SETUP
Page 26 of 36
Figure 3.11 - RSLogix 5000 General module properties for Pre-start Warning
Next the user needs to add the connection requested packet interval (RPI). This is the
rate at which the input and output assemblies are exchanged. The recommended
value is 100ms.
Figure 3.12 - Connection module properties in RSLogix 5000
Once the module has been added to the RSLogix 5000 I/O tree the user must assign
the User Defined Types (UDTs) to the input and output assemblies. The user can
import the required UDTs by right-clicking on User-Defined sub-folder in the Data
Types folder of the I/O tree and selecting Import Data Type. The assemblies are then
assigned to the UDTs with a ladder copy instruction (COP) as shown in the figure
below.
Figure 3.13
–
RSLogix 5000 I/O module tree