Before you begin this task, ensure that you have read and understood the safety warnings in the Safety with
Electricity section of the Safety Warnings handout topic.

Replace Fan Modules and Fan Trays, on page 87

Replace Power Supply, on page 89

Replace a Route Processor Card, on page 93

Installing and Removing Modular Port Adapters, on page 95

Replace Fan Modules and Fan Trays

If you cannot replace a fan module or fan tray within three minutes, we recommend that you leave it in the
chassis until you are prepared to replace it within that specified time limit.

Caution

If you remove more than one fan module or fan tray at a time during operations, the router allows up to 2
minutes of operations before shutting down, unless you replace extra missing fan modules or fan trays within
that time. If the router senses an over temperature condition when multiple fan modules or fan trays are
removed, the shutdown can occur in less than 2 minutes.

Note

Step 1

For NCS-57B1 routers, do the following:

a) Press both the latches on the fan module to disengage the fan module connection from the chassis.
b) Simultaneously press the latches, and pull the fan module fully out of the chassis.

Hardware Installation Guide for Cisco NCS 5700 Series Fixed-Port Routers

87

Summary of Contents for NCS 5700 Series

Page 1: ... 5700 Series Fixed Port Routers First Published 2021 06 23 Last Modified 2021 08 19 Americas Headquarters Cisco Systems Inc 170 West Tasman Drive San Jose CA 95134 1706 USA http www cisco com Tel 408 526 4000 800 553 NETS 6387 Fax 408 527 0883 ...

Page 2: ... 2021 Cisco Systems Inc All rights reserved ...

Page 3: ...moval 17 Transceiver and Cable Specifications 17 Prepare for Installation 19 C H A P T E R 2 Review Installation Roadmap 19 Review Safety Guidelines 20 Cautions and Regulatory Compliance Statements for NEBS 20 Review Installation Guidelines 21 Clearance Requirements 22 Airflow Directions 23 Procure Tools and Equipment 24 Accessory Kits for Fixed Port Routers 25 Prepare Your Location 25 Airflow for...

Page 4: ...sole Port 62 Create the Initial Router Configuration 65 Connect to the Management Ethernet Port 67 Accessing RJ 45 Cable 68 Install and Remove Transceiver Modules 70 Install and Remove SFP28 and SFP Modules 70 Bale Clasp SFP Module 72 Install a Bale Clasp SFP Module 72 Remove a Bale Clasp SFP Module 73 Install and Remove QSFP DD Transceiver Modules 75 Install and Remove QSFP QSFP28 Transceiver Mod...

Page 5: ...emoving Modular Port Adapters 95 Handling Modular Port Adapters 95 Online Insertion and Removal 96 Modular Port Adapter Installation and Removal 97 Verify Chassis Installation 99 C H A P T E R 6 Verify Device Installation 99 LEDs 101 C H A P T E R 7 Chassis LEDs 101 Route Processor Card LEDs 103 Port Status LEDs 105 Port Status LED Display 105 MPA LEDs 106 Management Port LEDs 107 Fan Module and F...

Page 6: ... 112 Time of Day Port Pinouts 112 USB Flash or MEM Port Pinouts 113 Console Port Pinouts 113 Power Supply Power Cord Specifications 114 Hardware Installation Guide for Cisco NCS 5700 Series Fixed Port Routers vi Contents ...

Page 7: ... of systems Those without external TCAM non SE rely only on the on chip resources available for feature scale The second type of system is equipped with external TCAM SE which provides an extended scale in addition to the on chip scale These systems provide functionality vital to both Top of Rack ToR and modern spine and leaf architectures NCS 57B1 The NCS 57B1 routers provide a power efficient pa...

Page 8: ...erpetual Licensing NCS 57C3 MODS SYS Flexible Consumption Model Also known as SE variant A total of 56 ports 48 ports of 25G SFP28 8 ports of 100G QSFP28 In addition the chassis has 3 Modular Port Adapter MPA slots See Modular Port Adapters on page 7 for information on MPAs NCS 57C3 MOD S Perpetual Licensing NCS 57C3 MOD SYS Flexible Consumption Model Also known as non SE variant For more informat...

Page 9: ...outer supports the NC57 B1 FAN1 FW fan module Figure 1 NCS 57B1 Fan Module The NCS 57C3 MOD router has 6 latched fan trays that install into the chassis from the rear Fan tray slots 0 and 1 support fan tray assembly with 2x60mm fans NC57 C3 FAN2 FW Fan tray slots 2 through 5 support fan tray assembly with 2x40mm fans NC57 C3 FAN1 FW Hardware Installation Guide for Cisco NCS 5700 Series Fixed Port ...

Page 10: ...Figure 2 NC57 C3 FAN2 FW Fan Tray 2x60mm Hardware Installation Guide for Cisco NCS 5700 Series Fixed Port Routers 4 NCS 5700 Router Overview Field Replaceable Units ...

Page 11: ... the entire system The router supports these PSUs PSU2KW ACPI 2000W AC power supply module with port side air intake PSU2KW DCPI 2000W 48V DC power supply module with port side air intake The router doesn t support a mix of AC and DC PSU for normal operation However router supports mix of AC and DC PSU only during migration from AC to DC or vice versa Hardware Installation Guide for Cisco NCS 5700...

Page 12: ... to DC type The PSUs provide 12V primary power to the entire system The router supports these PSUs NC57 1600W ACFW 1600W AC power supply module with port side air intake NC57 1600W DCFW 1600W 48VDC power supply module with port side air intake Figure 5 NCS 57C3 MOD AC Power Supply Unit Hardware Installation Guide for Cisco NCS 5700 Series Fixed Port Routers 6 NCS 5700 Router Overview Field Replace...

