CIAT PRO-DIALOG+ Instruction Manual Download Page 25

6 - DIAGNOSTICS - TROUBLESHOOTING

6.4 - Alarm codes

Alarm 
No.

Alarm 
code

Alarm description

Reset type

Probable cause

Action taken by the 
control

Thermistor faults

1

th-01

Sensor fault, fluid entering water 

heat exchanger

Automatic when the temperature 

measured by the sensor returns to 

normal

Defective thermistor

Unit is shut down

2

th-02

Sensor fault, fluid leaving water heat 

exchanger

As above

As above

As above

3

th-03

Defrost fault, circuit A

As above

As above

Circuit is shut down, if the unit 

is in heating mode

4

th-04

Defrost fault, circuit B or  second 

default sensor fault, circuit B

As above

As above

As above

5

th-10

Outside temperature sensor fault

As above

As above

Unit is shut down

6

th-11

CHWS fluid sensor fault  

(master/slave)

As above

As above

The master/slave mode is 

stopped

7

th-12

Suction sensor fault, circuit A

As above

As above

Circuit is shut down

8

th-13

Suction sensor fault, circuit B

As above

As above

As above

9

th-44

Suction sensor fault, coil 1

As above

As above

As above

10

th-45

Suction sensor fault, coil 2

As above

As above

As above

Pressure transducer faults

11

Pr-01

Discharge pressure transducer fault, 

circuit A

Automatic when the voltage 

transmitted by the sensor returns to 

normal

Defective transducer or installation 

fault

Circuit is shut down

12

Pr-02

Discharge pressure transducer fault, 

circuit B

As above

As above

As above

13

Pr-04

Suction pressure transducer fault, 

circuit A

As above

As above

As above

14

Pr-05

Suction pressure transducer fault, 

circuit B

As above

As above

As above

51

Pr-24

Entering water pressure sensor fault Automatic when the voltage 

transmitted by the sensor returns to 

normal

Defective transducer or installation 

fault

Circuit is shut down

52

Pr-25

Leaving water pressure sensor fault As above

As above

As above

Communication with the slave boards

15

CO-BB

Communication loss with the NRCP2 

board

Automatic when communication is 

re-established

Installation bus fault or defective 

slave board

Depending on the configuration, 

compressor A3 is shut down or 

circuit B is shut down.

16

Co-ht

Communication loss with the 

additonal heating stage board

As above

As above

The additional heating stages 

are shut down

17

Co-e1

Communication loss with the EXV 

board

As above

As above

Unit is shut down

18

Co-o1

Communication loss with the 

PD-AUX 1 board

As above

As above

Unit with optional water 

pressure sensors, unit is shut 

down

19

Co-o2

Communication loss with the 

PD-AUX 2 board

As above

As above

None

Process faults

20

P-01

Water heat exchanger frost 

protection

Automatic if the same alarm has 

not tripped during the last 24 hours, 

otherwise manual.

Water flow rate too low or defective 

thermistor

Unit is shut down

21

P-05

Low suction temperature, circuit A

Automatic when the temperature 

returns to normal, and if this alarm 

has not appeared during the last 24 

hours, otherwise manual.

Pressure sensor defective, EXV 

blocked or low refrigerant charge

Circuit  is shut down

22

P-06

Low suction temperature, circuit B

As above

As above

As above

23

P-08

High superheat, circuit A

As above

As above

As above

24

P-09

High superheat, circuit B

As above

As above

As above

25

P-11

Low superheat, circuit A

As above

As above

As above

26

P-12

Low superheat, circuit B

As above

As above

As above

27

P-14

Water flow control and customer 

interlock fault

Automatic if the unit is in manual 

shut-down status, otherwise manual.

Heat exchanger pump defect or 

water flow switch fault

Unit is shut down

28

P-16

Compressor A1 not started or no 

pressure increase registered

Manual

Connection problem

Compressor is shut down

29

P-17

Compressor A2 not started or no 

pressure increase registered

As above

As above

As above

30

P-18

Compressor A3 not started or no 

pressure increase registered

As above

As above

As above

31

P-20

Compressor B1 not started or no 

pressure increase registered

As above

As above

As above

32

P-21

Compressor B2 not started or no 

pressure increase registered

As above

As above

As above

 

 

EN - 23 

EREBA ACCESS

Summary of Contents for PRO-DIALOG+

Page 1: ...Instruction manual EREBA ACCESS 8 40 kW 11 2016 10183 PRO DIALOG...

Page 2: ......

Page 3: ...3 Password screens 6 4 4 Menu screen characteristics 6 4 5 Data screen or configurable parameter characteristics 6 4 6 Parameter modification 7 4 7 Operating mode screen 7 4 8 Menu tree structure 8 4...

Page 4: ...ty to the unit be shut off before any work is begun Shut off the main power supply at the main circuit breaker or isolator IMPORTANT This equipment conforms to all applicable codes regarding electroma...

Page 5: ...mounted under a metal plate An optional water system temperature sen sor can be used for master slave assembly control in the case of leaving water control In heat pump units a sensor placed on an air...

