Page 14
WS1TC & WS1.25 TC Manual
OEM General Instructions
The control valve offers multiple procedures that allow the valve to be modifi ed to suit the needs of the installation. These
procedures are:
•
OEM System Setup
•
Installer Displays & Settings (either 1-99 Days Between Regeneration option or 7-Day option)
•
User Displays
These procedures can be accessed in any order. Details on each of the procedures are provided below and on the following pages.
When in operation, normal user displays show the time of day or days remaining before regeneration. When stepping through a
procedure, if no buttons are pressed within fi ve minutes the display returns to a normal user display. Any changes made prior to the
fi ve minute time out are incorporated.
To quickly exit Installer Displays & Settings or OEM Setup, simultaneously press SET HOUR + DOWN. Any changes made prior
to the exit are incorporated.
To reinitialize the control valve, check to make sure the valve is in the User Display. Then simultaneously press SET HOUR +
DOWN or unplug power source plug (black wire) on the circuit board, and plug back in.
STEP 1SS
➟
OEM System Setup
STEP 1SS
– From normal mode, press SET HOUR + UP buttons simultaneously for 3 seconds
and release. Then press SET HOUR + UP buttons simultaneously for 3 seconds and release.
STEP 2SS
– Choose the desired program by pressing the UP or DOWN buttons. Prior to
selecting a program, verify the correct valve body, main piston, regenerant piston, and stack are
being used, and that the injector or injector plug(s) are in the correct locations. See Compliance
Table in Service Instructions under Injector Cap, Screen, Injector Plug and Injector section and
Figure 6. Press SET HOUR button to go to Step 3SS.
STEP 3SS
– If program P0 through P6 was selected, enter in the minutes of fi ll using the UP or
DOWN buttons. The allowable values vary from a low of 1 to a high of 99. If program P7, P8
or P9 was selected, dashes will appear for minutes of fi ll. Press SET HOUR button to go to Step
4SS. Note: For each minute of fi ll 0.5 gallons of water is added to the solution tank. With salt
(sodium chloride) this equates to approximately 1
1
/
2
pounds of salt per minute of fi ll.
STEP 2SS
➟
STEP 3SS
➟
➟
Regeneration Cycles and Times for Different Programs
Program
All times in Minutes
C1
1st Backwash
C2
Regenerate
C3
2nd Backwash
C4
Rinse
C5
Fill
P0
3
50
3
3
1-99
P1
8
50
8
4
1-99
P2
8
70
10
6
1-99
P3
12
70
12
8
1-99
P4
10
50
Skipped
8
1-99
P5
4
50
Skipped
4
1-99
P6
12
6
Skipped
12
1-99
P7
6
Skipped
Skipped
4
Skipped
P8
10
Skipped
Skipped
6
Skipped
P9
14
Skipped
Skipped
8
Skipped
Summary of Contents for Water Specialist WS1TC
Page 13: ...WS1TC WS1 25 TC Manual Page 13 Figure 3 Figure 4 Figure 1 Figure 2...
Page 21: ...WS1TC WS1 25 TC Manual Page 21 Drawings and Part Numbers...
Page 33: ...WS1TC WS1 25 TC Manual Page 33 Flow Diagrams Service and Backwash...
Page 34: ...Page 34 WS1TC WS1 25 TC Manual Flow Diagrams Down ow Brine and Rinse...
Page 35: ...WS1TC WS1 25 TC Manual Page 35 Flow Diagrams Fill...
Page 44: ...Page 44 WS1TC WS1 25 TC Manual...
Page 45: ...WS1TC WS1 25 TC Manual Page 45...
Page 46: ...Page 46 WS1TC WS1 25 TC Manual...
Page 47: ...WS1TC WS1 25 TC Manual Page 47...