S e n d d o c u m e n t c o m m e n t s t o n e x u s 7 k - d o c f e e d b a c k @ c i s c o . c o m
A-20
Cisco Nexus 7000 Series Hardware Installation and Reference Guide
OL-23069-06
Appendix A Technical Specifications
Chassis Airflow
64 to 71ºF (18 to 22ºC)
1459
89
1548
73 to 80ºF (23 to 27ºC)
1459
95
1554
82 to 89ºF (28 to 32ºC)
1459
124
1583
91 to 98ºF (33 to 37ºC)
1583
153
1736
100 to 107ºF (38 to 42ºC) 1713
180
1893
109 to 116ºF (43 to 47ºC) 2158
195
2353
118 to 125ºF (48 to 52ºC) 2461
207
2668
127 to 136ºF (53 to 58ºC) 2770
207
2977
> 136ºF (58ºC)
2770
207
2977
Table A-17
Airflow for a Fully Configured Cisco Nexus 7018 Switch (continued)
Temperature
System Airflow
(cfm)
Fabric Airflow
(cfm)
Total Airflow
(cfm)