Page 13: ... Active Link LED To determine which transceivers and cables are supported by these MPAs see Cisco Transceiver Modules Compatibility Information Before replacing an MPA card remove the port range configurations that are applied on that MPA If not done interfaces in the new MPA card will not be available Note 4 Port 40GE 100GE MPA with QSFP QSFP28 The 4 port 40GE 100GE MPA NC55 MPA 4H S provides 4 p...

Page 14: ...nk LED 2 1 port 100GE 200GE with CFP2 DCO 2 Port 40GE or 100GE with QSFP QSFP28 The 1 port 100GE 200GE 2 Port 40GE 100GE combination MPA NC55 MPA 1TH2H S provides 1 port for CFP2 DCO transceivers and 2 ports for 4x25GE via cable breakout QSFP 40Gbps or QSFP28 100Gbps transceivers CFP2 DCO port and Active Link LED 3 STATUS LED 1 ATTN LED 4 QSFP port and Active Link LED 2 Hardware Installation Guide...

Page 15: ...S 55A2 MOD and NCS 57C3 MOD routers This is the first modular port adapter to support the QSFP DD optical transceiver For port configuration details see the 4 Port 800GE MPA with QSFP28 QSFP DD section in 4 Port 800GE MPA with QSFP28 QSFP DD and Hardware Installation Guide for Cisco NCS 5700 Series Fixed Port Routers Release 7 4 1 NC57 MPA 2D4H S modular port adapter The NC57 MPA 2D4H S modular po...

Page 16: ...s QSFP28 100GE All ports Ports 0 and 2 When QDD 2x100GE transceivers are installed in ports 0 and 2 ports 1 and 3 cannot be used Note QDD 2x100GE Ports 0 and 2 When QDD 400GE transceivers are installed in ports 0 and 2 ports 1 and 3 cannot be used Note Port 0 When QDD 400GE transceiver is installed in port 0 ports 1 2 and 3 cannot be used Note QDD 400GE Figure 6 NC57 MPA 2D4H S Modular Port Adapte...

Page 17: ... 57B1 5DSE SYS Figure 7 NCS 57B1 5DSE SYS Front View 12 QSFP DD ZR ports 1 12x100G QSFP DD ports Only even ports support QSFP DD 100G ZR Note 2 5x400G QSFP DD ports 3 Figure 8 NCS 57B1 6D24 SYS Front View 12 QSFP DD ZR ports 1 12x100G QSFP DD ports Only even ports support QSFP DD 100G ZR Note 2 Hardware Installation Guide for Cisco NCS 5700 Series Fixed Port Routers 11 NCS 5700 Router Overview Net...

Page 18: ... 0 and PSU 1 1 and 3 Fan Trays 2 Six Fan Trays FT0 FT1 FT2 FT3 FT4 and FT5 4 5 6 7 8 and 9 NCS 57C3 MOD The Cisco NCS 57C3 MOD Router has the following hardware features 48 ports of 25G SFP28 4 ports NCS 57C3 MOD SE S or 8 ports NCS 57C3 MOD S of 100G QSFP28 MACsec supported on the following SFP28 ports NCS 57C3 MOD S ports 0 3 40 55 NCS 57C3 MOD SE S ports 0 7 36 51 Hardware Installation Guide fo...

Page 19: ...or 8 ports NCS 57C3 MOD S of 100G QSFP28 2 The rear view of both the chassis is same Figure 11 NCS 57C3 MOD Rear View Fan tray assembly with 2x60mm fans NC57 C3 FAN2 FW 1 Hardware Installation Guide for Cisco NCS 5700 Series Fixed Port Routers 13 NCS 5700 Router Overview Network Interfaces ...

Page 20: ...isco Network Convergence System 5700 Router Data Sheet Network Timing Interfaces 1PPS input or output and ToD input or output This shielded RJ 45 interface is used for input or output of time of day ToD and 1PPS pulses ToD format includes both NTP and IEEE 1588 2008 time formats Figure 12 NCS 57B1 Network Timing Interfaces Hardware Installation Guide for Cisco NCS 5700 Series Fixed Port Routers 14...

Page 21: ...S 10Mhz input and output 10MHz input for GPS Synchronization GPS 1 PPS input and output 1 PPS input for GPS Synchronization GNSS The GNSS port is present on the front panel GNSS module has an in built ESD protection on all pins including the RF input pin However additional surge protection is required if an outdoor antenna is being connected The Lightning Protector must support a low clamping volt...

Page 22: ...open Surge requirement GNSS modules have built in ESD protections on all pins including the RF input pin However additional surge protection may be required if rooftop antennas are being connected to meet the regulations and standards for lightning protection in the countries where the end product is installed A lightning protection must be mounted at the place where the antenna cable enters the b...

Page 23: ...th power supplies installed and active the load is shared between them When a power supply is removed not working failure or the input cable is removed the remaining power supply takes the entire load without disruption There are six fan modules for the NCS 57B1 chassis and six fan trays for the NCS 57C3 MOD chassis Each module or fan tray has two fan units Transceiver and Cable Specifications To ...

Page 24: ...Hardware Installation Guide for Cisco NCS 5700 Series Fixed Port Routers 18 NCS 5700 Router Overview Transceiver and Cable Specifications ...

Page 25: ...age 24 Accessory Kits for Fixed Port Routers on page 25 Prepare Your Location on page 25 Prepare Yourself on page 27 Prepare Rack for Chassis Installation on page 29 Review Installation Roadmap This figure lists the steps to install Cisco NCS 5700 series fixed port chassis and its components and prepare the system for operation Use this workflow as a reference to ensure that all components are pro...

Page 26: ...rical inspection authority or an electrician if you are uncertain about whether suitable grounding is available To prevent personal injury or damage to the chassis never attempt to lift or tilt the chassis using the handles on modules such as power supplies fans or cards these types of handles are not designed to support the weight of the unit Hazardous voltage or energy is present on the backplan...

