MAINTENANCE WITH Q & A
74
FROZEN COIL TROUBLESHOOTING PROCEDURES (OPTIONAL EQUIPMENT)
PROBLEM
PROBABLE CAUSE
CORRECTIVE ACTION
Coil not
freezing water
Frozen Coil Mode not engaged Dewpoint not low enough, let wet coil remove moisture
before unit enters frozen coil mode
Solenoid valve not working
Check liquid line solenoid (Frozen Coil)
Check EPR bypass solenoid. Do they have power?
Frozen Coil T.E.V. out of
adjustment
Adjust T.E.V. to increase superheat
Verify Frozen Coil is turned on by the event
and/or switch on the control panel
Table 5-9: Frozen Coil Troubleshooting Procedures
HIGH/LOW LIMIT CONTROL TROUBLESHOOTING ROCEDURES
PROBLEM
PROBABLE CAUSE
CORRECTIVE ACTION
No display on
control panel
AC unit is not connected, or is
connected improperly
Check AC input connections and correct if necessary. If
connections are correct and the there is still no display,
contact CSZ's Service Department.
Display indicates "- .
. ." and yellow
LO LIMIT LED is ON.
Solenoid coil burned out
Repair or replace the thermocouple
Display error
Sensor is connected improperly Check sensor locations, connections, and sensing
element. Repair or replace sensor as required
Place jumper wire across thermocouple terminals.
Indicator is functioning properly if display indicates
room temperature
Display indicates "-
000" and flashes
Jumper W8 for °F/°C selection is
not installed or is installed
improperly
Install Jumper W8 in desired location for °F or °C
Control is in a LO or
HI LIMIT condition
and cannot be reset
Actual temperature is below low
limit setpoint or above high limit
setpoint
Check low limit and high limit setpoints. If actual
temperature is not between low and high limit
setpoints, it cannot be reset, though alarm can be
silenced
If external reset switch is used, check wiring of external
reset switch
LO or HI LIMIT
temperature does
not appear accurate
Calibration adjustments incorrect Perform field calibration procedure.
Table 5-10: High/Low Limit Control Troubleshooting Procedures
Summary of Contents for ZP Series
Page 1: ...58911 rev B 1 2021 Installation Operation Maintenance Manual ZP Series ...
Page 4: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 6: ...CHAMBER LABELS AND MEANINGS ii THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 12: ...TABLE OF CONTENTS viii THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 24: ...GENERAL DESCRIPTION 12 Figure 2 4 Achievable Humidity Points ...
Page 52: ...GENERAL DESCRIPTION 40 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 66: ...OPERATING INSTRUCTIONS 54 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 96: ...MAINTENANCE WITH Q A 84 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 98: ...SERVICE PARTS WARRANTY 86 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 99: ...SYSTEM DIAGRAMS ELECTRICAL SCHEMATIC SYMBOLS Figure 9 1 Symbols Used on Electrical Scematics ...