Toenterormodifythekilowattsperpulsevalue,pressthe
keyrepeatedly,increasingthevalueoftheflashingdigit�
Whentheon-screenvalueisthatdesired,pressthe
keyto
gotothenextdigittomodifytheothervalues�
Ifyoupressthe
keyafterchangingthelastdigit,itwilljumpbacktothefirstdigitsoyou
canmodifythepreviouslyprogrammedvaluesagain�
Example:
To program 500 Wh per pulse:
000.500
To program 1.5 kWh per pulse:
001.500
Oncethedesiredoptionhasbeenprogrammed,pressthe
keytovalidatetheinformation
andtherebyfinishprogrammingthedevice�
Maximum programming value: 999999 KWh.
Minimum programming value: 000.001 KWh.
Programming by alarm condition
Onthisscreentheparametercodeforwhichyouwantanalarm
tobegeneratedisselected,basedon
�
The
keyjumpsbetweenthedifferentoptions�
Table 13: Parameter codes for alarm programming�
Parameter
Code
Parameter
Code
VoltagePhase-NeutralL1
01
THDvoltageL3
27
CurrentL1
02
THDcurrentL3
30
ActivepowerL1
03
Activethree-phasepower
16
Inductive/CapativereactivepowerL1
04
InductiveReactivethree-phasepower
17
PowerfactorL1
05
CapacitiveReactivethree-phasepower
18
THDvoltageL1
25
Apparentthree-phasepower
34
THDcurrentL1
28
Maximumdemand
35
VoltagePhase-NeutralL2
06
Three-phasecurrent
36
CurrentL2
07
Cos
φ
19
ActivepowerL2
08
Three-phasePowerfactor
20
Inductive/CapativereactivepowerL2
09
Frequency
21
PowerfactorL2
10
VoltageL1-L2
22
THDvoltageL2
26
VoltageL2-L3
23
THDcurrentL2
29
VoltageL3-L1
24
VoltagePhase-NeutralL3
11
MaximumdemandL1
(1)
35
CurrentL3
12
MaximumdemandL2
(1)
42
36
CVM-C5-xxx-485
Instruction Manual
Summary of Contents for CVM-C5 Series
Page 1: ...INSTRUCTION MANUAL M026B01 03 21A Power analyzer CVM C5 ITF 485 CVM C5 MC 485 CVM C5 mV 485...
Page 2: ...2 CVM C5 xxx 485 Instruction Manual...
Page 50: ...8 CE CERTIFICATE 50 CVM C5 xxx 485 Instruction Manual...
Page 51: ...51 Instruction Manual CVM C5 xxx 485...
Page 52: ...52 CVM C5 xxx 485 Instruction Manual...