4�6�10� MAXIMUM DEMAND VARIABLE
OnthisscreenthevariablestointegrateintotheMaximum
Demandconceptareselected�
Thedisplayshowsthedigitsthatidentifythatcodeforthe
variabletobeintegratedaccordingto
Table 11: Codes for maximum demand variables
Parameter
Code
Activethree-phasepower
16
Apparentthree-phasepower
34
Three-phasecurrent
36
CurrentL1,L2,L3
A-ph
None
00
The
keyjumpsbetweenthedifferentoptions�
Tovalidatetheinformationandgotothenextprogrammingstep,press
�
4�6�11� PERIOD OF MAXIMUM DEMAND INTEGRATION
Onthisscreenthemaximumdemandintegrationperiodis
programmed�
Toenterormodifytheintegrationperiodvalue,pressthe
key
repeatedly,increasingthevalueoftheflashingdigit�
Whentheon-screenvalueisthatdesired,pressthe
keyto
gotothenextdigittomodifytheothervalues�
Ifyoupressthe
keyafterchangingthelastdigit,itwilljumpbacktothefirstdigitsoyou
canmodifythepreviouslyprogrammedvaluesagain�
Theintegrationperiodmayrangefrom1to60minutes�
Tovalidatetheinformationandgotothenextprogrammingstep,press
�
Ifthevalueenteredisgreaterthanthemaximumprogrammingvalue,thedigitsflashfor2
secondsandtheprogrammedvalueisdeleted