Page 27: ... nonconductive coatings shall be removed on the surfaces between the mounting hardware and the enclosure or rack The surfaces shall be cleaned and an antioxidant applied before installation The DC return connection to this system should remain isolated from the system frame and chassis DC I The nominal DC operating voltage 48 VDC Review Installation Guidelines Before installing the chassis verify ...

Page 28: ...s The fixed port chassis requires front to back airflow Leave at least 6 0 in 15 24 cm front and rear clearance for air intake exhaust Leave an additional 6 0 inches 15 24 cm rear clearance for removal and installation of power supplies and fan modules Figure 15 Clearance Requirement 6 0 inches 15 24 cm rear clearance for air intake exhaust 4 Chassis 1 Hardware Installation Guide for Cisco NCS 570...

Page 29: ...r altitudes Altitude derating 1 C for every 300m In case of a single fan failure the maximum allowable temperature will be less than specified In case the air filter is clogged the temperature alarm may be raised at temperatures below the listed temperatures Note Airflow Directions The airflow through the fan trays and power supplies on the Cisco NCS 5700 series router is either from the port side...

Page 30: ...foam A Torx T15 screwdriver or the Torx T15 key to install adapters Grounding cable 6 AWG recommended sized according to local and national installation requirements the required length depends on the proximity of the switch to proper grounding facilities Ground lug 1 Crimping tool large enough to accommodate the girth of the lug Wire stripping tool ANSI Pair of 19 inch mounting brackets M4 screws...

Page 31: ...ssory Kit 1 Router Rack mount kit and ground lug kit 8200 1RU KIT NCS 57B1 6D24 SYS NCS 57B1 5DSE SYS Rack mount kit and ground lug kit NC57 3RU ACC KIT NCS 57C3 MOD SE S NCS 57C3 MOD S Prepare Your Location This section illustrates how the building that houses the chassis must be properly grounded to the earth ground This image is only for representational purposes Your grounding requirement depe...

Page 32: ...ite Planning Table 5 Cisco NCS 5700 Airflow Maximum System Airflow CFM at Maximum System Temperature Device 150 NCS 57B1 5DSE SYS NCS 57B1 6D24 SYS Hardware Installation Guide for Cisco NCS 5700 Series Fixed Port Routers 26 Prepare for Installation Airflow for Site Planning ...

Page 33: ...ore removing the chassis from the sealed antistatic bag The figures show how to cuff the ESD strap around the wrist and the ground cord that connects the cuff to the ground ESD wrist straps are the primary means of controlling static charge on personnel Hardware Installation Guide for Cisco NCS 5700 Series Fixed Port Routers 27 Prepare for Installation Prepare Yourself ...

Page 34: ...Figure 18 Wearing the ESD Strap Hardware Installation Guide for Cisco NCS 5700 Series Fixed Port Routers 28 Prepare for Installation Prepare Yourself ...

Page 35: ... between the posts of the rack must be wide enough to accommodate the width of the chassis Before you move the chassis or mount the chassis into the rack we recommend that you do the following Step 1 Place the rack where you plan to install the chassis Ensure that the rack that the chassis is being installed is grounded to earth ground as instructed in Prepare Your Location on page 25 Hardware Ins...

Page 36: ...he rack to the floor consult a company that specializes in floor mounting kits such as Hilti see Hilti com for details Make sure that floor mounting bolts are accessible especially if annual retorquing of bolts is required Hardware Installation Guide for Cisco NCS 5700 Series Fixed Port Routers 30 Prepare for Installation Prepare Rack for Chassis Installation ...

Page 37: ...s chapter are only for representation purposes unless specified otherwise The chassis actual appearance and size may vary Note Rack Types on page 31 Rack Mount the Chassis on page 33 Ground the Chassis on page 53 Connect AC Power to the Chassis on page 55 Connect DC Power to the Chassis on page 57 Power Supply Unit Input and Output Ranges on page 59 Rack Types Figure 20 Rack specification EIA 19 i...

Page 38: ...s the rack mounting brackets for 19 inch rack To install the chassis in a 23 inch rack or an ETSI rack you need adapter plates to accommodate the 19 inch rack mount brackets The adapter plates for installing in a 23 inch rack or an ETSI rack are included in the accessory kit for the NCS 57C3 MOD chassis Note Figure 21 Four Post Rack Type Hardware Installation Guide for Cisco NCS 5700 Series Fixed ...

Page 39: ...e for mounting the NCS 57C3 MOD S and NCS 57C3 MOD SE S chassis in a 2 post rack Rack Mount the NCS 57B1 Chassis in a 4 Post Rack on page 38 Contains the procedure for mounting the NCS 57B1 6D24 SYS and NCS 57B1 5DSE SYS chassis in a 4 post rack Rack Mount the NCS 57C3 MOD Chassis in a 4 Post Rack using Sliders on page 41 Contains the procedure for mounting the NCS 57C3 MOD S and NCS 57C3 MOD SE S...

Page 40: ...ackets 2 M4 x 6 mm Phillips counter sink screws 8 Step 1 Install two rack mount brackets to the router as follows a Position the router so that its ports will be in the cold aisle b With the bracket ears aligned to the front of the chassis position a rack mount bracket on the side of the chassis so that the four holes are aligned to four of the screw holes on the side of the chassis c Use four M4 ...

Page 41: ...o rack posts c Hold the chassis level while the second person inserts two screws 12 24 or 10 32 depending on the rack type in each of the two rack mount brackets using a total of four screws and into the cage nuts or threaded holes in the vertical rack mounting rails d Tighten the 10 32 screws to 20 in lb 2 26 N m or tighten the 12 24 screws to 30 in lb 3 39 N m Hardware Installation Guide for Cis...

Page 42: ... rack is on wheels ensure that the brakes are engaged or that the rack is otherwise stabilized Caution The following table lists the items contained in the rack mount kit provided with the routers Table 8 Router Rack Mount Kit Part Description Quantity Rack mount brackets 2 M4 x 6 mm Phillips counter sink screws 14 Hardware Installation Guide for Cisco NCS 5700 Series Fixed Port Routers 36 Install...

Page 43: ...unter sink screws 2 Rack mount brackets 1 Step 2 Install the router onto the 2 post rack as follows a With two people lift the router into position between the two rack posts b Move the router until the rack mount brackets come in contact with two rack posts c Hold the chassis level while the second person inserts six screws 12 24 or 10 32 depending on the rack type in each of the two rack mount b...

Page 44: ...tabilized Caution The following table lists the items that are contained in the rack mount kit Table 9 NCS 57B1 6D24 SYS and NCS 57B1 5DSE SYS Router Rack Mount Kit Part Description Quantity Rack mount brackets 2 M4 x 6 mm Phillips flat head screws 18 M4 x 6 mm Phillips pan head screws 2 Rack mount guides 2 Rack mount slider rails 2 Grounding lug 1 Hardware Installation Guide for Cisco NCS 5700 Se...

Page 45: ... that are aligned to four of the screw holes on the side of the chassis and then use four M4 counter sink screws to attach the bracket to the chassis Remove the grounding cover label and align the grounding cover plate with the grounding holes in the chassis and attach the rack mount brackets Note You can align four of the holes in the rack mount bracket to four of the screw holes on the front sid...

Page 46: ...24 screw Note b Repeat with the other slider rail on the other side of the rack c Use a tape measure and level to verify that the rails are at the same height and horizontal Step 4 Insert the router into the rack and attach it as follows a Holding the router with both hands position the back of the router between the front posts of the rack b Align the two rack mount guides on either side of the r...

Page 47: ...36 Note NC55 2RU ACC SL1 Designed for custom made cabinets that are 476 mm wide min 650 x650 mm or for cabinets with equivalent specifications This slider is attached directly to the chassis Rack Requirements to Install NC55 2RU ACC SL1 4 post rack 476 cm wide center to center rail mounting The width between the front rack mounting rails must be at least 17 75 inches 45 0 cm The minimum spacing fo...

Page 48: ... cabinet to the inner surface of the front door shall be min 5 8 inches 14 7 cm Depending on the cabinet ambient thermal set point this minimum distance can change The minimum spacing for the bend radius for fiber optic cables should have the front mounting rails of the cabinet offset from the front door by a minimum of 4 7 inches 12 0 cm The distance between the outside face of the front mounting...

Page 49: ...mount slider rails 2 M4 x 8 mm Phillips counter sink screws 8 M4 x 8 mm Phillips pan head screws 2 Grounding lug 1 Only NC55 2RU ACC SL1 M4 x 10 mm Phillips pan head screws 6 Only NC55 2RU ACC SL2 M4 x 8 mm Phillips flat head screws 6 Only NC55 2RU ACC SL2 washers 4 Only NC55 2RU ACC SL2 10 32 counter sink screws 4 Only NC55 2RU ACC SL2 9 1 mm rack mount pins 4 Hardware Installation Guide for Cisc...

Page 50: ...Tab 1 Step 2 Push the unlock feature of the middle slider member and slide the middle slider member back to the slider assembly Step 3 For NC55 2RU ACC SL1 attach the inner slider member to the sides of the chassis a Align the inner slider member with one side of the chassis and use three M4 x 10 mm pan head screws and tighten the screws to 12 in lbs 1 4 N m b Repeat this step to install the inner...

Page 51: ... member with one side of the tray and use seven M4 x 8 mm flat head screws and tighten the screws to 12 in lbs 1 4 N m b Repeat this step to install the inner slider member to the other side of the tray Figure 32 Install the Inner Slider Member to the Tray Hardware Installation Guide for Cisco NCS 5700 Series Fixed Port Routers 45 Install the Chassis Rack Mount the NCS 57C3 MOD Chassis in a 4 Post...

Page 52: ...pins that are provided in the package Note b NC55 2RU ACC SL1 The front end of the outer slider member passes through the screw holes of the rack and latches to the rack See Figure 33 Rear and Front End NC55 2RU ACC SL1 of the Outer Slider Member Figure 33 Rear and Front End NC55 2RU ACC SL1 of the Outer Slider Member Hardware Installation Guide for Cisco NCS 5700 Series Fixed Port Routers 46 Inst...

Page 53: ...r Slider Member Remove the screw thread adapter present at the front end of the outer slider member if you are unable to pass the slider through the rack holes Tighten the screws later after passing the slider through the rack holes Note Figure 34 Rear and Front End NC55 2RU ACC SL2 of the Outer Slider Member Counter sink screws 2 Screw thread adapter at the Front End Outer slider member 1 Hardwar...

Page 54: ...der member to the other side of the chassis Figure 35 Install the Outer Slider Member to the Rack Outer slider member 1 Step 5 Extend the middle slider member from the slider assembly Hardware Installation Guide for Cisco NCS 5700 Series Fixed Port Routers 48 Install the Chassis Rack Mount the NCS 57C3 MOD Chassis in a 4 Post Rack using Sliders ...

Page 55: ... the chassis or tray to the middle slider member on the rack Step 7 Slide the chassis or tray into middle slider member until it cannot be pushed further Hardware Installation Guide for Cisco NCS 5700 Series Fixed Port Routers 49 Install the Chassis Rack Mount the NCS 57C3 MOD Chassis in a 4 Post Rack using Sliders ...

