Positioning User Manual
42
552
Target address
change error
A command to change target address is issued while the
axis stops or dwells. (A command to change target address
is possible during a phase of acceleration, deceleration or
constant speed).
553
Duplicated position control
Another position control command is issued while the axis
is in operation.
554
Online edit error
Online program edit/modify is performed while the axis is
in operation.
Parameter
904
Pulse output mode
setting error
An unsupported value other than 0 or 1 is entered for the
pulse output mode of the parameters.
906
Bias speed setting error
When the bias speed is out of the setting range.
910
Speed limit setting error
When the speed is out of the setting range.
911
Acceleration and
Deceleration time No. 0
When it is beyond the setting range (0
~
65535 ms) of the
Acceleration and Deceleration time No. 0.
912
Acceleration and
Deceleration time No. 1
When it is beyond the setting range (0
~
65535 ms) of the
Acceleration and Deceleration time No. 1.
913
Acceleration and
Deceleration time No. 2
When it is beyond the setting range (0
~
65535 ms) of the
Acceleration and Deceleration time No. 2.
914
Acceleration and
Deceleration time No. 3
When it is beyond the setting range (0
~
65535 ms) of the
Acceleration and Deceleration time No. 3.
920
Backlash setting error
When the backlash compensation value is beyond the
setting range (0
~
65535).
921
Software upper limit
setting error
When the software upper limit value is out of the setting
range (-2,137, 483, 648
~
2,147,483,647).
922
Software lower limit
setting error
When the software lower limit value is out of the setting
range (-2,137, 483, 648
~
2,147,483,647).
956 Jog speed limit setting error
When the jog operation speed is configure higher than the
jog speed limit of the extended parameters.
980
OPR method setting error
When a wrong configuration value other than 0
~
3 is
entered for the OPR method setting.
981
OPR direction setting error
When a wrong configuration value other than 0 or 1 is
entered for the OPR direction setting.