4�6�2� SECONDARY VOLTAGE
Onthisscreenthevoltagetransformersecondaryisprogrammed�
Toenterormodifythevoltagetransformersecondaryvalue,press
the
keyrepeatedly,increasingthevalueoftheflashingdigit�
Whentheon-screenvalueisthatdesired,pressthe
keytogotothenextdigitandmodify
theothervalues�
Ifyoupressthe
keyafterchangingthelastdigit,itwilljumpbacktothefirstdigitsoyou
canmodifythepreviouslyprogrammedvaluesagain�
Tovalidatetheinformationandgotothenextprogrammingstep,press
�
Ifthevalueenteredisgreaterthanthemaximumprogrammingvalue,thedigitsflashfor2
secondsandtheprogrammedvalueisdeleted�
Maximum programming value: 999.
Minimum programming value: 0.
4�6�3� PRIMARY CURRENT
Onthisscreenthecurrenttransformerprimaryisprogrammed�
Toenterormodifythetransformerprimaryvalue,pressthe
keyrepeatedly,increasingthevalueoftheflashingdigit�
Whentheon-screenvalueisthatdesired,pressthe
keyto
gotothenextdigittomodifytheothervalues�
Ifyoupressthe
keyafterchangingthelastdigit,itwilljumpbacktothefirstdigitsoyou
canmodifythepreviouslyprogrammedvaluesagain�
Tovalidatetheinformationandgotothenextprogrammingstep,press
�
Ifthevalueenteredisgreaterthanthemaximumprogrammingvalue,thedigitsflashfor2
secondsandtheprogrammedvalueisdeleted�
Maximum programming value: 9999.
Minimum programming value: 0.
29
Instruction Manual
CVM-C5-xxx-485
Summary of Contents for CVM-C5 Series
Page 1: ...INSTRUCTION MANUAL M026B01 03 21A Power analyzer CVM C5 ITF 485 CVM C5 MC 485 CVM C5 mV 485...
Page 2: ...2 CVM C5 xxx 485 Instruction Manual...
Page 50: ...8 CE CERTIFICATE 50 CVM C5 xxx 485 Instruction Manual...
Page 51: ...51 Instruction Manual CVM C5 xxx 485...
Page 52: ...52 CVM C5 xxx 485 Instruction Manual...