Troubleshooting the Cisco RPS B-9
Reading Error Messages on Cisco 2600 and 3600 Series Routers
SNMP Trap Issued Upon Correction of Error:
ciscoEnvMonRedundantSupplyNotification is generated. The varbinds
included are ciscoEnvMonSupplyStatusDescr and
ciscoEnvMonSupplyState. The value of ciscoEnvMonSupplyState will be
normal.
FAN LED is amber
FAIL
Console Error Message:
When an external device console screen displays the Cisco IOS software
prompt (routername > or routername #)
“System detected
Redundant Power Supply THERMAL FAIL condition.”
The Cisco IOS software checks the condition once every 30 seconds. If
the condition still exists, the error message redisplays.
When an external device console screen displays the ROMMON prompt
(rommon #>)
“*** System Environmental Interrupt ***
WARNING: REDUNDANT POWER SUPPLY THERMAL BIT IS
ASSERTED.”
Description of Error:
One of the Cisco RPS’s fans has failed. The remaining fans switch to full
speed to keep the Cisco RPS cool.
SNMP Trap Issued Upon Error:
ciscoEnvMonRedundantSupplyNotification is generated. The varbinds
included are ciscoEnvMonSupplyStatusDescr and
ciscoEnvMonSupplyState. The value of ciscoEnvMonSupplyState will be
a warning.
How to Correct Error:
The Cisco RPS continues to operate with a single fan failure. To correct
the failure, the Cisco RPS needs to be replaced.
Table B-2
Error Descriptions and LED Status (Continued)
RPS LED Status
Condition
Error Indicators, Descriptions, and Solutions