Page 56: ...nner slider member 3 Step 8 For NC55 2RU ACC SL2 with the tray do the following a Place the chassis on the tray and align the chassis with the screw holes on the tray Hardware Installation Guide for Cisco NCS 5700 Series Fixed Port Routers 50 Install the Chassis Rack Mount the NCS 57C3 MOD Chassis in a 4 Post Rack using Sliders ...

Page 57: ...sides simultaneously to release the lock position Continue to push the chassis to the rack Step 10 Tighten the thumbscrews on either side of the chassis that is aligned with the screw thread adapter of the outer slider member through the rack holes Hardware Installation Guide for Cisco NCS 5700 Series Fixed Port Routers 51 Install the Chassis Rack Mount the NCS 57C3 MOD Chassis in a 4 Post Rack us...

Page 58: ... Chassis to the Rack Figure 41 Secure the Tray to the Rack Hardware Installation Guide for Cisco NCS 5700 Series Fixed Port Routers 52 Install the Chassis Rack Mount the NCS 57C3 MOD Chassis in a 4 Post Rack using Sliders ...

Page 59: ...r conductor wires must be used and the copper conductor must comply with NEC code for ampacity Caution When terminating the frame ground do not use soldering lug connectors screwless push in connectors quick connect connectors or other friction fit connectors Caution Step 1 Use a wire stripping tool to remove approximately 0 75 inches 19 mm of the covering from the end of the 6 AWG grounding cable...

Page 60: ...24 SYS and NCS 57B1 5DSE SYS Ground Lug Figure 43 NCS 57C3 MOD Ground Lug Pan head screws 2 Grounding lug 1 Hardware Installation Guide for Cisco NCS 5700 Series Fixed Port Routers 54 Install the Chassis Ground the Chassis ...

Page 61: ...th maximum output power of 1000 W To provide full output power of 2000 W the nominal voltage rating value ranges between 200Vac to 240Vac depending on the standards in various countries Note The following combinations of power supplies are supported on NCS 57B1 6D24 SYS and NCS 57B1 5DSE SYS PSU2KW ACPI PSU2KW ACPI port side intake airflow In low line applications 90 140V AC redundancy is not guar...

Page 62: ...e cable clamp toward the plug Step 5 Close the cable clamp on the shoulder of the power cable to secure the power cable Figure 44 Cable Clamp Examples Hardware Installation Guide for Cisco NCS 5700 Series Fixed Port Routers 56 Install the Chassis Connect AC Power to the Chassis ...

Page 63: ...ment 1074 Installation of the equipment must comply with local and national electrical codes Warning Before installing a DC power supply to the switch you will need to attach DC connection wires that you provide to the DC power connector included in the DC power supply s accessory kit For 240 380 VDC power supply the dual pole breaker or fuse rating is 20 A For 40 72 VDC power supply the single br...

Page 64: ...rify that the correct fuse panel is installed in the top mounting space Step 2 Ensure that the DC circuit is powered down either breaker turned off or fuse pulled and proper lockout tag out procedures are followed Use the cable supplied with the power supply If you prefer to use your own cable the cable size must be 6 AWG Figure 46 NCS 57B1 Connecting DC Power Hardware Installation Guide for Cisco...

Page 65: ...57 1600W DCFW power supply module with the power source you must procure the CAB 48DC 40A 8AWG power cord Note Step 6 Ensure that the locking mechanism has engaged to secure the cable Step 7 Turn on the circuit breaker at the power source Power Supply Unit Input and Output Ranges This table summarises input and output power ranges for PSU low line and nominal applications Table 11 Input and output...

Page 66: ...12V 167A 2000W 12A 200 240V ac PSU2KW ACPI For nominal voltage application 12V 167A 2000W 40A 40V to 72V DC PSU2KW DCPI Hardware Installation Guide for Cisco NCS 5700 Series Fixed Port Routers 60 Install the Chassis Power Supply Unit Input and Output Ranges ...

Page 67: ...s and life of your transceivers and optical cables do the following Wear an ESD preventative wrist strap that is connected to an earth ground whenever handling transceivers The router is typically grounded during installation and provides an ESD port to which you can connect your wrist strap Do not remove and insert a transceiver more often than is necessary Repeated removals and insertions can sh...

Page 68: ...outer to the network you must create a local management connection through a console terminal and configure an IP address for the router You also can use the console to perform the following functions each of which can be performed through the management interface after you make that connection Configure the router using the command line interface CLI Monitor network statistics and errors Configur...

Page 69: ...and Management Port Location Console port 2 Time of Day ToD port 1 Management Ethernet port 4 USB 3 Hardware Installation Guide for Cisco NCS 5700 Series Fixed Port Routers 63 Connect Router to the Network Connect to the Console Port ...

Page 70: ...be available An RJ 45 rollover cable and DB9F RJ 45 adapter Network cabling should already be routed to the location of the installed router Step 1 Set your terminal to these operational values 115200 bps 8 data bits no parity 1 stop bits 115200 8N1 Step 2 Attach the terminal end of the cable to the interface port on the data terminal Step 3 Attach the other end of the cable to the console port Ta...

Page 71: ... Connect a power source to the router Determine the IP address and netmask needed for the Management interfaces MgmtEth0 RP0 CPU0 0 and MgmtEth0 RP1 CPU0 0 Step 1 Power up the router The LEDs on each power supply light up green when the power supply units are sending power to the router The Administrative User Dialog prompt appears Step 2 When the system is booted up for the first time you must en...

Page 72: ...oes not contain proper names Contains both uppercase and lowercase characters Contains numbers as well as letters Clear text passwords cannot include the dollar sign special character Note If a password is trivial such as a short easy to decipher password the software rejects the password configuration Be sure to configure a strong password as explained in this step Passwords are case sensitive Ti...

Page 73: ...dress conflict do not connect the management Ethernet port until the initial configuration is complete Note To connect cables to the system management port attach Category 5 cables directly to the RJ 45 receptacle on the management Ethernet port Figure 50 NCS 57B1 Management and Console Port Locations Console port 2 Management Ethernet port 4 Hardware Installation Guide for Cisco NCS 5700 Series F...

