/60/1
197/254
1
25.6
170.0
4.90
30.5
36.9
60
1.07
31.6
38.0
60
H
R22
208-
230/60/3
197/254
1
14.7
124.0
4.90
19.6
23.3
35
1.07
20.7
24.3
35
F
R22
460/60/3
414/506
1
7.4
59.6
2.50
9.9
11.8
15
1.07
11.0
12.8
20
N
R22
575/60/3
518/633
1
5.9
49.4
1.90
7.8
9.3
15
N/A
N/A
N/A
N/A
U
R22
380-
420/50/3
342/462
1
7.4
59.6
2.5
9.9
11.8
15
N/A
N/A
N/A
N/A
U
R407C
380-
420/50/3
342/462
1
8.2
61.8
2.5
9.9
11.8
15
N/A
N/A
N/A
N/A
*
NEUTRAL CONNECTION REQUIRED! All F Voltage (460 vac) units with internal secondary circulators require a four
wire power supply with neutral. ECM motors/internal secondary circulators are rated 265 vac and are wired between
one hot leg and neutral.
HACR circuit breaker in USA only
All fuses Class RK-5