SYSTEM SETUP 1
SYSTEM SETUP 2
SYSTEM SETUP 3
SYSTEM SETUP 4
SYSTEM SETUP 5
Page 14
WS2H Control Valve Manual
System Setup Screens
continued on Page 15
Returns to normal operation after 5 minutes
SYSTEM SETUP 1
Select country.
US or SI.
This sets the use of a 12 or 24 hour clock
and the display of gallons or liters.
SYSTEM SETUP 2
Select the total number of units, from 1-4, in a
system. This screen will only allow 1 or 2 if a
system board is not installed.
SYSTEM SETUP 3
Select unit fl ow rate unit add point.
1. If set to 0, all units are online unless one is regenerating.
2. If greater than 0, the system acts as a stage by fl ow adding units as fl ow
capacity increases.
3. If set to ALT the system acts as an alternator
system, keeping one unit off line at all times.
The screen will not display if set to 1 unit.
SYSTEM SETUP 4
Single units have a selection of hard water bypass, no hard water bypass or relay operation.
When the units starts a regen, HbP will allow hard water bypass, noHbp and RELAY
will not allow hard water bypass. Systems will allow setting noHbP or RELAY & 2 unit
alternators have an additional selection of ALT-A. Setting noHbP requires a motor driven
bypass, ALT-A requires a motor driven alternator valve on the controlling unit and RELAY
relys on external valving for noHbP control.
Units
Range
Increments
US
(GAL)
0-500
1
SI
(L)
0-1896
4
SYSTEM SETUP 5
Select day control type.
Time clock 1-28 day; Time clock 7 day; or OFF.
When volumetric capacity is set, volume regeneration can
be combined with time clock control. OFF will not be an
option if volumetric capacity is OFF.
Accessed by pressing NEXT and DOWN
simultaneously for >3 seconds.