Page 74: ...ded at both ends Note Before you begin You must have completed the initial router configuration Step 1 Plug the cable directly into the RJ 45 receptacle Step 2 Connect the network end of your RJ 45 cable to a switch hub repeater or other external equipment Accessing RJ 45 Cable The RJ 45 cable is available on the Management port To access the RJ 45 cable perform the following steps Hardware Instal...

Page 75: ...he management port Note 1 Insert the Philips flat head screwdriver in between the timing ports Figure 52 Inserting a screwdriver between the timing ports 2 Press the clip on the RJ 45 jack downwards and pull the RJ 45 jack from the port This releases the RJ 45 cable from the port Hardware Installation Guide for Cisco NCS 5700 Series Fixed Port Routers 69 Connect Router to the Network Accessing RJ ...

Page 76: ...erefore you need QSA module QSFP to SFP Adapter CVR QSFP SFP10G to support SFP module Note The Cisco NCS 57C3 MOD router has three rows of SFP28 ports In the top row install SFP28 transceivers with the electrical connectors on the bottom In the two bottom rows install SFP28 transceivers with the electrical connectors on the top Note Hardware Installation Guide for Cisco NCS 5700 Series Fixed Port ...

Page 77: ...se 7 3 15 SFP modules can t be used Note Invisible laser radiation may be emitted from disconnected fibers or connectors Do not stare into beams or view directly with optical instruments Statement 1051 Warning Protect the line card by inserting a clean SFP module cage cover shown in the figure below into the optical module cage when there is no SFP module installed Caution Figure 55 SFP Module Cag...

Page 78: ...ptacle Verify that the modules are completely seated and secured in their assigned receptacles on the line card by firmly pushing on each SFP module Note Bale Clasp SFP Module The bale clasp SFP module has a clasp that you use to remove or install the module see the figure below Figure 56 Bale Clasp SFP Module Install a Bale Clasp SFP Module To install this type of SFP module follow these steps St...

Page 79: ...shown in the figure below If the bale clasp is obstructed and you cannot use your index finger to open it use a small flat blade screwdriver or other long narrow instrument to open the bale clasp Step 4 Grasp the SFP module between your thumb and index finger and carefully remove it from the port as shown in the figure below This action must be performed during your first instance After all the po...

Page 80: ...ic shielding bag if you plan to return it to the factory Step 6 Protect your line card by inserting a clean SFP module cage covers into the optical module cage when there is no SFP module installed Hardware Installation Guide for Cisco NCS 5700 Series Fixed Port Routers 74 Connect Router to the Network Remove a Bale Clasp SFP Module ...

Page 81: ...SFP DD optical transceiver and 100 Gigabit QSFP28 optical transceiver are similar to the 40 Gigabit QSFP optical transceiver Figure 58 400 Gigabit QSFP DD Transceiver Module Front view Figure 59 400 Gigabit QSFP DD Transceiver Module Rear view Pull tab latch 1 The QSFP DD transceiver module is a static sensitive device Always use an ESD wrist strap or similar individual grounding device when handl...

Page 82: ...transceiver module body to verify that you have the correct model for your network Do not remove the dust plug until you re ready to attach the network interface cable Note Step 4 Hold the QSFP DD transceiver module by the pull tab Step 5 Align the QSFP DD transceiver module in front of the module s transceiver socket opening and carefully slide the transceiver into the socket until the transceive...

Page 83: ...0GBASE QSFP transceiver body 1 Bail clasp latch 2 Overview The 40 Gigabit GE QSFP and 100 Gigabit QSFP28 transceiver module is a hot swappable parallel fiber optical module with 4 independent optical transmit and receive channels These channels can terminate in another 40 Gigabit QSFP transceiver or the channels can be broken out to 4 separate 10 Gigabit SFP transceivers The QSFP transceiver modul...

Page 84: ...ver module follow these steps Step 1 Attach an ESD wrist strap to yourself and a properly grounded point on the chassis or the rack Step 2 Remove the QSFP or QSFP28 transceiver module from its protective packaging Step 3 Check the label on the QSFP or QSFP28 transceiver module body to verify that you have the correct model for your network Step 4 For optical QSFP or QSFP28 transceiver modules remo...

Page 85: ...sceiver module with your thumb to fully seat the transceiver in the module s transceiver socket see the below figure If the latch is not fully engaged you might accidentally disconnect the QSFP or QSFP28 transceiver module Caution Hardware Installation Guide for Cisco NCS 5700 Series Fixed Port Routers 79 Connect Router to the Network Installing the 40 Gigabit QSFP or 100 Gigabit Transceiver Modul...

Page 86: ...begin Before you remove the dust plugs and make any optical connections follow these guidelines Keep the protective dust plugs installed in the unplugged fiber optic cable connectors and in the transceiver optical bores until you are ready to make a connection Inspect and clean the MPO connector end faces just before you make any connections Grasp the MPO connector only by the housing to plug or u...

Page 87: ...static sensitive device Always use an ESD wrist strap or similar individual grounding device when handling QSFP or QSFP28 transceiver modules or coming into contact with modules Caution To remove a QSFP or QSFP28 transceiver module follow these steps Step 1 For optical QSFP or QSFP28 transceiver modules disconnect the network interface cable from the QSFP or QSFP28 transceiver connector Step 2 For...

Page 88: ... port you must install SFP transceivers for 1 Gigabit optical ports or install SFP transceivers for 10 Gigabit optical ports or QSFP transceivers for 100 Gigabit ports before installing the fiber optic cable in the transceivers Removing and installing a transceiver can shorten its useful life Do not remove and insert transceivers any more than is absolutely necessary We recommended that you discon...

