CIAT VECTIOS POWER IPJ Series Instruction Manual Download Page 47

VECTIOS

POWER TM

 PJ

EN-47

12  -  FACTORY OPTIONS AND ACCESSORIES

12.11 Zoning of the air 

fl

 ow

This option allows the management of the air 

fl

 ow of the unit 

to condition up to 4 di

 erent zones with a minimum air 

fl

 ow of 

35% (all of them in same operating mode: heating or cooling). 
This function allows to adapt the indoor air 

fl

 ow to the installation 

requirements. 

Electrical

cabinet

zone 1 

(addr.11)

Servo. zone 1

Servo. zone 2

Servo. zone 3

Servo. zone 4

zone 2 

(addr.12)

zone 3 

(addr.13)

zone 4 

(addr.14)

The installer must carry out the following connections:

 Connection of the zone terminals: 

-  Power supply (the same as the control board) at 230Vac 

50/60Hz (L&N): 2 wires (section 0.5 at 1.5 mm

2

).

-  Communication (RX+/TX+ & RX-/TX-): shielded cable 

type AWG20 or AWG22 with 1 braided pair + dra 
shielding (e.g., model BELDEN 7703NH).  

Zone terminals can be installed at a maximum distance of 
100 metres from the zoning box. 
These terminals are con

fi

 gured with their corresponding 

address in the factory. In the unlikely event of a communications 
failure the screen will display “

Cn

”. Please make sure to check 

connections and the 

fi

 rmware version.

 Connection of the servomotors for the supply dampers: 

 - 5 wires (section 0.5 at 1.5 mm

2

), supply 24Vac.

 Connection to the electrical cabinet of the PJ unit: 

-  Power supply: 230Vac ((L&N): 2 wires (section 0.5 at 1.5 

mm

2

).

-  Communication (RX+/TX+ & RX-/TX-): shielded cable 

type AWG20 or AWG22 with 1 braided pair + dra 
shielding (e.g., model BELDEN 7703NH). 

Note: Please refer to the wiring diagram provided with the unit 
and the Vectic control manual to get more detailed information 
about the wiring.

Zone terminals

These terminals are the same as the TCO user’s terminal 
(optional). 

The main screen shows the ambient 
temperature, current operating mode of 
the unit, time and day of the week.
The following screen shows the 
temperature setpoint for this zone in the 
current operating mode.

This screen can also show the zone that corresponds to the 
terminal, the regulation band  associated with the temperature 
setpoint, the  active alarms by means of codes and the delay 
set for the opening/closing of the damper.
These terminals also allow the schedule programming.
With the air zoning, the VecticGD terminal it also provides 
information on setpoints for each zone.

Zoning box connections

The control board of the air zoning is assembled in a separate 

box from the PJ unit. This board is connected in series on the 

Field-Bus of the main board of the Vectic control, placed on the 

electrical cabinet of the unit.  

Regulation gives the control signal to the dampers installed 
in each zone (dampers and servomotors for those dampers 
not supplied). The unit modifies the air flow and capacity 
depending on information coming from sensors in each zone 
and considering active zones in each moment. 
The option includes 4 zone terminals (one for each zone), the 
additional control board supplied in an independent box to be 
connected with the 4 terminals, the unit board and also to the 
servomotors that control dampers in each zone (dampers and 
servos not supplied). 
The temperature information for each zone is coming from 
temperature sensor integrated inside each zone terminal. It is 
not needed to install any extra ambient sensor. 

Summary of Contents for VECTIOS POWER IPJ Series

Page 1: ...NA 20 574 A 10 2020 BROCHURE Instruction manual VECTIOS POWER TM PJ...

Page 2: ......

Page 3: ...he costumer 22 9 FANS AND AIR DUCTS 25 9 1 Checks in the axial fans 25 9 2 Checks in the EC plug fans 25 9 3 Checks in the centrifugal fans optional 25 9 4 Air ducts connections 26 10 CONDENSATE DRAIN...

Page 4: ......

Page 5: ...cumentation provided with the product In case of a leak Toxicity According to EN 378 1 R 410A belongs to the A1 A1 group i e with high safety both in the mix and also in the case of a leak Although it...

Page 6: ...g fan or centrifugal fan in top box Rotary heat exchanger passive recovery I I I R R R N I R N I E I I R N E N I I R E R N I I E N I I R E N I I R E E N I I R Indoor airflow direction Group 25 0 Lower...

Page 7: ...pment Directive Markings name plate punch marks labels must remain visible They must not be altered removed or modified With a condensation pressure control operating down to 10 C When the outdoor tem...

Page 8: ...rall dimensions of the available assemblies in paragraph 7 6 Recommended service clearance Gripping point Container discharge In case of container transport the unit incorporates skids that facilitate...

Page 9: ...directly on silent blocks to the ground it is recommended that a template of the unit s footprint with the anchoring points of the silent blocks be made as described in the paragraph Preparation of t...

