MAINTENANCE WITH Q & A
75
SATURATED TEMPERATURE/PRESSURE CHART
TEMP.
GAUGE PRESSURE (P.S.I.G.)
°
F
R-404A
R-410A
R-23
R-508B
-130
28.0*
-
11.4*
3.8*
-125
27.5*
-
7.9*
0.4
-120
27.0*
-
3.9*
2.9
-115
26.1*
-
0.3*
5.9
-110
25.5*
-
2.9
9.2
-105
24.6*
-
5.7
12.8
-100
23.5*
-
9.0
16.8
-95
22.3*
-
12.7
21.4
-90
20.9*
-
16.7
26.3
-85
19.2*
-
21.3
31.8
-80
17.5*
12.0*
26.3
37.8
-75
15.2*
10.2*
32.0
44.3
-70
12.8*
7.0*
38.0
51.5
-65
10.1*
3.4*
44.7
59.3
-60
7.0*
0.3
52.0
67.7
-55
3.6*
2.5
60.0
76.9
-50
0.2
5.0
68.7
86.8
-45
2.2
7.8
78.1
97.5
-40
4.5
10.8
88.3
109.0
-35
7.0
14.2
99.4
121.3
-30
9.8
17.8
111.3
134.6
-25
12.9
21.9
124.0
148.8
-20
16.2
26.3
137.8
164.0
-15
19.9
31.2
152.5
180.2
-10
23.8
36.4
168.2
197.5
-5
28.1
42.2
185.1
215.8
0
32.8
48.2
202.9
235.3
5
37.8
55.1
221.1
256.0
10
43.3
62.1
242.4
277.9
15
49.1
70.1
264.0
301.2
20
55.4
78.2
286.9
325.7
25
62.2
87.5
311.3
351.6
30
69.4
96.8
337.1
378.9
35
77.2
107.5
364.5
407.7
40
85.5
118.0
393.6
438.0
45
94.3
130.2
424.4
469.9
50
113.7
142.0
457.1
503.5
55
115.7
156.0
491.7
538.7
60
124.3
170.0
528.5
Critical
65
135.6
185.2
567.5
Pressure
70
147.5
200.0
608.9
75
160.1
218.0
652.9
80
173.5
235.0
Critical
85
187.6
254.0
Pressure
90
202.4
274.0
95
218.1
295.0
100
234.6
317.0
105
252.0
340.0
110
270.3
364.0
115
289.5
390.0
120
309.6
417.0
125
330.8
445.0
130
352.9
475.0
135
376.1
506.0
140
400.5
538.0
*inches of mercury below one atmosphere
Summary of Contents for ZP Series
Page 1: ...58911 rev B 1 2021 Installation Operation Maintenance Manual ZP Series ...
Page 4: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 6: ...CHAMBER LABELS AND MEANINGS ii THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 12: ...TABLE OF CONTENTS viii THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 24: ...GENERAL DESCRIPTION 12 Figure 2 4 Achievable Humidity Points ...
Page 52: ...GENERAL DESCRIPTION 40 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 66: ...OPERATING INSTRUCTIONS 54 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 96: ...MAINTENANCE WITH Q A 84 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 98: ...SERVICE PARTS WARRANTY 86 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 99: ...SYSTEM DIAGRAMS ELECTRICAL SCHEMATIC SYMBOLS Figure 9 1 Symbols Used on Electrical Scematics ...