Page 89: ... Connect the other end of the shielded coaxial cable to the GNSS antenna after the primary protector The GNSS RF In port should have a primary protector installed to meet the Local Safety guidelines Note Figure 67 NCS 57B1 GNSS Port Hardware Installation Guide for Cisco NCS 5700 Series Fixed Port Routers 83 Connect Router to the Network Connecting a Cable to the GNSS Antenna Interface ...

Page 90: ...ax 50 Ohm connectors provided in the front panel to output this 1PPS and 10MHz The table below summarizes the GPS port pinouts Table 13 GPS Port Pinouts 1PPS Input and Output 10 MHz Input and Output Input Rectangular pulse Output Rectangular pulse Input Sine wave Output Square wave Waveform Input 2 4 volts TTL compatible Output 2 4 volts TTL compatible Input 1 7 volt p p 8 to 10 dBm Output 2 4 vol...

Page 91: ...s can shorten its useful life Keep all optical connections covered when not in use Clean them before use to prevent dust from scratching the fiber optic cable ends Do not touch the ends of connectors Touching the ends would leave fingerprints and cause other contamination Clean the connectors regularly the required frequency of cleaning depends upon the environment In addition clean connectors if ...

Page 92: ...Hardware Installation Guide for Cisco NCS 5700 Series Fixed Port Routers 86 Connect Router to the Network Maintain Transceivers and Optical Cables ...

Page 93: ...e prepared to replace it within that specified time limit Caution If you remove more than one fan module or fan tray at a time during operations the router allows up to 2 minutes of operations before shutting down unless you replace extra missing fan modules or fan trays within that time If the router senses an over temperature condition when multiple fan modules or fan trays are removed the shutd...

Page 94: ...ight side of the fan tray to disengage the fan tray connection from the chassis b Simultaneously press the latch and pull the fan tray fully out of the chassis Figure 70 Remove Fan Tray from the NCS 57C3 MOD Chassis Hardware Installation Guide for Cisco NCS 5700 Series Fixed Port Routers 88 Replace Chassis Components Replace Fan Modules and Fan Trays ...

Page 95: ...ou should immediately hear them in operation If you do not hear them ensure that the fan module is inserted completely in the chassis Step 7 Verify that the fan module LED is green If the LED is not green one or more fans are faulty After installation we recommend that you move the fan handles to the right side so that the fan module LED is visible Note Replace Power Supply The router provides the...

Page 96: ... the DC power supply Before performing any of the following procedures ensure that power is removed from the DC circuit Statement 1003 Warning Only trained and qualified personnel should be allowed to install replace or service this equipment Statement 1030 Warning Follow these steps to remove and replace the DC power supply Step 1 Before servicing the power supply switch off the circuit breaker i...

Page 97: ...he power supply you are installing is off To ensure that power has been removed from the DC circuits locate the circuit breakers for the DC circuits switch the circuit breakers to the OFF position and tape the circuit breaker switches in the OFF position Step 4 Grasp the power supply handle with one hand Place your other hand underneath the power supply Step 5 Slide the power supply into the power...

Page 98: ...Simultaneously press the power supply lock towards the left and pull the power supply out from the chassis while supporting it with the other hand Install the AC Power Supply Module Follow these steps to install the AC power supply module Step 1 Ensure that the system earth ground connection has been made Step 2 If necessary remove the blank power supply filler plate from the chassis power supply ...

Page 99: ... only one RP card installed a new RP can be installed in the empty RP slot during operation Statement 1029 Blank Faceplates and Cover Panels Blank faceplates and cover panels serve three important functions they prevent exposure to hazardous voltages and currents inside the chassis they contain electromagnetic interference EMI that might disrupt other equipment and they direct the flow of cooling ...

Page 100: ...isconnect the following cables from the card Console cable Ethernet Management cable b If there are any external drives attached to the card through its USB ports detach those drives c Run the hw module location loc shutdown command in admin EXEC mode which gracefully shuts down RP module to prevent any of the file systems from being corrupted d Verify that the RP LED for the slot that you specifi...

Page 101: ... follows The STATUS LED blinks in amber color then turns to solid amber color and later turns to green color The Active ACT LED is amber or green Installing and Removing Modular Port Adapters The following sections describe how to install or remove an MPA on the NSC 57C3 MOD router Handling Modular Port Adapters Each modular port adapter MPA circuit board is mounted to a metal carrier and is sensi...

Page 102: ...ion and removal of Modular port adapters MPAs is comprised of the following steps Shut down the MPA with the hw module subslot rack slot subslot shutdown command Confirm that the LEDs have gone from green to off Execute the do show platform command to verify that the MPA to be removed is in the disabled state Physically remove the MPA to be replaced Physically insert the replacement MPA Return the...

Page 103: ...fully slide the MPA all the way in the chassis until the MPA is firmly seated in the MPA interface connector When fully seated the MPA might be slightly behind the faceplate The MPA will slide easily into the slot if it is properly aligned on the tracks If the MPA does not slide easily do NOT force it Remove the MPA and reposition it paying close attention to engaging it on the tracks Push the MPA...

Page 104: ...Ensure that you first loosen the right screw and then the left 5 Grasp the MPA and pull the MPA from the chassis You have already disconnected the cables from the MPA Hardware Installation Guide for Cisco NCS 5700 Series Fixed Port Routers 98 Replace Chassis Components Modular Port Adapter Installation and Removal ...

Page 105: ...ersion Displays all environment related router information admin show environment Displays temperature readings for card temperature sensors Each system controller route processor line show environment temperature card and fabric card has temperature sensors with two thresholds Minor temperature threshold when a minor threshold is exceeded a minor alarm occurs and the following actions occur for a...

