VECTIOS
POWER TM
PJ
EN-13
Self-adhesive rubber gasket
of 9 mm (standard)
External insulation
(to be carried
out by the installer)
Sealing upsweep, that must be
performed on all sides of the roofcurb
(to be carried out by the installer)
Insulation of 9 mm on
the ducts of supply
and return (standard)
Upper profile of 40 mm
for waterproof sealing
7 - POSITIONING AND INSTALLATION
Air ducts connections
For units with vertical air
fl
ow, the ducts must be connected to
the pro
fi
les from underneath the roofcurb.
In order to carry out the air ducts follow the recommendations
in the paragraph 9.4 “Air ducts connections”.
A
E
D
C
A
A
A
F
A
B
A
A
153mm
A
Dimensions (mm)
A
B
C
D
E
F
Standard
roofcurb
0420 to 0500
51
1699
547
612
547 1699 (*)
0560 to 0720
51
2005
547
612
547 2005 (*)
0760 to 0960
51
2200
547
612
547 2200 (*)
1050 to 1200
51
2596
547
612
547 2596 (*)
Burner roofcurb
Dimensions (mm)
A B C D E F G H
I
J
Burner
roofcurb
0420 to 0500
PCH080
50 1698 546 568 95 418 220 264 1522 164
PCH130
50 1698 546 171 95 943 92 264 1522 164
0560 to 0720
50 2004 546 171 95 943 92 264 1827 164
0760 to 0960
50 2200 546 171 95 943 92 264 2022 164
1050 to 1200
50 2597 546 171 95 943 92 264 2419 164
Standard roofcurb
G
E
D
C
F
A
A
B
A
I
H
J
A
Dimensions (mm)
A
B
C
D
E
a
Burner
roofcurb
0420 to 0500
1259 1121 109 33 855 2,3º (4,0%)
0560 to 0720
PCH130
1259 1121 109 33 855 2,0º (3,5%)
PCH160
1259 1121 109 33 814 2,0º (3,5%)
0760 a 0960
1259 1121 109 33 814 1,6º (2,8%)
1050 to 1200
1259 1121 109 33 814 1,3º (2,3%)
Side view after installation on roof (position C):
a
A
C
B
D
a
A
C
B
D
E
Standard roofcurb
Dimensions (mm)
A
B
C
D
a
Standard
roofcurb
0420 to 0500
538
400
133
33
2,3º (4,0%)
0560 to 0960
538
400
133
33
2,0º (3,5%)
1050 to 1200
538
400
133
33
1,3º (2,3%)
Burner roofcurb
a = maximum slope
a = maximum slope
Detail of the roofcurb installed on the roof (position C):
The thickness of the sheet metal profiles to connect the
discharge and/or return ducts to the roofcurb are shown in the
following tables:
Note: If the unit incorporates a hot water coil (optional), the
length of the supply duct is reduced by 153 mm.