![ClimateMaster Genesis Compact (GC) Series Installation, Operation & Maintenance Instructions Manual Download Page 29](http://html1.mh-extra.com/html/climatemaster/genesis-compact-gc-series/genesis-compact-gc-series_installation-operation-and-maintenance-instructions-manual_2624719029.webp)
29
c l i m a t e m a s t e r. c o m
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
P a c k a g e d U n i t s
R e v. : 1 / 0 6 / 0 9 B
Electrical - Line Voltage
Table 4d: Tranquility 20™ (TS) Series Electrical Data - (PSC High Static Motor & ClimaDry)
All TS Units with High Static PSC Fan Motor
TS (H.S. PSC) Units
TS Units with H.S. PSC Fan Motor
and ClimaDry
Model
Voltage
Code
Rated
Voltage
Voltage
Min/
Max
Compressor
Fan
Motor
FLA
Total
Unit
FLA
Min
Circuit
Amp
Max
Fuse/
HACR
Reheat
Pump
FLA
Total
Unit
FLA
Min
Circuit
Amp
Max
Fuse/
HACR
QTY
RLA
LRA
TSH/V/D
018
G
208-230/60/1
197/254
1
9.0
48.0
1.1
10.1
12.4
20
0.8
10.9
13.2
20
E
265/60/1
239/292
1
8.4
40.0
0.9
9.3
11.4
15
0.7
10.0
12.1
20
TSH/V/D
024
G
208-230/60/1
197/254
1
12.8
60.0
1.4
14.2
17.4
30
0.8
15.0
18.2
30
E
265/60/1
239/292
1
10.9
58.0
1.6
12.5
15.2
25
0.7
13.2
15.9
25
H
208-230/60/3
197/254
1
8.0
55.0
1.4
9.4
11.4
15
0.8
10.2
12.2
20
F
*
460/60/3
*
414/506
1
4.0
22.4
0.9
4.9
5.9
15
0.7
5.6
6.6
15
TSH/V/D
030
G
208-230/60/1
197/254
1
13.5
61.0
1.8
15.3
18.7
30
0.8
16.1
19.5
30
E
265/60/1
239/292
1
10.9
58.0
2.0
12.9
15.6
25
0.7
13.6
16.3
25
H
208-230/60/3
197/254
1
8.3
63.0
1.8
10.1
12.2
20
0.8
10.9
13.0
20
F
*
460/60/3
*
414/506
1
4.5
27.0
1.24
5.7
6.9
15
0.7
6.4
7.6
15
TSH/V/D
036
G
208-230/60/1
197/254
1
14.7
72.5
2.0
16.7
20.4
35
0.8
17.5
21.2
35
E
265/60/1
239/292
1
12.5
61.0
1.66
14.2
17.3
25
0.7
14.9
18.0
30
H
208-230/60/3
197/254
1
10.4
63.0
2.0
12.4
15.0
25
0.8
13.2
15.8
25
F
*
460/60/3
*
414/506
1
4.5
32.0
1.0
5.5
6.6
15
0.7
6.2
7.3
15
TSH/V/D
042
G
208-230/60/1
197/254
1
15.4
83.0
3.0
18.4
22.3
35
0.8
19.2
23.1
35
H
208-230/60/3
197/254
1
11.5
77.0
3.0
14.5
17.4
25
0.8
15.3
18.2
25
F
*
460/60/3
*
414/506
1
5.1
35.0
1.7
6.8
8.1
15
0.7
7.5
8.8
15
N
575/60/3
518/633
1
4.3
31.0
1.4
5.7
6.8
15
N/A
N/A
N/A
N/A
TSH/V/D
048
G
208-230/60/1
197/254
1
20.5
109.0
3.4
23.9
29.0
45
1.07
25.0
30.1
50
H
208-230/60/3
197/254
1
14.6
91.0
3.4
18.0
21.7
35
1.07
19.1
22.7
35
F
*
460/60/3
*
414/506
1
7.1
46.0
1.8
8.9
10.7
15
1.07
10.0
11.7
15
N
575/60/3
518/633
1
5.1
34.1
1.4
6.5
7.8
15
N/A
N/A
N/A
N/A
TSH/V/D
060
G
208-230/60/1
197/254
1
26.9
145.0
5.8
32.7
39.4
60
1.07
33.8
40.5
60
H
208-230/60/3
197/254
1
17.6
123.0
5.8
23.4
27.8
45
1.07
24.5
28.9
45
F
*
460/60/3
*
414/506
1
9.6
64.0
2.6
12.2
14.6
20
1.07
13.3
15.7
25
N
575/60/3
518/633
1
6.1
40.0
2.3
8.4
9.9
15
N/A
N/A
N/A
N/A
*
NEUTRAL CONNECTION REQUIRED! All F Voltage (460 vac) units with ClimaDry require a four wire power supply
with neutral. Reheat pump is rated 265 vac and is wired between one hot leg and neutral.