INSTALLER 1
INSTALLER 2
INSTALLER 2
INSTALLER 3
INSTALLER 4
INSTALLER 5
INSTALLER 2
INSTALLER 2B
INSTALLER 2C
WS2H Control Valve Manual
Page 13
Installer Setup Screens
Accessed by pressing NEXT and
UP simultaneously for >3 seconds.
Returns to normal operation after 5 minutes.
Set current day and regen days
when set as a 7 day time clock
or hybrid in System Setup 1.
INSTALLER 1
Set volumetric capacity or OFF. OFF will not be an
option if the day control is set to OFF.
INSTALLER 2
Set day override. 1-28 days between regenerations, or if set to
7 day time clock, see 7 day setup below. OFF will display if
selected in Day Control screen.
INSTALLER 3
Select time of regen. Use up and down arrows to scroll
hours. AM/PM alternates at midnight. “on0” will be
displayed on units with no time dependent regen control.
INSTALLER 4
Select time of regen. Use up and
down arrows to scroll minutes.
INSTALLER 5
Select time of 2nd regen
(if confi gured as a multiple
regenerating unit.)
7 Day Option
INSTALLER 2
7 day time clock option.
Set current day of the week:
INSTALLER 2B
Scroll through days 1-7 using the UP and DOWN arrows.
Pressing the Set Clock will toggle regen ON or OFF for
that day. (i.e., regen on Monday.)
INSTALLER 2C
(i.e., no regeneration on Saturday.)
Installer 3
Units
Range
Increments
US
(GAL)
10-10,000
10,000-100.00 x 1000
100.00-999.00 x 1000
10
100
1000
SI
(L)
38-38,000
38,000-380.00 x 1000
380.00-3796.2 x 1000
38
38
3800
X1000 Indicator Illuminates At 10,000 Gallons
(“1” only shows if set for multiple regens.)
Return To
Normal Operation.
1 = Sunday
2 = Monday
3 = Tuesday
4 = Wednesday
5 = Thursday
6 = Friday
7 = Saturday