4�6�15� PROGRAMMING THE DIGITAL OUTPUT (
MODEL
CVM-C-xxx-RS485-C )
The
CVM-C5
digitaloutputmaybeprogrammedas:
Pulse by n kWh or kvarh (Energy)
:thevaluecorrespondingtotheenergyconsumed
orgeneratedmaybeprogrammed,togenerateapulse�
Alarm condition:
amagnitudemaybeassociatedwiththedigitaloutput,settinga
maximum,minimumanddelayvalueforthetripcondition�
Ifyoudonotwishtoprogramavariable,put00andvalidatewiththe
key�
Pulse programming by n kWh or kvarh
Onthisscreentheenergycodeisselectedbasedon
for
theenergyyouwantthepulseoutputtogenerate�
The
keyjumpsbetweenthedifferentoptions�
Table 12:
Codes for the different energy types.
Parameter
Code
ActiveEnergyIIITariff1
31
InductiveReactiveEnergyIIITariff1
32
CapacitiveReactiveEnergyIIITariff1
33
ApparentEnergyIIITariff1
48
ActiveEnergyIIIGeneratedTariff1
49
InductiveReactiveEnergyIIIGeneratedTariff1
50
CapacitiveReactiveEnergyIIIGeneratedTariff1
51
ApparentEnergyIIIGeneratedTariff1
52
ActiveEnergyIIITariff2
55
InductiveReactiveEnergyIIITariff2
56
CapacitiveReactiveEnergyIIITariff2
57
ApparentEnergyIIITariff2
58
ActiveEnergyIIIGeneratedTariff2
59
InductiveReactiveEnergyIIIGeneratedTariff2
60
CapacitiveReactiveEnergyIIIGeneratedTariff2
61
ApparentEnergyIIIGeneratedTariff2
62
ActiveEnergyConsumed
(Regardlessofthetariffselected)
99
OnceanEnergycodehasbeenselectedandvalidatedusingthe
keyyoumustenterthe
kilowattsperpulse�
35
Instruction Manual
CVM-C5-xxx-485
Summary of Contents for CVM-C5 Series
Page 1: ...INSTRUCTION MANUAL M026B01 03 21A Power analyzer CVM C5 ITF 485 CVM C5 MC 485 CVM C5 mV 485...
Page 2: ...2 CVM C5 xxx 485 Instruction Manual...
Page 50: ...8 CE CERTIFICATE 50 CVM C5 xxx 485 Instruction Manual...
Page 51: ...51 Instruction Manual CVM C5 xxx 485...
Page 52: ...52 CVM C5 xxx 485 Instruction Manual...