Page 10: ...TION These roofcurbs can also incorporate a gas burner For more information consult the paragraph 12 9 Gas burner Note There are a wide range of adaptation roofcurbs that are ready for direct replacem...

Page 11: ...lied with a return safety grille intended for plenum installations For installations with ducted return the grille must be removed prior to place the machine on the roofcurb Safety grille 7 POSITIONIN...

Page 12: ...Supply Return Supply Return Supply Return Note Position A is best suited for gas burner roofcurb In this position it is easier to access the burner register It is also the most optimal solution in are...

Page 13: ...1698 546 568 95 418 220 264 1522 164 PCH130 50 1698 546 171 95 943 92 264 1522 164 0560 to 0720 50 2004 546 171 95 943 92 264 1827 164 0760 to 0960 50 2200 546 171 95 943 92 264 2022 164 1050 to 1200...

Page 14: ...fety grille Important All roofcurb are supplied with a return safety grille intended for plenum installations For installations with ducted return the grille must be removed prior to place the machine...

Page 15: ...et profile 2 L shaped brackets using the 4 screws supplied in a bag self tapping screws M4 8 Profile for outlet Closing plate The procedure is the same as that used for supply except with the CS assem...

Page 16: ...vity mm Weight kg Reactions in the supports kg X Y Z R1 R2 R3 R4 R5 R6 0420 1723 1210 853 1780 276 361 178 312 434 218 0450 1723 1210 853 1795 279 364 179 315 438 220 0500 1723 1210 853 1810 281 367 1...

Page 17: ...IPJ CR assembly Centre of gravity mm Weight kg Reactions in the supports kg X Y Z R1 R2 R3 R4 R5 R6 R7 R8 0760 2561 1200 960 2935 270 475 333 280 313 569 378 317 0840 2543 1211 946 3005 277 483 336 2...

Page 18: ...720 A B C D A B C D IPJ Overall dimensions mm Service clearance mm Length Width Height A B C D 0420 to 0500 3 820 2 257 2 293 2 200 1 000 1 200 1 000 0560 to 0720 4 224 2 257 2 340 2 400 1 000 1 200 1...

Page 19: ...5 300 2 257 2 421 2 600 2 500 1 200 1 000 1050 to 1200 6 350 2 257 2 494 3 000 2 500 1 200 1 000 IPJ Overall dimensions mm Service clearance mm Length Width Height A B C D 0760 to 0960 5 300 2 257 2...

Page 20: ...lation The access doors are insulated to prevent condensation 8 3 Wire sizing Wire sizing is the responsibility of the installer to suit the characteristics of the installation site and comply with ap...

Page 21: ...onnected in intermediate boxes located next to these components BOX1 Motor compressor circuit 1 BOX2 Motor compressor circuit 2 BOX3 Mixing box BOX4 Indoor unit BOX5 Rotary heat exchanger optional In...

Page 22: ...Vectic electronic control Vectic electronic control is basically comprised of a control board sensors a VecticGD graphic terminal a TCO user terminal optional and a BMS card optional By default this...

Page 23: ...ac 2 wires Temperature S21 to S24 Temperature humidity S31 to S34 Note in the case of more than one probe connection of the probes in series in the RS485 network Please refer to the control manual S5a...

Page 24: ...the air duct in these two ways Electrical connection This probe S10 is configured as analogue output 4 20 mA 0 2000 ppm in the analogue input B10 of the control board connector J18 Recommended cable s...

Page 25: ...minal please refer to the Vectic control brochure 9 FANS AND AIR DUCTS Flow control pressostat 9 3 Checks in the centrifugal fans optional If the unit is equipped with centrifugal return fans availabl...

Page 26: ...or Consideration should be given to the need to install filters on the return ducts taking into account any particles in suspension existing which could settle inside the machine e g textile fibres Fl...

Page 27: ...uction can be made CONNECT SIPHON METTRE SIPHON PONER SIFON V220014 10 CONDENSATE DRAIN Important the water drain pipe must be provided with a siphon to avoid bad smell and water spills A Condensates...

Page 28: ...ches the setpoint It disconnects at 42 bar and it is automatically reactivated Protection for power lines Protection for power lines of compressors with manual motor starters and power lines of fan mo...

Page 29: ...ature has dropped to below 40 C Note Vectic electronic control allows to select the functioning logic for the fulfillment of the ERP French fire regulations Remote alarm optional Vectic control allows...

Page 30: ...them back on attaching the profile 12 FACTORY OPTIONS AND ACCESSORIES 12 1 Dampers hoods Depending on the assembly chosen the fresh air and exhaust air damper hoods are supplied folded down to be fit...

Page 31: ...Note On models 0760 to 1200 there is no such support bed Next the module is coupled to the unit Do not remove the fork lift truck until the module is not secured to the unit The module is secured to t...

Page 32: ...n screws Left hand panel Drain connection Filters on the exhaust air outlet Access panel to filters M4 Allen screws Wheel Filters on the fresh air intake The thickness of the frames is 25 mm for the G...

