MINIMUM RECOMMENDED DILUTION VENTILATION RATES FOR CARBON MONOXIDE EXPOSURE CONTROL
PROPANE-POWERED PBU FLOOR BURNISHER NILFISK-ADVANCE, INC.
Machine & Environment
See note 7
Propane Fuel
Consumption
(lbs/hour)
Calculated
CO
Generation
Rate (CFM)
Air Mixing
Factor K
(see Notes 3
and 4)
Dilution Ventilation Requirement, CFM (see Note 5)
Comment
Federal
OSHA PEL
(50 ppm CO)
NIOSH
REL (35
ppm CO)
Minnesota
OSHA PEL
(35 ppm
CO)
ACGIH TLV (25
ppm CO)
Machines without catalytic
converter; Moderate air
mixing
3.65
0.304
1.5
326
465
465
651
See Notes
4 & 5
Machines with catalytic
converter; Moderate air
mixing
3.65
0.216
1.5
232
331
331
463
See Notes
4 & 5
Machines without catalytic
converter; Poor air mixing
3.65
0.304
3.0
651
930
930
1302
See Notes
4 & 5
Machines with catalytic
converter; Poor air mixing
3.65
0.216
3.0
463
662
662
926
See Notes
4 & 5
Notes:
1 Abbreviations:
“CO” means carbon monoxide
“CO2” means carbon dioxide
“CFM” means cubic feet per minute
“PEL” means Permissible Exposure Limit. (The total exposure limit you can breathe during an eight hour period.) The PELs and TLVs shown are time-weighted average
concentrations.
“NIOSH REL” means National Institute for Occupation Safety and Health Recommended Exposure Limit.
“ACGIH TLV” means American Conference of Governmental Industrial Hygienists Threshold Limit Value. Note that some countries and provinces, such as The Ontario Ministry
of Labour reference the ACGIH TLV for CO as their occupational exposure limit.
2
These calculated ratios are based on the tailpipe emissions (see text). The ratio has been multiplied by 3 to account for the three carbons in each molecule of propane.
3
The air mixing factor, K, varies from 1 to 3, depending on the ef
fi
ciency of air mixing.
4
It is prudent to set the K factor at 3 for rooms with poor air mixing or where the equipment is used in one area for longer than usual, such as during stripping.
5
The dilution air recommendations are minimum outside air guidelines. Real-time personnel exposure monitoring should be performed using direct sensing CO monitors with
alarms in order to ensure that the
fl
oor burnisher is adequately tuned and that suf
fi
cient dilution ventilation is being provided in all of the areas in which the burnisher will be used.
It would be advisable to consult an experienced occupational health & safety adviser, such as an industrial hygienist for special situations.
The dilution ventilation equation is:
Where:
Q
OA
= Volumetric
fl
ow rate for outside dilution air, in CFM
q = Generation rate for contaminant (CO), in CFM
OEL = Occupational Exposure Limit (see Table for PEL, TLV, etcetera)
K
eff
= A mixing factor to account for incomplete or poor delivery of dilution air (OA) to occupants. For example, a K
eff
value of 3.0 is consistent with a point source of contaminants
operated in crowded spaces with tight partitions, walls or barriers and poor air supply and return locations (AIHA, 2003). A K
eff
of 1.0 indicates ideal ventilation mixing ef
fi
ciency.
References
AIHA (2003) “General Methods for the Control of Airborne Hazards,” The Occupational Environment – Its Evaluation and Control, Second Edition, American Industrial Hygiene
Association, Fairfax, VA, pp. 829-846.
6
In some cases, it may be necessary to measure carbon dioxide (CO2) concentrations, especially if the background CO2 concentration already present in the room is expected to
be elevated prior to use of the burnisher.
7
See table below for model identi
fi
cation with and without Catalytic Convertor option:
Model 21KBCATCLDC
27KBCATCLDC
Part Number
56381408
56381409
Catalytic Converter
Yes
Yes
revised 3/11
Summary of Contents for 56381408 (21KBCATCLDC)
Page 44: ...Propane Floor Burnisher Equipment Parts Manual...
Page 45: ...FORM NO 56091023 PBU BURNISHER WITH DUST CONTROL 10 10 P 2 BASE SYSTEM...
Page 47: ...FORM NO 56091023 PBU BURNISHER WITH DUST CONTROL 10 10 P 4 BURNISH SYSTEM 21...
Page 49: ...FORM NO 56091023 PBU BURNISHER WITH DUST CONTROL 10 10 P 6 BURNISH SYSTEM 27...
Page 51: ...FORM NO 56091023 PBU BURNISHER WITH DUST CONTROL 10 10 P 8 DECAL SYSTEM...
Page 53: ...FORM NO 56091023 PBU BURNISHER WITH DUST CONTROL 10 10 P 10 ELECTRICAL SYSTEM...
Page 55: ...FORM NO 56091023 PBU BURNISHER WITH DUST CONTROL 10 10 P 12 ENGINE SYSTEM...
Page 61: ......
Page 64: ...Nilfisk Advance Inc Plymouth MN 55447 3408 2011...