3.6.2 - Volt-free contact on/off/cooling/heating
If the unit works in the remote operating mode (Remote) and the
automatic heating/cooling changeover function is not selected and
if the user configuration allows this (heat pump and Pro-Dialog in
-
terface selection) the operation of the on/off contacts and the heat-
ing/cooling contacts is as follows:
Without multiplexing
Off
On cooling
On heating
On/off contact
Open
Closed
Closed
Heating/cooling contact
-
Open
Closed
With multiplexing
Off
On
cooling
On
heating
On
auto
On/off contact
Open
Closed
Closed
Open
Heating/cooling contact
Open
Open
Closed
Closed
NOTE: The automatic changeover function (on auto) selects
the cooling or heating mode based on the outdoor tempera-
ture (see chapter 5.2).
3.6.3 - Volt-free setpoint selection contact
Cooling
Heating
csp 1
csp 2
hsp 1
hsp 2
Set point selection contact
Open
Closed
Open
Closed
3.6.4 - Volt-free demand limit selection contact
100%
Limit 1
Limit 2
Limit 3
Demand limit 1
Open
Closed
Open
Closed
Demand limit 2
Open
Open
Closed
Closed