Page 106: ...crease the temperature During this interval the software monitors the temperature every 5 seconds and continuously sends system messages as configured We recommend that you install dual route processor cards If you are using a router without dual route processor cards we recommend that you immediately replace the fan card even if just one fan is not working Note Powers up or shuts down a card hw m...

Page 107: ... Module and Fan Tray LED on page 108 Power Supply LED on page 109 Chassis LEDs On the NCS 57B1 chassis the STATUS ALARM SYNC and FAN LEDs are located at the far left of the front panel Power and GNSS LEDs are located at the far right of the front panel just below the USB port Figure 77 NCS 57B1 Chassis LEDs GNSS LED 2 POWER LED 1 Hardware Installation Guide for Cisco NCS 5700 Series Fixed Port Rou...

Page 108: ...MOD RP2 E route processor LEDs Figure 78 NCS 57C3 MOD Chassis LEDs Table 14 LED Descriptions Status Color LED The module is operational and has no active major or critical alarms Green STAT The module is booting up Blinking Amber Host kernel booted and is ready to start XR Amber The module is powered off Off Hardware Installation Guide for Cisco NCS 5700 Series Fixed Port Routers 102 LEDs Chassis ...

Page 109: ...o thermal or fan failure Amber Chassis power failure Power supply failure due to one of the following conditions Over voltage Over current Over Temperature Fan failure Red GNSS is not configured Off GNSS GNSS is locked to an RF input Satellites Green GNSS Receiver not locked RF input Satellites Amber Route Processor Card LEDs On the NC57 MOD RP2 E route processor card the Status STS Active ACT and...

Page 110: ...ill not power on or boot up The module is not fully inserted Red The module is not receiving power Off XR VM is operational and is in the active redundancy role on this module Green ACT Active XR VM is operational and is in the standby redundancy role on this module Amber XR VM is not operational on this module Off The operator has activated this LED to identify this module in the chassis Flashing...

Page 111: ...ormation of the optical ports Table 16 NCS 57B1 Port Status LEDs one per port Description LED Color Port is administratively shut down Off Port is administratively enabled and the link is up Green Port is administratively enabled and the link is down Amber Port Status LED Display The NCS 57C3 MOD front panel LED display shows the status of the ports DISPLAY Mode Button 2 Port Status LED Display 1 ...

Page 112: ...e MPA and the attention ATTN is located on the front right of the MPA The Link LED for each port is located either between the two rows of ports each of these LEDs is a triangle pointing to the port above or below the LED or under the port Status Color LED The operator has activated this LED to identify this MPA in the chassis Flashing blue ATTN This LED is not being used Off This MPA is operation...

Page 113: ... at the right side on the front panel of the chassis Figure 80 Management Port LEDs Port Activity 1 Port Link 2 Table 18 Management Port LEDs Description Status Color LED The ethernet link is up and operational Green Port Activity The ethernet link is down Off The port is either receiving or transmitting packets Green Blinking Port Link No packets are being received or transmitted Off Hardware Ins...

Page 114: ...t corner of the module Figure 81 NCS 57B1 Fan Module LED The NCS 57C3 MOD fan tray LED is located on the bottom left corner of the module Figure 82 NCS 57C3 MOD Fan Tray LED Hardware Installation Guide for Cisco NCS 5700 Series Fixed Port Routers 108 LEDs Fan Module and Fan Tray LED ...

Page 115: ...eiving power Off Power Supply LED The power supply LED is located on the lower right corner portion of the module Figure 83 NCS 57B1 Power Supply LED Figure 84 NCS 57C3 MOD Power Supply LED Status LED location 1 Hardware Installation Guide for Cisco NCS 5700 Series Fixed Port Routers 109 LEDs Power Supply LED ...

Page 116: ...reen Power supply failure due to one of the following conditions Over Voltage Over Current Over Temperature Fan Failure Amber Power supply is operating but a warning condition has occurred due to one of the following conditions High temperature High power Slow fan Blinking Amber Power supply units are not receiving power Off Hardware Installation Guide for Cisco NCS 5700 Series Fixed Port Routers ...

Page 117: ...ical specifications and power consumption refer to the following data sheets NCS 57B1 Fixed Chassis Data Sheet NCS 57C3 Fixed Chassis Data Sheet Environmental Specifications For information on environmental specifications see table Environmental properties in the following data sheets NCS 57B1 Fixed Chassis Data Sheet NCS 57C3 Fixed Chassis Data Sheet RJ 45 Connectors The RJ 45 connector connects ...

Page 118: ...ure 85 RJ 45 Connector Pin 2 2 Pin 1 1 Management Pinouts The following table summarizes the Management Ethernet port pinouts Table 20 Management Ethernet Port Pinouts Signal Name Pin TRP0 1 TRP0 2 TRP1 3 TRP1 4 TRP2 5 TRP2 6 TRP3 7 TRP3 8 Time of Day Port Pinouts The following table summarizes the ToD 1 PPS port pinouts Hardware Installation Guide for Cisco NCS 5700 Series Fixed Port Routers 112 ...

Page 119: ...marizes the USB flash or MEM port pinouts Table 22 USB Flash or MEM Port Pinouts Description Signal Name Pin 5 VDC Vcc A1 Data D A2 Data D A3 Ground Gnd A4 Console Port Pinouts The following table summarizes the Console port pinouts Table 23 Console Port Pinouts Description Direction Signal Name Pin Loopback 1 NA Loop1 1 Loopback 2 NA Loop2 2 Console RS232 transmit Output TxD 3 Ground NA Gnd 4 Har...

Page 120: ...ly Power Cord Specifications For more information on the supported power cables see Ordering information for power cables supported on NCS 5700 on the Cisco Network Convergence System 5700 Router Data Sheet Hardware Installation Guide for Cisco NCS 5700 Series Fixed Port Routers 114 System Specification Power Supply Power Cord Specifications ...