Max Frame Spacing and Footing Options of Panel Dimensions 2m x 1m
Notes
*
The maximum frame spacing is based on the structural capacity of the frame in the edge (perimeter
zone of array. We recommend to perform tests on site for the geotechnical capacity of the driven post.
The spacing may need to be decreased to achieve the available geotechnical capacity of the driven
post following from the test results.
**Footing option 2 recommended for 'Firm' soils with allowable end bearing capacity of 100 kPa (damp
clays, sandy clays, damp sands). Other piers sizes are possible. Contact Clenergy for site specific
conditions.
*For SolarTerrace II-A driven post installation, maximum post height above ground is 1.3m.
*For SolarTerrace II-A concrete pier installation, maximum post height above ground 1.5m.