4.4
Electrical installation
Qualified professionals must undertake all
regardless of whether a project is needed or not, depending on the power installed.
The device already includes 30mA differential protection required, so if it’s necessary to
protect upstream, it must be selective or time sensitivity.
responsible for the design of the facility, so that REBT is met and to ensure maximum
system availability.
This device can not be installed in places where there is a risk of explosion (explosive
atmosphere).
The minimum breaking power of the automatic header switch (circuit breaker) must be
4500A.
Esta información es únicamente a título informativo, no ac
por cualquier posible daño o perjuicio que la instalación pueda provocar. Es el instalador final
quien deberá elegir (bajo su responsabilidad) la forma de instalación en función de las
variables citadas, especialmente las l
There is a ground terminal that
minimum section of 6mm
2
. I
ITS DIMENSIONS.
The minimum section of the conductors must be 6mm
the installation conditions (length, ducts,…)
appendices. The responsibility for the installation corresponds to the authorized
installer that designs and makes.
Depending on the model, t
devices, so it will be able to send and receive commands or information.
The Rs-485 network installation must follow the requirements that the standard
prescript, among others, the linear topology, end
equipotential mass, ... Such communication can be enhanced by connecting to R
module or multipoint system; data can then be stored and accessed via Ethernet..
The following layouts show the outline of the installation in blocks. They are shown
for information purposes only.
dimensioning the section, protection elements and lengths, in compliance with the
current regulations.
CIRCONTROL, S.A. – Innovació, 3 – 08232 – Viladecavalls (Barcelona)
Tel.: +34 937 362 940 – Fax: +34 937 362 941
rcontrol.com – E-mail:
Electrical installation. General considerations
Qualified professionals must undertake all activities related to the electrical installation,
regardless of whether a project is needed or not, depending on the power installed.
This unit has been designed for its use in a single
230Va.c. and three-phase 400Va.c. with a ±10% tolerance.
The device already includes 30mA differential protection required, so if it’s necessary to
, it must be selective or time sensitivity. The choice must be made by
responsible for the design of the facility, so that REBT is met and to ensure maximum
be installed in places where there is a risk of explosion (explosive
The minimum breaking power of the automatic header switch (circuit breaker) must be
Esta información es únicamente a título informativo, no aceptándose responsabilidad alguna
por cualquier posible daño o perjuicio que la instalación pueda provocar. Es el instalador final
quien deberá elegir (bajo su responsabilidad) la forma de instalación en función de las
variables citadas, especialmente las legalmente exigibles en su país.
There is a ground terminal that must be properly wired to the conductor with the
. IT IS VERY IMPORTANT ITS RIGHT CONNECTION AND
The minimum section of the conductors must be 6mm
2
, but that will be in function of
the installation conditions (length, ducts,…) may be higher. Consult REBT or the
appendices. The responsibility for the installation corresponds to the authorized
installer that designs and makes.
Depending on the model, the device is able to communicate by Rs-
devices, so it will be able to send and receive commands or information.
installation must follow the requirements that the standard
among others, the linear topology, end of line resistor, shielding,
Such communication can be enhanced by connecting to R
module or multipoint system; data can then be stored and accessed via Ethernet..
In any case, the end user must be protected against
indirect contact with a residual voltage relay (DDR or
differences) with a sensitivity of 30mA.
The following layouts show the outline of the installation in blocks. They are shown
for information purposes only. The installation company will be responsible for
dimensioning the section, protection elements and lengths, in compliance with the
Viladecavalls (Barcelona)
10
activities related to the electrical installation,
regardless of whether a project is needed or not, depending on the power installed.
This unit has been designed for its use in a single-phase
with a ±10% tolerance.
The device already includes 30mA differential protection required, so if it’s necessary to
The choice must be made by
responsible for the design of the facility, so that REBT is met and to ensure maximum
be installed in places where there is a risk of explosion (explosive
The minimum breaking power of the automatic header switch (circuit breaker) must be
eptándose responsabilidad alguna
por cualquier posible daño o perjuicio que la instalación pueda provocar. Es el instalador final
quien deberá elegir (bajo su responsabilidad) la forma de instalación en función de las
must be properly wired to the conductor with the
S VERY IMPORTANT ITS RIGHT CONNECTION AND
, but that will be in function of
may be higher. Consult REBT or the
appendices. The responsibility for the installation corresponds to the authorized
-485 compatible
devices, so it will be able to send and receive commands or information.
installation must follow the requirements that the standard
of line resistor, shielding,
Such communication can be enhanced by connecting to R-440
module or multipoint system; data can then be stored and accessed via Ethernet..
n any case, the end user must be protected against
indirect contact with a residual voltage relay (DDR or
The following layouts show the outline of the installation in blocks. They are shown
The installation company will be responsible for
dimensioning the section, protection elements and lengths, in compliance with the