21
Instruction Manual
VLOG-10
Figure 15:Setup screen�
The setup parameters are:
Tensión de Red
(Mains voltage)
The facility's operating voltage.
Minimum configuration value
:
87
V.
Maximum configuration value
:
259
V.
Umbral de sobretensión
(Overvoltage threshold)
Voltage level above which an overvoltage event is generated.
Minimum configuration value
:
87
V.
Maximum configuration value
:
265
V.
Umbral de hueco de tensión
(Voltage gap threshold)
Voltage level below which a
Voltage gap
event is generated.
Minimum configuration value:
85
V.
Maximum configuration value:
The selected
Mains voltage
.
Tiempo entre logs
(Time between logs)
Here you can configure the intervals at which the device periodically measures and records the
nominal value of the mains in the memory.
Minimum configuration value:
1
second.
Maximum configuration value:
7200
seconds.
The recommended configuration value is
900
seconds.