Page 33: ...eliminate by opening the purger Pour more water into the circuit and repeat the previous steps Activate the water pump to be foreseen by the installer and repeat the previous steps until no air noises...

Page 34: ...essed by the same panel that the supply fan These heaters are accessed by removing the panels 1 and 2 and then the inside panel 3 all of them fixed with M6 Allen screws Frame attachment screw 1 3 2 To...

Page 35: ...of the water circuit is connected As a backup in COOLING mode in accordance with the return and the outlet temperatures Note the hot water coil is not compatible with the stop drop in the indoor coil...

Page 36: ...rating range allowing it to increase its performance when the thermal power drops If there is no combustion air the valve will not supply gas if the combustion air flow drops the valve will automatica...

Page 37: ...over the burner do not touch the moving parts of the burner General recommendations Delivery of the roofcurb with gas burner Check the condition of the equipment upon delivery Check that the details...

Page 38: ...to the required depth Tighten the screw on the bracket to fasten 3 x M3x10 self tapping male Rotate to open Rotate to close Clamp for attaching to the duct Screw to fix the probe position PT3 5x12 61...

Page 39: ...l on the roof by means of its own ducting Type C53 Sealed combustion circuit type C connected by means of its own ducting split in two terminals which could end up in areas with di erent pressure such...

Page 40: ...w ex GZ41 5 Poland can be found in the manufacturer s installation and maintenance manual APENGROUP supplied with the unit PCH130 PCH160 PCH210 PCH080 Gas supply 1 1 2 5 Gas filter small section 6 Ant...

Page 41: ...nds the unit is supplied already set up and regulated for G20 or G25 3 Conversion from one type of gas to another can only be performed by authorised service centres Note The conversion kit to G25 G25...

Page 42: ...ic reset and positive safety setting is installed on the heater module The breaking of the sensitive element corresponds to a safety intervention When the thermostat intervenes through the flame monit...

Page 43: ...stead of the compressors if the outdoor temperature is lower than the value set 5 C by default When the return temperature drops below the value set for the burner connection the burner will start to...

Page 44: ...the bottom towards the top and they start over when the end of the menu is reached Entering the password From the initial screen ON OFF rdy FXX use the arrow up and arrow down keys to reach the ABI f...

Page 45: ...ng the second password grants access to third level This password must be requested directly to CIAT technical service Fault Description Cause Remedy Blocks caused by Flame Dependent on the TER equipm...

Page 46: ...frigerant charge of the recovery circuit when this one is lower than required It s placed on the liquid line before the dryer filter In models 0420 to 0720 the charging valve can be accessed via the c...

Page 47: ...he unit and the Vectic control manual to get more detailed information about the wiring Zone terminals These terminals are the same as the TCO user s terminal optional The main screen shows the ambien...

Page 48: ...SOR S STARTING AU PREMIER D MARRAGE OU APR S UNE ABSCENCE TENSION 24 HEURES AVANT D AUTORISER LE D MARRAGE DU DES COMPRESSEUR S AL PRIMO AVVIAMENTO U DOPO UNA INTERRUZIONE PROLUNGATA DELLA ALIMENTAZIO...

Page 49: ...C Gas inlet temperature C Liquid outlet temperature 3 C Subcooling 2 3 C Overheating 4 1 C Check the unit operation by verifying the electronic control and the safety devices It is also recommendable...

Page 50: ...ing oil from an opened container stored under incorrect conditions Check the oil level and aspect In case of a colour change check the oil quality using a contamination test In the case of the presenc...

Page 51: ...down the operating readings and perform the following checks at least twice a year and mandatory after each time a unit is started for seasonal use Weekly checks With the unit running at full capacity...

Page 52: ...replaced on site by other types of filters with di erent thickness The filter holder structure supports the following filter combinations 25 mm 25 mm 50 mm 50 mm 50 mm The filter holder structure inc...

Page 53: ...onic control The same recommendations for the maintenance of the components of the main circuits must be followed for the components of this circuit Refrigerant leak detector optional The gas detector...

Page 54: ...g lifetime of the heater it is advisable to run some inspections every year before turning it on for the season 1 check the status of the start up electrodes detection electrodes and pilot flame 2 che...

Page 55: ...8 Inspection of the safety thermostat s This procedure must be done with the heater on and the burner lit Open the thermostat series with an insulated tool 230 V remove the fast on from the safety th...

Page 56: ...element are open c Timing of anti cycle short does not allow the starting d Open contact e Contactor coil burnt f Indoor klixon open a Check di erential fuses b Verify the safety chain of the electro...

Page 57: ...o be recovered for treatment Refrigerant Energy transfer fluid depending on the installation water glycol water mix Compressor oil Important In order to recycle these units follow the stipulations of...

Page 58: ...Notas...

Page 59: ......

Page 60: ......

Reviews: