19
Instructions Manual
GETEST
1 m
≥ 40 m
1 m
5 A
Auxiliary ground
Hardware ground
Measuring
electrodes
Access door
Figure 11: Step voltage Test connection�
The recommended distance between the hardware ground fitting and the
auxiliary ground is 5 times the diagonal of the substation enclosure or the transformation
centre.
The separation distances shown in the connection diagrams of this manual are
minimum distances, which will have to be increased depending on the sizing of the
transformation centre or substation.
4�-
Ensure the electrodes are stable.
Despite featuring a non-slip design, the electrodes can slide on the surface. Make sure
they are stable before using them.
5�-
Stand on the electrodes, stepping inside the marked surface,
.
Figure 12: Stand on the electrodes�
Always wear non-conducting safety footwear when using the electrodes.
Always stand inside the marked area.
6�-
Keep your body in a fixed position that avoids motion during the measurements.