Page 6: ...24 30A 31A NRCP2 BASE Unit operation relay output J3 CH 25 37 38 NRCP2 BASE Network connection J12 NRCP2 BASE RS 485 series connection Pin 1 signal Pin 2 ground Pin 3 signal Setpoint selection J4 CH 8...

Page 7: ...g cooling contact Open Closed With multiplexing Off On cooling On heating On auto On off contact Open Closed Closed Open Heating cooling contact Open Open Closed Closed NOTE The automatic changeover f...

Page 8: ...cs There are four default screens Each screen shows The unit status its screen number Three displayed parameters LOCAL OFF 1 On the left the unit status on the right the screen number Entering water t...

Page 9: ...on hps1 40 0 C hps2 40 0 C hramp_sp 27 4 C Cooling Setpoint 2 Description of the item framed by the selection cursor The following screen allows modification of a parameter Modify value Screen descrip...

Page 10: ...OLIDY16S HOLIDY02S OCC1P01S OCC1P02S NAVIGATION Password 0 ACCESS ALL USER DEFAULT SCREENS PASSWORD General parameters Temperatures Pressures Setpoint Inputs Outputs Pump status Operating time Unit st...

Page 11: ...emperature OAT nnn n C Outside air temperature CHWSTEMP nnn n C Common master slave temperature SCT_A nnn n C Saturated condensing temperature A SST_A nnn n C Saturated suction temperature A SCT_B nnn...

Page 12: ...B HD_POS_B 0 100 Position variable fan speed controller B RV_B On Off Four way refrigerant valve C_HEATER On Off Heat exchanger and lower coil heater BOILER On Off Boiler output EHS_STEP 0 4 Electric...

Page 13: ...urs Operating hours pump 1 hr_cpum2 nnnnn hours Operating hours pump 2 nb_def_a nnnnn Number of defrost cycles circuit B nb_def_b nnnnn Number of defrost cycles circuit A 4 9 9 MODES menu NAME FORMAT...

Page 14: ...t alarm 2 alarm_3c nnnnn Current alarm 3 alarm_4c nnnnn Current alarm 4 alarm_5c nnnnn Current alarm 5 alarm_1 nnnnn Current JBus alarm 1 alarm_2 nnnnn Current JBus alarm 2 alarm_3 nnnnn Current JBus...

Page 15: ...tartdow 1 to 7 7 Day of the week 1 Monday startwom 1 to 5 5 Week of the month Winter time stopmon 1 to 12 10 Month stoptdow 1 to 7 7 Day of the week 1 Monday stopwom 1 to 5 5 Week of the month 4 9 18...

Page 16: ...r_deg 16 7 to 16 7 0 C Cooling reset value HEATING RESET oathr_no 10 to 51 7 10 C Outside temperature for no reset oathr_fu 10 to 51 7 10 C Outside temperature for maximum reset dt_hr_no 0 to 13 9 0 C...

Page 17: ...onday Tuesday P3 period 3 7h00 21h00 Wednesday P4 period 4 7h00 17h00 Thursday Friday P5 period 5 7h00 12h00 Saturday P6 period 6 20h00 21h00 Holidays P7 period 7 Not used in this example P8 period 8...

Page 18: ...ending on the programmed periods validated for public holidays Each of these public holiday periods can be displayed and changed with the aid of a sub menu ATTENTION The broadcast function must be act...

Page 19: ...utomatic mode the outdoor temperature determines the heating cooling standby changeover based on the two threshold values configured by the user see RESETCFG menu for cooling and heating mode changeov...

Page 20: ...ents the unit from starting if it is open when the delay at start up has expired This open contact leads to an alarm shut down if the unit is running 5 5 Heat exchanger frost protection The heater for...

Page 21: ...Heating sp 2 closed Heating setpoint 2 5 6 2 Reset Reset means that the active setpoint is modified so that less machine capacity is required in cooling mode the setpoint is increased in heating mode...

Page 22: ...lt prevent ing the use of the heating capacity The other electric heating stages will continue to operate as described above 5 14 Control of a boiler NOTE The control of the electric heating stages or...

Page 23: ...The follower will automatically use the master unit active setpoint The lead machine will be held at its full available capacity for as long as the active capacity on the follower is not zero When th...

Page 24: ...t are active on the unit 6 3 Resetting alarms When the cause of the alarm has been corrected the alarm can be reset depending on the type either automatically on return to normal or manually when acti...

Page 25: ...unication is re established Installation bus fault or defective slave board Depending on the configuration compressor A3 is shut down or circuit B is shut down 16 Co ht Communication loss with the add...

Page 26: ...too low less than 10 C prevents unit start up Automatic when the temperature detected returns to normal or when the mode returns to cooling Operating compressor protection out of range or pressure se...

Page 27: ......

Page 28: ...ompagnie Industrielle d Applications Thermiques S A au capital de 26 728 480 R C S Bourg en Bresse B 545 620 114 Non contractual document With the thought of material improvement always in mind CIAT r...

Reviews: