6.5
Corrective maintenance
6.5.1
Problems – Causes
•
METERING CURRENT PRO
o
If no credits discounts despite consumption. Then the toroidal
transformer is probably assembled incorrectly
correct if necessary.
It could be problems with the corresponding card energy control (the main
or auxiliary). If it is appro
replace the corresponding toroidal transformer. Attention to assembling the
toroidal transformer because it has polarity.
toroidal brown side.
It is also important whatever the
that the original bridges have inserted, and reproduce in the spare card. Do
not replace any card under supply or with a different type.
o
If there is no reaction when the card is inserted, probably it not
recognizes the card or it is empty.
•
COMUNICATION PROBLEMS ( COM
The communication follows always the same order:
X2 communicates with R
communicates with the network. Obviously the posts which don’t have R
modem do not apply to
o
Behind a communication interruption check as the following order,
depending with the material that the
The
wirings peg.)
flashing.
When the R
are flashing.
I case that doesn’t work, check the twisted cable Rs
reliability and is will connected.
Check the R
necessary to know the PowerStudio and connect by modem or
Ethernet cable (inverted).
CIRCONTROL, S.A. – Innovació, 3 – 08232 – Viladecavalls (Barcelona)
Tel.: +34 937 362 940 – Fax: +34 937 362 941
rcontrol.com – E-mail:
orrective maintenance
s –
Solutions
METERING CURRENT PROBLEMS
If no credits discounts despite consumption. Then the toroidal
transformer is probably assembled incorrectly.
Solution: Check and
correct if necessary.
It could be problems with the corresponding card energy control (the main
or auxiliary). If it is appropriate replace it, remember that it must also
replace the corresponding toroidal transformer. Attention to assembling the
toroidal transformer because it has polarity. The ground wire must pass the
toroidal brown side.
It is also important whatever the type of electronic card to replace, to verify
that the original bridges have inserted, and reproduce in the spare card. Do
not replace any card under supply or with a different type.
If there is no reaction when the card is inserted, probably it not
the card or it is empty.
COMUNICATION PROBLEMS ( COM)
The communication follows always the same order:
X2 communicates with R-440. R-440 communicates with modem. Modem
communicates with the network. Obviously the posts which don’t have R
to them what is said.
a communication interruption check as the following order,
depending with the material that the CCL-CP2 incorporates:
The COM led of the X2 card Works correctly (see on electrical
wirings peg.). The communication with R-440 works when is
flashing.
When the R-440 communicates with the X2, the led Tx and Rx
are flashing.
I case that doesn’t work, check the twisted cable Rs
reliability and is will connected.
Terminal A = (+), Terminal B =( -)
Check the R-440 configuration is charged correctly. I
necessary to know the PowerStudio and connect by modem or
Ethernet cable (inverted).
Viladecavalls (Barcelona)
20
If no credits discounts despite consumption. Then the toroidal
Solution: Check and
It could be problems with the corresponding card energy control (the main
priate replace it, remember that it must also
replace the corresponding toroidal transformer. Attention to assembling the
The ground wire must pass the
type of electronic card to replace, to verify
that the original bridges have inserted, and reproduce in the spare card. Do
If there is no reaction when the card is inserted, probably it not
440 communicates with modem. Modem
communicates with the network. Obviously the posts which don’t have R-440 or
a communication interruption check as the following order,
incorporates:
led of the X2 card Works correctly (see on electrical
440 works when is
440 communicates with the X2, the led Tx and Rx
I case that doesn’t work, check the twisted cable Rs-485 has
configuration is charged correctly. It is
necessary to know the PowerStudio and connect by modem or