CIAT PRO-DIALOG+ Instruction Manual Download Page 19

5.1 - Start/stop control

The table below summarises the unit control type and stop or 
go status with regard to the following parameters.

• 

Operating type: this is selected using the start/stop button 
on the front of the user interface.

 

LOFF: local off, L-C: local on, L-SC: local schedule, REM: 
remote, Net.: network, MAST: Master

• 

Remote start/stop contacts: these contacts are used 
when the unit is in remote operating type (Remote). See 
sections 3.6.2 and 3.6.3.

• 

CHIL_S_S: this network command relates to the unit 

start/stop when the unit is in network mode.

• 

Command set to Stop: the unit is halted. 

• 

Command set to Start: the unit runs in accordance with 
schedule 1.

• 

Start/Stop schedule: occupied or unoccupied status of 
the unit as determined by the chiller start/stop program 
(Schedule 1).

• 

Master control type. This parameter is used when the unit 
is the master unit in a two chiller lead/lag arrangement. 
The master control type determines whether the unit is to 
be controlled locally, remotely or through Network (this 

parameter is a Service configuration).

• 

Network emergency shutdown: if this network command 
is activated, it shuts the unit down whatever the active 
operating type.

• 

General alarm: the unit is totally stopped due to failure.

5.2 - Heating/cooling/standby operation

5.2.1 - General

The heating / cooling / standby selection applies to all units. But 
only liquid chillers, controlling a boiler can change over to heating 

mode. Heating/cooling control can be automatic or manual.

In automatic mode the outdoor temperature determines the 
heating/cooling/standby changeover based on the two threshold 

values configured by the user (see RESETCFG menu for cooling 

and heating mode changeover thresholds). 

If the unit is in standby it does not cool or heat, and no com-
pressor can be activated. The diagram below summarises the 
operating principle in automatic mode.

HEATING

STANDBY

COOLING

Outdoor 

temperature

Heating 

threshold*

Cooling 

threshold

*   This threshold does not apply to cooling only units that do not control a 

boiler.

ACTIVE OPERATING TYPE

STATUS OF PARAMETERS

CONTROL 
TYPE

UNIT 
MODE

LOFF

L-ON

L-SC

rEM

Net.

MASt

CHIL_S_S

REMOTE 
START/
STOP 
CONTACT

MASTER 
CONTROL 
TYPE

START/STOP 
SCHEDULE 
MODE

NETWORK 
EMERGENCY 
SHUTDOWN

GENERAL 
ALARM

-

-

-

-

-

-

-

-

-

-

Enable

-

-

Off

-

-

-

-

-

-

-

-

-

-

-

Yes

-

Off

Active

-

-

-

-

-

-

-

-

-

-

-

Local

Off

-

-

Active

-

-

-

-

-

-

Unoccupied

-

-

Local

Off

-

-

-

Active

-

-

-

Off

-

-

-

-

Remote

Off

-

-

-

Active

-

-

-

-

-

Unoccupied

-

-

Remote

Off

-

-

-

-

Active

-

Disable

-

-

-

-

-

Network

Off

-

-

-

-

Active

-

-

-

-

Unoccupied

-

-

Network

Off

-

-

-

-

-

Active

-

-

Local

Unoccupied

-

-

Local

Off

-

-

-

-

-

Active

-

Off

Remote

-

-

-

Remote

Off

-

-

-

-

-

Active

-

-

Remote

Unoccupied

-

-

Remote

Off

-

-

-

-

-

Active

Disable

-

Network

-

-

-

Network

Off

-

-

-

-

-

Active

-

-

Network

Unoccupied

-

-

Network

Off

-

Active

-

-

-

-

-

-

-

-

Disable

No

Local

On

-

-

Active

-

-

-

-

-

-

Occupied

Disable

No

Local

On

-

-

-

Active

-

-

-

On cooling

-

Occupied

Disable

No

Remote

On

-

-

-

Active

-

-

-

On heating

-

Occupied

Disable

No

Remote

On

-

-

-

Active

-

-

-

On auto

-

Occupied

Disable

No

Remote

On

-

-

-

-

Active

-

Enable

-

-

Occupied

Disable

No

Network

On

-

-

-

-

-

Active

-

-

Local

Occupied

Disable

No

Local

On

-

-

-

-

-

Active

-

On cooling

Remote

Occupied

Disable

No

Remote

On

-

-

-

-

-

Active

-

On heating

Remote

Occupied

Disable

No

Remote

On

-

-

-

-

-

Active

-

On auto

Remote

Occupied

Disable

No

Remote

On

-

-

-

-

-

Active

Enable

-

Network

Occupied

Disable

No

Network

On

5 - PRO- CONTROL OPERATION

 

 

EN - 17 

EREBA ACCESS

Summary of Contents for PRO-DIALOG+

Page 1: ...Instruction manual EREBA ACCESS 8 40 kW 11 2016 10183 PRO DIALOG...

Page 2: ......

Page 3: ...3 Password screens 6 4 4 Menu screen characteristics 6 4 5 Data screen or configurable parameter characteristics 6 4 6 Parameter modification 7 4 7 Operating mode screen 7 4 8 Menu tree structure 8 4...

Page 4: ...ty to the unit be shut off before any work is begun Shut off the main power supply at the main circuit breaker or isolator IMPORTANT This equipment conforms to all applicable codes regarding electroma...

Page 5: ...mounted under a metal plate An optional water system temperature sen sor can be used for master slave assembly control in the case of leaving water control In heat pump units a sensor placed on an air...

Page 6: ...24 30A 31A NRCP2 BASE Unit operation relay output J3 CH 25 37 38 NRCP2 BASE Network connection J12 NRCP2 BASE RS 485 series connection Pin 1 signal Pin 2 ground Pin 3 signal Setpoint selection J4 CH 8...

Page 7: ...g cooling contact Open Closed With multiplexing Off On cooling On heating On auto On off contact Open Closed Closed Open Heating cooling contact Open Open Closed Closed NOTE The automatic changeover f...

Page 8: ...cs There are four default screens Each screen shows The unit status its screen number Three displayed parameters LOCAL OFF 1 On the left the unit status on the right the screen number Entering water t...

Page 9: ...on hps1 40 0 C hps2 40 0 C hramp_sp 27 4 C Cooling Setpoint 2 Description of the item framed by the selection cursor The following screen allows modification of a parameter Modify value Screen descrip...

Page 10: ...OLIDY16S HOLIDY02S OCC1P01S OCC1P02S NAVIGATION Password 0 ACCESS ALL USER DEFAULT SCREENS PASSWORD General parameters Temperatures Pressures Setpoint Inputs Outputs Pump status Operating time Unit st...

Page 11: ...emperature OAT nnn n C Outside air temperature CHWSTEMP nnn n C Common master slave temperature SCT_A nnn n C Saturated condensing temperature A SST_A nnn n C Saturated suction temperature A SCT_B nnn...

Page 12: ...B HD_POS_B 0 100 Position variable fan speed controller B RV_B On Off Four way refrigerant valve C_HEATER On Off Heat exchanger and lower coil heater BOILER On Off Boiler output EHS_STEP 0 4 Electric...

Page 13: ...urs Operating hours pump 1 hr_cpum2 nnnnn hours Operating hours pump 2 nb_def_a nnnnn Number of defrost cycles circuit B nb_def_b nnnnn Number of defrost cycles circuit A 4 9 9 MODES menu NAME FORMAT...

Page 14: ...t alarm 2 alarm_3c nnnnn Current alarm 3 alarm_4c nnnnn Current alarm 4 alarm_5c nnnnn Current alarm 5 alarm_1 nnnnn Current JBus alarm 1 alarm_2 nnnnn Current JBus alarm 2 alarm_3 nnnnn Current JBus...

Page 15: ...tartdow 1 to 7 7 Day of the week 1 Monday startwom 1 to 5 5 Week of the month Winter time stopmon 1 to 12 10 Month stoptdow 1 to 7 7 Day of the week 1 Monday stopwom 1 to 5 5 Week of the month 4 9 18...

Page 16: ...r_deg 16 7 to 16 7 0 C Cooling reset value HEATING RESET oathr_no 10 to 51 7 10 C Outside temperature for no reset oathr_fu 10 to 51 7 10 C Outside temperature for maximum reset dt_hr_no 0 to 13 9 0 C...

Page 17: ...onday Tuesday P3 period 3 7h00 21h00 Wednesday P4 period 4 7h00 17h00 Thursday Friday P5 period 5 7h00 12h00 Saturday P6 period 6 20h00 21h00 Holidays P7 period 7 Not used in this example P8 period 8...

Page 18: ...ending on the programmed periods validated for public holidays Each of these public holiday periods can be displayed and changed with the aid of a sub menu ATTENTION The broadcast function must be act...

Page 19: ...utomatic mode the outdoor temperature determines the heating cooling standby changeover based on the two threshold values configured by the user see RESETCFG menu for cooling and heating mode changeov...

Page 20: ...ents the unit from starting if it is open when the delay at start up has expired This open contact leads to an alarm shut down if the unit is running 5 5 Heat exchanger frost protection The heater for...

Page 21: ...Heating sp 2 closed Heating setpoint 2 5 6 2 Reset Reset means that the active setpoint is modified so that less machine capacity is required in cooling mode the setpoint is increased in heating mode...

Page 22: ...lt prevent ing the use of the heating capacity The other electric heating stages will continue to operate as described above 5 14 Control of a boiler NOTE The control of the electric heating stages or...

Page 23: ...The follower will automatically use the master unit active setpoint The lead machine will be held at its full available capacity for as long as the active capacity on the follower is not zero When th...

Page 24: ...t are active on the unit 6 3 Resetting alarms When the cause of the alarm has been corrected the alarm can be reset depending on the type either automatically on return to normal or manually when acti...

Page 25: ...unication is re established Installation bus fault or defective slave board Depending on the configuration compressor A3 is shut down or circuit B is shut down 16 Co ht Communication loss with the add...

Page 26: ...too low less than 10 C prevents unit start up Automatic when the temperature detected returns to normal or when the mode returns to cooling Operating compressor protection out of range or pressure se...

Page 27: ......

Page 28: ...ompagnie Industrielle d Applications Thermiques S A au capital de 26 728 480 R C S Bourg en Bresse B 545 620 114 Non contractual document With the thought of material improvement always in mind CIAT r...

Reviews: